HomeMy WebLinkAboutS-419301.1
^n
V`
N
1
CL
SE 7 /4 OF THE N/W 7 /4, SEC. 10, TWP. 23 N., RGE. 5 E., W.M.
FIND 4"X4" CONC.
MON WITH
FIND 4"X4"
CONC. MON WITH 2" BRASS DISC LOCATED
7-21 -20 FIND 4"X4" CONC.
MON WITH
2" BRASS
DISC LOCATED
2" BRASS DISC LOCATED
7-21-ED
_
79 _ z
7-21-20
_
479.
7s
_ - -ST
9 s
L=1ss. oz S
89°51 03 E 130.00
Cc
0 i
CQ
FIND 4"X4" CONC. MON WITH
2"
o
BRASS DISC LOCATED 7-21-20
0
00LO
to
co
0
30' o
10
0
0
N89°51'03"W
178.00 BM
"A"
24'
1
CD
CD
o
o
Ln
/
PROJECT
U�
co
LO
1 0
w
SITE
w
w
/
o
00
Q
00
P
CD
/
0
z
o
W
1
N89°51'03"W
178.00
U
co
j
� I
Mo �
0
N FOUND MON IN CASE
1 1 /2" BRASS DISK
WITH PUNCH MARK CALC CTR OF
CITY OF RENTON #1848 SECTION NOT FND
00 N: 1 83691 .4502
E: 1 31 1 377.410 __
0 - -
I FOUND MON IN CASE
2" BRASS DISK WITH
PUNCH MARK
CITY OF RENTON #1849
N: 183615.5055
E: 1313987.638
HORIZONTAL CONTROL DIAGRAM.
1" = 60'
CONDITIONS OFAPPROVAL
0
I�
ILO
00 30' 0
0
THE HARDY SHORT PLAT, F/LE NO.. LUA21-000169, SHPL-A, AS DEPICTED /N EXHIBIT 2, IS APPROVED AND /S SUBJECT TO THE FOLLOWING
CONDITIONS.-
1. THE APPLICANT SHALL SUBMIT A REVISED SHORT PLAT LA POUT W/TH THE C/V/L CONSTRUCAON PERMIT APPL/CAT/ON THAT PROVIDES TRACT A
WITH A W/OTH OF 24.5 FEET THAT WOULD INCLUDE 16-FOOT W/DE PAINED DRIVf'AA Y, A 6-INCH INERT/CAL CURB, AND 8-FOOT WIDE PLANTER
STRIP AND TO PROVIDE LOT 2 W/TH A WIDTH OF 61 FEET. THE REVISED SHORT PLAT LA POUT SHALL BE REVIEWED AND APPROVED BY THE
CURRENT PLANNING PROJECT MANAGER PR/OR TO PERM/T ISSUANCE.
2. A DENOL/T/ON PERMIT SHALL BE OBTAINED AND THE REMOVAL OF EX/SANG STRUC7URES AND ALL REWIRED INSPECTORS BE COMPLETED PR/OR
TO THE RECORDING OF THE SHORT PLAT.
3. A DETAILED LANDSCAPE PLAN SHALL BE PROVIDED AT THE AUE OF CONSTRUCT/ON PERM/T REVIEW. THE DETAILED LANDSCAPE PLAN SHALL
INCLUDE AN 8-FOOT WIDE LANDSCAPE STRIP WITH TREES, SHRUBS AND GROUNDCOW_R BETWEEN THE SHARED DRIVf'HA Y AND SOUTH PROPERTY
LINE ALONG THE FULL LENGTH OF THE SHARED DR/VEW,4 Y TRACT (TRACT A) THE LANDSCAPE STRIP BETWEEN THE SHARED DR/VEWA Y AND
SOUTH PROPERTY LINE SHALL BE SEPARA TED WITH A VERACAL CURB. A TOTAL OF 2 TREES SHALL BE PROVIDED W/TH/N THE FRONT YARD OF
LOT 1. STREET TREES SHALL BE SELECTED FROM THE CITYS APPROVED STREET LIST AND SPACING GUIDELINES OR OTHERWISE APPROVED BY THE
CITY ARBOR/ST. THE DETAILED LANDSCAPE PLAN SHALL BE SUBMITTED WITH THE CURRENT PLANNING PROJECT MANAGER FOR REVIEW AND
APPROVAL.
