PARK AVENUE N EXTENSION
ADDENDUM NO. 1
City Project Number: TED4003948
CAG-22-265
DATE OF ADDENDUM ISSUE: December 2, 2022
BID DUE DATE: December 13, 2022 (CHANGED FROM DATE IN CALL FOR BIDS)
DATE OF BID OPENING: December 15, 2022 (CHANGED FROM DATE IN CALL FOR BIDS)
NOTE TO ALL PLANHOLDERS:
This Addendum No. 1, containing the following revisions, additions, deletions, and/or clarifications, is
hereby made a part of the Plans and Contract Provisions (Contract Documents) for the above-named
project. Bidders shall take this Addendum into consideration when preparing and submitting their bids.
Bidders shall acknowledge receipt and acceptance of this Addendum No. 1 in the space provided on the
Proposal Signature Page or by signing in the space provided below and submitting the signed addendum
with the bid package. Failure to provide this written acknowledge may result in disqualification of the Bidder’s
submittal.
CALL FOR BIDS
1. Bid Due Date and Bid Opening Date:
• Sealed bids will be received until 1:00 p.m., Tuesday, December 13, 2022, at the lobby Renton
City Hall, 1055 South Grady Way, Renton, WA 98057. All supplemental documents, that are
allowed to be submitted after this date and time, shall be received at the lobby of Renton City
Hall. Sealed bids will be opened and publicly read via Zoom videoconferencing web
application at 1:00 p.m., Thursday, December 15, 2022. Any bids received after the published
bid submittal time cannot be considered and will not be accepted.
INFORMATION AND CHECKLIST FOR BIDDERS
2. Item 10(e) of the Information and Checklist for Bidders is revised as follows:
e. Exhibit C, Contractor Requirements – An Exhibit C-1, executed by the prime Contractor, as
included within these documents, and as required by Appendix H, shall be submitted. No
substitutions will be accepted. Exhibits C-1, fully executed by the prime Contractor and all
Subcontractors, are required prior to entrance upon railroad right of way. Appendix H is
Park Avenue N Extension Addendum No. 1
Page 2 of 2
included as a draft version during this bidding period. The Contracting Agency will replace
Appendix H, and the included Exhibit C-1, with the final and fully executed version after the
bid opening. The final version of Appendix H will include signatures between the
Contracting Agency and BNSF but will have no substantive changes, including no substantive
changes to Exhibit C-1.
SPECIAL PROVISIONS
3. Revise the Special Provision Section 9-26.6(1) Light and Signal Standards (Page 181) as follows:
Section numbering in 9-29.6(1) is modified.
The second paragraph of Section 9.29.6(1)E is revised as follows:
Arterial street decorative roadway luminaire poles and subassemblies for all other areas shall be
per City of Renton Standard Plans 117.1 and 117.3. These poles shall not include the decorative
base cover shown in City of Renton Standard Plan 117.1.
APPENDIX B – STANDARD PLANS (CITY OF RENTON AND WSDOT)
4. City of Renton Public Works Department Standard Plan 300.8 (Steel Pipe Casing) is added to
Appendix B.
ALL OTHER REQUIREMENTS OF THE CONTRACT DOCUMENTS REMAIN IN EFFECT.
Sincerely,
CITY OF RENTON
Hebé C. Bernardo, PMP
Project Manager
Receipt acknowledged, and conditions agreed to this _____ day of ________, 2022
Bidder _______________________________
Signature
WATER MAIN
(CARRIER PIPE)
NOTES:
1.CASING SPACERS SHALL BE "CENTER POSITIONING" TYPE.
2.RUNNER WIDTH SHALL BE MINIMUM 2".
3.RUNNER HEIGHT SHALL BE SIZED TO PROVIDE:
·MINIMUM 3/4" BETWEEN CARRIER PIPE BELL AND CASING PIPE WALL AT ALL TIMES.
·MINIMUM 1" CLEARANCE BETWEEN RUNNERS AND TOP OF CASING WALL TO PREVENT JAMMING DURING INSTALLATION.
4.STEEL CASING DIAMETERS ARE "OUTSIDE DIAMETER" FOR 16" AND LARGER.
5.PROVIDE SHOP-APPLIED ANTI-CORROSIVE COATING ON CASING EXTERIOR CONFORMING TO AWWA C210. TNEMEC HI-BUILD TNEME-TAR
SERIES 46H-413 OR EQUAL. MINIMUM COATING THICKNESS 16 MILS DFT, MAXIMUM COATING THICKNESS NOT TO EXCEED
MANUFACTURER'S RECOMMENDATIONS.
CASING END SEAL WITH STAINLESS STEEL BANDS
(SEE APPROVED MATERIALS LIST), EACH END
BLACK STEEL CASING PIPE
ONE SPACER SHALL BE PLACED ON THE SPIGOT
END OF EACH SEGMENT AT THE LINE MARKING
THE LIMIT OF INSERTION INTO THE BELL. WHEN
THE JOINT IS COMPLETE, THE SPACER SHALL BE
IN CONTACT WITH THE BELL OF THE JOINT SO
THAT THE SPACER PUSHES THE JOINT AND
RELIEVES COMPRESSION WITHIN THE JOINT
END SPACER, 12" MAX
FROM END OF CASING
CARRIER PIPE DIAMETER 4"6"8"10"12"16"
CASING PIPE DIAMETER
(PUSH-ON JOINT CARRIER PIPE)10"12"14"16"20"26"
CASING PIPE DIAMETER
(MJ/MEGALUG CARRIER PIPE)14"16"18"20"24"30"
CASING PIPE WALL THICKNESS SCHEDULE 20 OR GREATER
SPACER BAND WIDTH 8"
CASING SPACER
SEPARATION
10' MAX ON CENTER
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
STEEL PIPE CASING
STD. PLAN - 300.8