HomeMy WebLinkAboutRS_Resubmittal_1_Engineers_Redline_Responses_180911_v2
1915 Dayton Ave NE, Renton, WA 98056
Phone: 206.200.8764
Email: elreng33@gmail.com
Date: 9/11/2018
To: Alan D. Findlay, PE
Building Plan Reviewer
City of Renton
From: Eric L. Rice, PE
ELR Engineering
Subject: Response to plan review letter dated 8/29/18
Permit ID: B18004109
Plan ID: 2335 lot 10
Project address: 908 Chelan Ave NE
Renton, WA
Attachments: 4 pages
Reference: Revised S-2, S-0, SD-1, SD-2 and new S-3
The purpose of this letter is to respond to the structural items (general and lateral) in the plan review referenced
above as follows:
3. a. S-0 is revised as per plan review comment.
b. S-0 is revised as per plan review comment.
c. S-0 is revised as per plan review comment.
d. S-0 is revised as per plan review comment.
4. Detail 6/SD-1 is revised as per plan review comment.
5. Detail 6/SD-1 and detail 23/SD-2 are revised as per plan review comment.
6. Detail 23/SD-2 and detail 6/SD-1 are revised as per plan review comment.
7. S-2 is revised as per plan review comment. A new sheet S-3 has been generated to meet the requirements of
the plan review comment.
8. There are no 2W3 nor 2W2 shear walls on this project. However, the shear wall schedules on S-2 and S-3
are revised to eliminate all unused shear wall designations in the shear wall schedule. Only shear walls
used on this project are shown on the shear wall schedule.
9. S-2 is revised to specify HF2 studs as intended. See attached calculations for the combined loading
condition.
10. See response to 8 above.
Please call or email with any questions.
Eric L. Rice, PE
ELR Engineering
Eric L. Rice 09/11/18
Eric L. Rice08/08/17
D08-053
B18004109
V2
APPROVEDBUILDING DIVISION
THIS SET OF APPROVED PLANS MUST BE ON THE JOB AT ALLTIMES DURING CONSTRUCTION. THIS BUILDING IS NOT TO BEOCCUPIED UNTIL AFTER FINAL INSPECTION BY THE RENTONBUILDING DIVISION AND RECEIPT OF CERTIFICATE OFOCCUPANCY.
APPROVAL SHALL NOT BE CONSTRUED AS THE AUTHORITY TOVIOLATE OR CANCEL ANY PROVISIONS OF CODES, ORDINANCES,OR OTHER REGULATIONS ENFORCED BY THIS CITY.
DATE: 10/18/2018
ASCE 7-10 Wind Forces Chpt 28, Pt2 & Chpt 30, Pt2
Licensee : ELR EngineeringLic. # : KW-06010691
Description :)>ASCE 7-10 wind forces
ELR Engineering
1915 Dayton Ave NE
Renton, WA 98056
phone: 206.200.8764
email: elreng33@gmail.com
Project Title:Engineer:ELRProject ID:
Printed: 6 SEP 2018, 8:54AM
Project Descr:
File = C:\Dropbox\ELRENG~1\ELR_PR~1\2018\1_RUEP~1\JKMONA~1\RENTON~1\LOTS10~1\2335-L~1\Enercalc\2342.ec6 .
Software copyright ENERCALC, INC. 1983-2018, Build:10.18.8.25 .
Calculations per ASCE 7-10Analytical Values
110.0
Roof Rise:Run Ratio >7:12
Exposure B
24.0
10.0
300.0
>7 to 27 degrees
psf
Topographic Factor Kzt per 26.8 1.00
17.670LHD : Least Horizontal Dimension ft
a = max (0.04 * LHD, 3, min(0.10 * LHD, 0.4*MRH))3.00 ft max (0.04 * LHD, 3, min(0.10 * LHD, 0.4*MRH))
Effective Wind Area of Component & Cladding
V : Basic Wind Speed per Sect 26.5-1 A, B or C mph
Roof pitch for cladding pressure
ft^2
Occupancy per Table 1.5-1 II All Buildings and other structures except
those listed as Category I, III, and IV
Exposure Category per 26.7
MRH : Mean Roof Height ft "Lambda" is interpolated between height tablular values.
Lambda : per Figure 28.6-1, Page 305 1.00
User specified minimum design pressure
Design Wind Pressures Minimum Additional Load Case per 28.4.4 = 16 PSF on entire vertical plane
Horizontal Pressures . . .
Load Case # 1 . . .
Overhangs . . .
Zone: A =21.60 psf Zone: C =17.20 psf
Load Case # 1 . . .
Zone: B =14.80 psf Zone: D =11.80 psf
Zone: Eoh =-10.00 psf Zone: Goh =-10.00 psf
Load Case # 2 . . .
Load Case # 2 . . .
Zone: A =21.60 psf Zone: C =17.20 psf
Zone: Eoh =-10.00 psf Zone: Goh =-10.00 psf
Zone: B =14.80 psf Zone: D =11.80 psf
Vertical Pressures . . .