4. A FINAL TREE RETENAON PLAN SHALL BE SUBMITTED AT THE AME OF CONSTRUCAON PERMIT REVIEW. THE FINAL TREE RETENAON PLAN SHALL
INCLUDE TREE PROTECTION MEASURES, FOR TREES TO BE RETAINED ON AND OFF SITE, THE BE IMPLEMENTED DURING CONSTRUCAON OF THE
SHORT PLAT AND THE FUTURE HOME IN ACCORDANCE WITH RUC 4-4-130H.9. THE FINAL TREE PROTECTON PLAN SHALL BE SUBMITTED TO THE
CURRENT PLANNING PROJECT MANAGER FOR REVIEW AND APPROVAL PR/OR TO PERMIT ISSUANCE.
5. AN ARBOR/ST SHALL BE PRESENT ONS/TE DURING THE INS TALLA AON OF THE STORM L/NE TO ENSURE PRO TECTON OF ON AND OFF S/TE TREES
DURING CONSTRUCAON.
6. DR/VEWA Y ACCESS FOR LOT 2 SHALL BE PROVIDED OFF OF THE SHARED DRIVEWA Y TRACT (TRACT A) A NOTE TO THIS EFFECT SHALL BE SHOWN
ON THE FINAL SHORT PLAT SUBMITTAL TO BE REVIEWED AND APPROVED BY THE CURRENT PLANNING PROJECT MANAGER AND RECORDED ON THE
FACE OF THE FINAL SHORT PLA T.
7. A SHARED MAINTENANCE AGREEMENT SHALL BE ESTABL/SHED FOR THE MAINTENANCE OF COMMON /UPROVEUENTS WITH/N THE SUBD/V/S/ON,
INCLUDING, BUT NOT L/U/TED TO THE STORMWATER FACILITY AND SHARED DRIVEWAY TRACT (TRACT A) A NOTE TO THIS EFFECT SHALL BE
RECORDED ON THE FACE OF THE SHORT PLAT.
8. BOTH HOMES SHALL BE CONSTRUCTED WITH APPROVED FIRE SPRINKLER SYSTEMS. A NOTE TO THIS EFFECT SHALL BE SHOWN ON THE FINAL
SHORT PLAT SUBMITTAL TO SE REVIEWED AND APPROVED BY THE CURRENT PLANNING PROJECT MANAGER AND RECORDED ON THE FACE OF THE
FINAL SHORT PLAT.
9. THE FRONT ENTRY FOR THE NEW HOME TO BE CONSTRUCTED ON PROPOSED LOT 2 SHALL BE REQUIRED TO FACE TO THE EAST TO F/ELD
A VE NE.
