SURFACE MOUNTING PANEL SCHEDULE
65,000 AIC
No. MDP
LOCATION: EXTERIOR
SERVING: SONICS
120/208 VOLTS 3PHASE 4WIRE
600 AMPS WITH 600 MAIN BREAKER
COT
N0.
LOAD DESCRIPTION
KVA
TRIP TRIP
AMPS AMPS
KVA
LOAD DESCRIPTION
COT
N0.
1
PANEL A
16.80
225
3
7a57
3
2Z5Z
7 3
125
3
100
3
200
3
100
3
30/
i2
3QL
2
3QZ
2
15L
2
29Z
2
2QL
2
39Z
2
125
3
20
20
3QZ
2
SPARE
2
3
4
5
PANEL B
SPARE
6
8
7
4.50
9
SPARE
10
11
12
13
PANEL C
.50
SPARE
14
16
15
17
SPARE
18
19
SPARE
20
21
23
SPARE
22
24
25
SPARE
SPARE
26
27
28
29
31
SPARE
SPARE
30
32
33
34
35
SPARE
36
37
39
SPARE
SPARE
SPARE
38
40
41
42
REMARKS: SERVICE ENTRANCE RATED.
CONNECTED LOAD: 28.3 KVA 79 AMPS
DEMAND LOAD: 30.2 KVA 84 AMPS
* PROVIDE HACR BREAKER
** PROVIDE GFCI BREAKER
PROVIDE HANDLE TIES FOR ALL MULTI -CIRCUIT HOMERUNS SHARING A NEUTRAL PER THE NATIONAL ELECTRIC CODE ARTICLE 210.4
MULTIWIRE BRANCH CIRCUITS, PART (B) DISCONNECTING MEANS. DRAWINGS ARE DIAGRAMMATIC. WHERE THE CONTRACTOR
MODIFIES THE CIRCUITING, THE CONTRACTOR SHALL PROVIDE AN INDIVIDUAL NEUTRAL PER CIRCUIT, MULTI -POLE CIRCUIT BREAKERS,
OR CIRCUIT BREAKER HANDLE TIE TO MEET THE NEC ARTICLE. ALL COSTS ASSOCIATED WITH MODIFICATIONS SHALL BE INCLUDED IN
THE CONTRACTOR'S BID.
PANEL MDP LOAD CALCULATIONS
SERVICE KVA LOAD
FACTOR
NEC REF. DEMAND LOAD
LIGHTING 7.76
X
1.25
220.19(A)(1) = 9.70
RECEPTS TO 10KW -
X
1.00
220.44 = -
RECEPTS OVER 10KW
X
0.50
220.44 = -
MOTORS (LARGEST)
X
1.25
430.24 = -
MOTORS
X
1.00
430.24 = -
KITCHEN EQUIP.
X
0.65
220.56 = -
WELDERS -
X
1.00
630.11(B) _ -
AIR CONDITIONING
X
1.00
220.50 = -
ELECTRIC HEAT -
X
1.00
220.51 = -
MISCELLANEOUS 20.54
X
1.00
= 20.54
TOTAL CONNECTED 28.3 KVA
(79 AMPS)
METER
120/208V, 3P/600 AMP
ELECTRICAL SERVICE FROM
POWER COMPANY
TRANSFORMER EC TO
PROVIDE FULL
COORDINATION WITH
U TI LI TY.
C.T. CABINET
O BY UTILITY CO.
2 SETS -
(4) 350 KCMIL THWN,
4" CONDUITS
TOTAL DEMAND 30.2 KVA
(84 AMPS)
25,150A
MDP
120/208V, 3
PHASE,
65 KAIC, 42
SPACE
DISTRIBUTION
PANEL "MDP"
WITH 600 A
MAIN CIRCUIT
BREAKER
NEMA 3R
2 SETS -
(4) 350 KCMIL THWN, #
2/0 CU GROUND =
4" CONDUITS
FLUSH MOUNTING PANEL SCHEDULE
22,000 AIC
No. A
LOCATION: KITCHEN
SERVING: SONICS
120/208 VOLTS 3PHASE 4WIRE
225 AMPS WITH MAIN LUGS
COT
N0.
LOAD DESCRIPTION
KVA
TRIP TRIP
AMPS AMPS
KVA
LOAD DESCRIPTION
COT
N0.