C
RT
ClVIL CONSTRUCT/ON PERM/T
r'/TY nF RFIV TnA1 W,4 SH/lVn TnIV
RECORD DRA WINGS
SITE INFORMA T/ON
ADDRESS.• 857 FIELD A Vf- NE, RENTON WA 98059
PARCEL NO. 1437650040
PROPERTY OWNER- ALEXANDER WENZL
SITE INFORMA TION
✓UR/SD/CT/ON.-
PARCEL NUMBERS -
GROSS SITE AREA:
EX/STING ZONING:
VOLUME
PROPOSED NUMBER OF LOTS
PROPOSED SQUARE FOOTAGE /N
EACH LOT
SQUARE FOOTAGE OF LAND /N STREET
AND OPEN SPACE
SQUARE FOOTAGE OF LAND /N
PUBL/CL Y DEDICATED STREET
SQUARE FOOTAGE OF LAND /N
PR/VA TE ACCESS EASEMENT/TRACT
DENSITY PROPOSED AND DENSITY
PERMITTED BY CODE
CITY OF RENTON
14.37650040
15,130 SF (0.35 AC)
R-8
CUT 90 CY
FILL J40 CY
NET 250 CY (CUT)
2
LOT 1 7,565 SF
LOT 2 5,264 SF
2,277 SF
170 SF
2,132 SF
GROSS DENSITY 5.76 DU/AC (2 LOTS/0.347 AC)
NET DENSITY 5.86 DU/AC (2 LOTS/0.341 AC)
BASIS OF BEARINGS
BASIS OF BEARINGS /S NAD83191 (CITY OF RENTON)
NA VD 88
LEGAL DESCRIPTION
LOT 4, CASTLEWOOD RANCHETTES, ACCORDING TO THE PLAT THEREFORE RECORDED /N
VOLUME 129 OF PLATS, PAGE 13, IN KING COUNTY, WASH/NGTON
BENCHMARK
SOURCE • GPS OBSERVA AON NORTH ZONE
DA TUM.• NA VD88
C/TY OF RENTON CONTROL POINT 1848 1 1/2" BRASS DISC W/TH PUNCH MARK ON A 4'X4"
CONCRETE POST DOWN 0.4' IN CASE AT THE CONSTRUCTED INTERSECT/ON OF NE 87H COURT AND
UN/ON A Vf-NUE NE
BENCHMARK 'A "
SET PK 13.0'f/- EAST OF NORTHEAST CORNER OF SUBJECT PROPERTY.
ELEVA T/ON = 472.18 FEET
BENCHMARK 19"'
SET PK 8.0'f/- NORTH AND 14.0'4/- EAST OF THE SOUTHEAST CORNER OF SUBJECT PROPERTY.
ELEVA AON = 471.81 FEET
SURVEYOR'S NOTES
1. INS TRUMENTA T/ON FOR THIS SURVf Y WAS A TOPCON 1 SECOND TOTAL STA T/ON AND A
SPECTRA SP80 DPS UNIT. PROCEDURES USED /N THIS SURVEY WERE FIELD TRAVERSE,
MEETING OR EXCEED/NG STANDARDS SET BY HA 332-130-090.
2. THE /NFORUA AON DEPICTED ON THIS MAP REPRESENTS THE RESUL TS OF A SURVf-Y MADE
IN ✓UL Y, 2020, AND SHOWS THE GENERAL CONDITION EXISTING AT THAT AUE.
3. CONTOURS DERtVf-D FROM FIELD OBSERVATIONS.
4. THE UNDERGROUND UAL/AES SHOWN HERON ARE BASED UPON PA/NTUARKS AND F/ELD
OBSERVATIONS AND ARE NOT GUARANTEED TO BE CORRECT, NOR ALL /NCLUSIVf. ALL
UAL/AES MUST BE VfR/F/ED PR/OR TO CONSTRUCT/ON. CALL 1- 800- 424 - 5555 FOR
UAL/TY LOCATORS.
DESIGN STANDARDS
M/N LOT AREA:
5, 000 SF (ONE LOT MA Y BE 4,500 SF)
M/N LOT W/D171-
50' 60' CORNER
M/N LOT D6,0N.-
80'
FRONT SETBACK.•
20' (SECONDARY FRONT YARD 15)
SIDE YARD SETBACK-
5'
REAR YARD SETBACK-
20'
MAX HEIGHT
30'
MAX IMPERVIOUS-
659
MAX BLDG. COVERAGE.'
509
UTILITY CONTACTS
ELECTRICITY/NATURAL GAS.•
PUGET SOUND ENERGY
P 0 BOX 97034
BELLEV!Jf,, WASHINGTON 98009
1-800-.321-7890
WATER.•
KING COUNTY WA TER D/STR/CT 190
15606 SE 128TH STREET
RENTON, WASHINGTON 98059
425-255-9600
CABLE
COUCAST
14870 NE 95TH STREET
REDMOND, WASHINGTON 98052
1-877-824-2288
TESC SUPERVISOR
T.B.D.
SHEET INDEX
C/VlL PLANS.•
C1. 01
ATLE SHEET / HORIZONTAL & VERACAL CONTROL PLAN
C1.02
SITE & COMPOSITE UTILITY PLAN
C2.01
TEMPORARY EROSION & SEDIMENT CONTROL PLAN
C2.31
TEMPORARY EROSION & SEDIMENT CONTROL DETAILS & NOTES
C3 01
ROAD & GRADING PLAN
C3.31
ROAD DETAILS
C4.01
UALITY PLAN
C4.21
UALITY PLAN & PROFILE
C4.22
UALITY PROFILE
C4.31
DETENAON VAULT DETAILS
C4.32
UALITY DETAILS
C4.33
UALITY DETAILS
LANDSCAPE PLANS.•
L 1.01
TREE RETENAON PLAN
L2.01
LANDSCAPE PLAN
L2.31
LANDSCAPE DETAILS AND NOTES
PERMIT NUMBER
CIVIL CONSTRUCAON.• C21-004477
4-26-2023
SURVEYED: XXX SCALE:
DESIGNED: SHY
DRAWN: SES
ONE INCH
CHECKED: SHY AT FULL SCALE
IF NOT ONE INCH
NO. REVISION BY DATE AP P R APPROVED: SHY
SCALE ACCORDINGLY
E 10TH S
zz
J
CL
J J
D >
o o
z
w
Z
Q
7
O
_
NE 10TH ST
w
z
E 9TH ST
U
E g� ST
o
P�NE.71T;
NE 8TH P
NE 8THSTSIT
w
J
o
a
w_
o
m
NE 7TH P
J
D
O
Uj
=
z
y
v
a
z
>
r
m
y
NE 6TH
�
v
O
VICINITY MAP
NOT TO SCALE
STORM LEGEND
STORM PIPE
® STORM STRUCTURE (W/INLET PROTECTON)
STORM SERVICE
STORM PIPE FLOW ARROW
STORM VAUL T EXTERIOR WALL
- - - - - - - STORM VAULT INTERIOR WALL
STORM VAUL T WATER LEVEL
STORM EASEMENT
EXISTNG STORM PIPE
EXISTNG STORM PROFILE
SEWER LEGEND
0 SPIER PIPE
SEVER STRUCTURE
SEVER SERVICE
SEIER PIPE FLOW ARROW
SEHER EASEMENT
EXISTNG SEHER PIPE
EXISTNG SEHER PIPE PROFILE
WA TER LEGEND
T TT WATER METER
- - WATER EASEMENT
EXIS17NG WATER PIPE
EXISTNG WATER PROFILE
ROAD LEGEND
CURB LINES
GUTTER LINES
ASPHAL T ROAD
0
ASPHAL T ROAD PATTERN
SIDEWALK
SIDEWALK PATTERN
DRII/_WA Y
DRII/_WA Y PATTERN
GRA I/EL
GRA I/EL PATTERN
ADA RAMP
ADA RAMP PATTERN
ROAD MARKINGS
- -
SAWCUT
01/ERLAY
- - - -
ROAD EASEMENT
SURFACE LEGEND
190
EXISTNG GROUND SURFACE TEXT (CONTOUR LABELS)
EXISTNG GROUND CONTOUR UA✓OR
EXISTNG GROUND CONTOUR UINOR
FINISH GRADE SURFACE TEXT (CONTOUR LABELS)
FINISH GRADE CONTOUR UA✓OR
FINISH GRADE CONTOUR UINOR
EROSION CONTROL LEGEND
CLEARING LIMITS LINE
CLEARING LIMITS LINE
xxx- SILT FENCE
TREE RETENAON FENCE
- 0- 0- 0- CONSTRUCAON FENCE
PROJECT NO. 21019
CIVIL ENGINEERING
LANDSCAPE ARCHITECTURE
PLANNING
�zw�
DESIGN SURVEYING
12100 NE 195th St, Suite 300 Bothell, Washington 98011 425.885.7877
com
HORIZV ONTAL: NAD 1983/1991 CITY OF
RENTON
DATUM
Planning/Building/Public Works Dept.
S-419301
RECORD DRAWING R-419301
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
TITLE SHEET/HORIZONTAL &
VERTICAL CONTROL PLAN
NOV 2021
PAGE:
Cl. Ol
T: ' OF: 15