1
CANOPY LIGHTING
1.28
20
20
30
30
20
11
20
30
2
20
J
20 J
20
l
20
.80
CANOPY PAYS
2
3
SPARE
.80
CANOPY MENU
4
5
CANOPY NIGHT LIGHTING
CANOPY STAR STALL LED
.23
SPARE
SIGNAGE
6
8
7
.60
1.00
9
CANOPY STAR STALL LED
.10
1.00
SIGNAGE
10
11
SPARE
SPARE
12
13
SPARE
14
16
15
CANOPY & TOWER LED
1.00
17
TOWER SIGN
1.20
18
19
TOWER SIGN
1.20
20
21
TOWER SIGN
1.20
22
24
23
TOWER SIGN
1.20
25
TOWER LIGHTING
.65
26
27
SPARE
28
29
SPARE
SPARE
30
32
31
33
READER BOARD SIGN
3.84
34
35
36
37
POLE SIGN
ORDER PEDESTAL
1.20
38
40
39
1.00
41
MENU BOARD
1.00
42
43
PREVIEW BOARD
1.00
44
45
ORDER PEDESTAL
1.00
46
48
47
MENU BOARD
1.00
49
PREVIEW BOARD
1.00
50
51
SPARE
52
53
1 SPARE
SPARE
54
REMARKS:.
CONNECTED LOAD: 16.8 KVA 47 AMPS
DEMAND LOAD: 17.1 KVA 48 AMPS
* PROVIDE GFI BREAKER
PROVIDE HANDLE TIES FOR ALL MULTI -CIRCUIT HOMERUNS SHARING A NEUTRAL PER THE NATIONAL ELECTRIC CODE ARTICLE 210.4
MULTIWIRE BRANCH CIRCUITS, PART (B) DISCONNECTING MEANS. DRAWINGS ARE DIAGRAMMATIC. WHERE THE CONTRACTOR
MODIFIES THE CIRCUITING, THE CONTRACTOR SHALL PROVIDE AN INDIVIDUAL NEUTRAL PER CIRCUIT, MULTI -POLE CIRCUIT BREAKERS,
OR CIRCUIT BREAKER HANDLE TIE TO MEET THE NEC ARTICLE. ALL COSTS ASSOCIATED WITH MODIFICATIONS SHALL BE INCLUDED IN
THE CONTRACTOR'S BID.
PANEL A LOAD CALCULATIONS
SERVICE
KVA LOAD
FACTOR
NEC REF. DEMAND LOAD
LIGHTING
3.26 X
1.25
220.19(A)(1) = 4.08
RECEPTS TO 10KW
- X
1.00
220.44 = -
RECEPTS OVER 10KW
- X
0.50
220.44 = -
MOTORS (LARGEST)
X
1.25
430.24 =
MOTORS
- X
1.00
430.24 = -
KITCHEN EQUIP.
X
1.00
220.56 =
WELDERS
- X
1.00
630.11(B) _ -
AIR CONDITIONING
X
1.00
220.50 =
ELECTRIC HEAT
- X
1.00
220.51 = -
MISCELLANEOUS
20.04 X
1.00
= 20.04
TOTAL CONNECTED 16.8 KVA
(47 AMPS)
PROVIDE 65K/22K SERIES RATINGS FROM
BREAKERS IN MDP FEEDING PANELS A, B, & C.
EXTERIOR I INTERIOR
21,796A
PANEL "A"
120/208V.
3PH., 4W.
ISOLATED GRID.
225A.
M.L.O.
FLUSH MTD.
NEMA 1
(4) # 1 /0 CU THWN
(1) # 6 CU GROUND
(1) # 6 CU IG GROUND
(1) 2" CONDUIT
SEE GROUNDING DETAIL THIS SHEET
600A ELECTRICAL RISER DIAGRAM
SCALE: N.T.S.
20,955A
PANEL "B"
120/208V
3PH., 4W.
225A.
M.L.O.
FLUSH MTD.
NEMA 1
SECTION 1
(4) # 1 /0 CU TH WN
(1) # 6 CU GROUND
(1) 2" CONDUIT
TOTAL DEMAND 17.1 KVA
(48 AMPS)
19,340A
PANEL "C"
120/208V
3PH., 4W.
225A.
M.L.O.
FLUSH MTD.
NEMA 1
NO. REVISION
J
LIGHTING
CONTACTORS.
SEE DETAIL ON
E2.01 FOR
ADDITIONAL
INFORMATION.
FLUSH MOUNTING PANEL SCHEDULE
22,000 AIC
No. B
LOCATION: KITCHEN
SERVING: SONICS
120/208 VOLTS 3PHASE 4WIRE
225 AMPS WITH MAIN LUGS
COT
N0.
LOAD DESCRIPTION
KVA
TRIP TRIP
AMPS AMPS
KVA
LOAD DESCRIPTION
COT
N0.
1
SPARE
��3
30
3
20
20
20
30
2
20
30
3
30
2 �It
!30
73
20
30
2
20
20
60
3
-
20
20
2QZ
2
20
2
60
3
-
SPARE
2
3
4
5
SPARE
SPARE
6
8
7
9
10
11
12
13
SPARE
if
SPARE
14
15
16
17
18
19
SPARE
20
21
22
23
SPARE
SPARE
24
25
SPARE
SPARE
26
27
1.50
POLE MOUNTED LIGHTS
28
29
30
31
SPARE
3.00
POLE MOUNTED LIGHTS
32
33
34
35
SPARE
SPARE
36
37
38
39
40
41
SPARE
-
42
REMARKS:
CONNECTED LOAD: 4.5 KVA 13 AMPS
DEMAND LOAD: 5.6 KVA 16 AMPS
* SHUNT TRIP BREAKER
PROVIDE HANDLE TIES FOR ALL MULTI CIRCUIT HOMERUNS SHARING A NEUTRAL PER THE NATIONAL ELECTRIC CODE ARTICLE 210.4
MULTIWIRE BRANCH CIRCUITS, PART (B) DISCONNECTING MEANS. DRAWINGS ARE DIAGRAMMATIC. WHERE THE CONTRACTOR
MODIFIES THE CIRCUITING, THE CONTRACTOR SHALL PROVIDE AN INDIVIDUAL NEUTRAL PER CIRCUIT, MULTI -POLE CIRCUIT BREAKERS,
OR CIRCUIT BREAKER HANDLE TIE TO MEET THE NEC ARTICLE. ALL COSTS ASSOCIATED WITH MODIFICATIONS SHALL BE INCLUDED IN
THE CONTRACTOR'S BID.
ELECTRICAL CONTRACTOR MUST
PROVIDE EQUIPMENT CAPABLE OF A
SERIES FAULT CURRENT RATING OF
NOT LESS THAN 65K AIC.
PROVIDE EQUIPMENT MANUFACTURERS
SUBMITTAL DATA SHOWING COMBINED
RATING OF FEEDER CIRCUIT BREAKER
AT MDP AND DOWN STREAM
BREAKERS AT PANELS "A", "B" &
„C„
(4) # 1 CU THWN
(1) # 6 CU GROUND
(1) 1-1/2" CONDUIT
*
FLUSH MOUNTING PANEL SCHEDULE
22,000 AIC
No. C
LOCATION: KITCHEN
SERVING: SONICS
120/208 VOLTS 3PHASE 4WIRE
225 AMPS WITH MAIN LUGS
COT
N0.
LOAD DESCRIPTION
KVA
TRIP TRIP
AMPS AMPS
KVA
LOAD DESCRIPTION
COT
N0.
1
SPARE
20
2
20
20
20
�2Z
15
2
20
�'2/
20
2
20
20
20
l
l
20
20
2
20
20
SPARE
2
3
4
5
6
8
7
9
10
11
12
13
15
14
16
17
18
19
20
21
23
22
24
25
26
27
28
29
30
32
31
33
34
35
36
37
SPARE
.50
38
40
39
BACKFLOW
DEVICE
41
SPARE
SPARE
42
REMARKS:
L
CONNECTED LOAD: .5 KVA 1 AMPS
DEMAND LOAD: .5 KVA 1 AMPS
PROVIDE HANDLE TIES FOR ALL MULTI -CIRCUIT HOMERUNS SHARING A NEUTRAL PER THE NATIONAL ELECTRIC CODE ARTICLE 210.4
MULTIWIRE BRANCH CIRCUITS, PART (B) DISCONNECTING MEANS. DRAWINGS ARE DIAGRAMMATIC. WHERE THE CONTRACTOR
MODIFIES THE CIRCUITING, THE CONTRACTOR SHALL PROVIDE AN INDIVIDUAL NEUTRAL PER CIRCUIT, MULTI -POLE CIRCUIT BREAKERS,
OR CIRCUIT BREAKER HANDLE TIE TO MEET THE NEC ARTICLE. ALL COSTS ASSOCIATED WITH MODIFICATIONS SHALL BE INCLUDED IN
THE CONTRACTOR'S BID.
PANEL B LOAD CALCULATIONS PANEL C LOAD CALCULATIONS
SERVICE
KVA LOAD
FACTOR
NEC REF. DEMAND LOAD
SERVICE KVA LOAD
FACTOR
NEC REF. DEMAND LOAD
LIGHTING
4.50 X
1.25
220.19(A)(1) = 5.63
LIGHTING -
X
1.25
220.19(A)(1) _
RECEPTS TO 10KW
- X
1.00
220.44 = -
RECEPTS TO 10KW -
X
1.00
220.44 = -
RECEPTS OVER 10KW
- X
0.50
220.44 =
RECEPTS OVER 10KW -
X
0.50
220.44 =
MOTORS (LARGEST)
- X
1.25
430.24 =
MOTORS (LARGEST) -
X
1.25
430.24 =
MOTORS
- X
1.00
430.24 =
MOTORS -
X
1.00
430.24 =
KITCHEN EQUIP.
- X
0.65
220.56 =
KITCHEN EQUIP. -
X
0.65
220.56 =
WELDERS
- X
1.00
630.11(B) _ -
WELDERS -
X
1.00
630.11(B) _ -
AIR CONDITIONING
- X
1.00
220.50 =
AIR CONDITIONING -
X
1.00
220.50 =
ELECTRIC HEAT
- X
1.00
220.51 = -
ELECTRIC HEAT -
X
1.00
220.51 = -
MISCELLANEOUS
- X
1.00
=
MISCELLANEOUS .50
X
1.00
= .50
TOTAL CONNECTED 4.5 KVA
(13 AMPS)
METAL FRAME OF BUILDING
CONNECTIONS MADE WITHIN 5'-0"
OF POINT OF ENTRANCE OF PIPE
#2/0 AWG CU
* size per table 250.66, 3/0 max
#6 AWG CU MIN.
0" x 10'-0" COPPE
CLAD GROUND ROD
TOTAL DEMAND 5.6 KVA
(16 AMPS)
Ou0
D
TOTAL CONNECTED .5 KVA
(1 AMPS)
MAIN SERVICE EQUIPMENT
#2/0 AWG CU GROUNDING
ELECTRODE CONDUCTOR
* size per table 250.66, 3/0 max
AL WATER PIPE
/ CONCRETE ENCASED ELECTRODE
�- AT LEAST 20'-0" LONG (#4 AWG
AWG CU. CU MIN. OR D" DIA. MIN. STEEL
REINFORCING BAR)
0
SIZED NO SMALLER THAN #2 AWG CU MIN. GROUND RING AT
THE GROUND RING LEAST 20'-0" LONG
i3� GROUNDING ELECTRODE DETAIL
SCALE: N.T.S.
TOTAL DEMAND .5 KVA
(1 AMPS)
R-3929017.
APPROVED FOR CONSTRUCTION
SUBJECT TO ERRORS AND OMISSIONS
O
N
N
O
O
O
T
a
J
BY:
DATE:
BY:
DATE:
CROSS ENGINEERS, INC
BY:
DATE:
6509 6th Avenue Phone: (253) 759-0118
BY:
DATE:
_U
Z
Tacoma, WA 98406 Job Number: 17-046
O
info@crossengineers.com
0
SURVI YI D_
SCALE:
AS SHOWN
VERTICAL: DAVD 1988
HORIZONTAL NAD 1983/1991
C T Y O
RENTON SONICS
DATE:
4.28.2017
Z
DI SlGfdl li
B.JA
FIELDBOOK:
R E N TO N
PACE
Z
DRA,CK
BJA
POWER RISER DIAGRAM /
DRAWING N0:
EO.0 1
ON= INC-
U
AI FI SGAIF
IF VOT ONE NCH
°ABM
Planning/Building/Public works Dept.
PANEL SCHEDULES
Z
W
CH ARID
_jv
DA E
APPR
SCALE ACCORDINGY
Ir
APPROVI D.
SHEET. OF
15 16