Load Case # 1 . . .
Zone: E =10.00 psf Zone: G =10.00 psf
Zone: F =-13.10 psf Zone: H =-11.30 psf
Load Case # 2 . . .
Zone: E =10.00 psf Zone: G =10.00 psf
Zone: F =-10.00 psf Zone: H =-10.00 psf
ASCE 7-10 Wind Forces Chpt 28, Pt2 & Chpt 30, Pt2
Licensee : ELR EngineeringLic. # : KW-06010691
Description :)>ASCE 7-10 wind forces
ELR Engineering
1915 Dayton Ave NE
Renton, WA 98056
phone: 206.200.8764
email: elreng33@gmail.com
Project Title:Engineer:ELRProject ID:
Printed: 6 SEP 2018, 8:54AM
Project Descr:
File = C:\Dropbox\ELRENG~1\ELR_PR~1\2018\1_RUEP~1\JKMONA~1\RENTON~1\LOTS10~1\2335-L~1\Enercalc\2342.ec6 .
Software copyright ENERCALC, INC. 1983-2018, Build:10.18.8.25 .
Design Wind Pressure = Lambda * Kzt * Ps30 per Eq 30.5-1
Component & Cladding Design Wind Pressures
Minimum Additional Load Case per 28.4.4 = 16 PSFRoof Zone 1 :Positive :10.000 psf
Negative :-18.100 psf on entire vertical plane
Roof Zone 2 :Positive :10.000 psf
Negative :-25.500 psf
Roof Zone 3 :Positive :10.000 psf
Negative :-40.200 psf
Wall Zone 4 :Positive :17.350 psf
Negative :-19.250 psf
Wall Zone 5 :Positive :17.350 psf
Negative :-20.350 psf
Roof Overhang Zone 2:-40.600 psf
Roof Overhang Zone 3:-46.100 psf
Wood Column
Licensee : ELR EngineeringLic. # : KW-06010691
Description :090618)> Plan review comment #9 for 2X6 HF2 at 16" oc at B.F. walls
ELR Engineering
1915 Dayton Ave NE
Renton, WA 98056
phone: 206.200.8764
email: elreng33@gmail.com
Project Title:Engineer:ELRProject ID:
Printed: 6 SEP 2018, 8:56AM
Project Descr:
File = C:\Dropbox\ELRENG~1\ELR_PR~1\2018\1_RUEP~1\JKMONA~1\RENTON~1\LOTS10~1\2335-L~1\Enercalc\2342.ec6 .
Software copyright ENERCALC, INC. 1983-2018, Build:10.18.8.25 .
.Code References
Calculations per NDS 2015, IBC 2015, CBC 2016, ASCE 7-10
Load Combinations Used : ASCE 7-10
General Information
Wood Section Name 2x6Analysis Method :
17.677Overall Column Height ft
Allowable Stress Design
( Used for non-slender calculations )Allow Stress Modification Factors
End Fixities Top & Bottom Pinned
Wood Species Hem Fir
Wood Grade No.2
Fb +850.0
850.0psi
1,300.0
405.0
150.0
525.0
26.830
psi Fv psi
Fb -Ft psi
Fc - Prll psi
psi
Density pcf
Fc - Perp
E : Modulus of Elasticity . . .
1,300.0
470.0
1,300.0
470.0
Cfu : Flat Use Factor 1.0
Cf or Cv for Tension 1.30
Use Cr : Repetitive ?
Kf : Built-up columns 1.0 NDS 15.3.2
Exact Width 1.50 in
Exact Depth 5.50 in
Area 8.250 in^2
Ix 20.797 in^4
Iy 1.547 in^4
Wood Grading/Manuf.Graded Lumber
Wood Member Type Sawn
Ct : Temperature Factor 1.0
Cf or Cv for Compression 1.10
1,300.0
Axial
Cm : Wet Use Factor 1.0
Cf or Cv for Bending 1.30
x-x Bending y-y Bending
ksi YesMinimum
Basic
Y-Y (depth) axis :
X-X (width) axis :
Unbraced Length for Y-Y Axis buckling = 17.677 ft, K = 1.0
Unbraced Length for X-X Axis buckling = 1 ft, K = 1.0
Brace condition for deflection (buckling) along columns :
.Service loads entered. Load Factors will be applied for calculations.Applied Loads
Column self weight included : 27.172 lbs * Dead Load FactorAXIAL LOADS . . .
Axial Load at 17.677 ft, D = 0.320, S = 0.5330 kBENDING LOADS . . .Lat. Uniform Load creating Mx-x, W = 0.0270, E = 0.0130 k/ft .DESIGN SUMMARY
PASS
PASS
Max. Axial+Bending Stress Ratio =0.7040
Location of max.above base 8.779 ft
Applied Axial 0.7469 k
Applied Mx 0.4746 k-ft
Load Combination +D+0.750S+0.450W
Load Combination +D+0.60W
Bending & Shear Check Results
Maximum Shear Stress Ratio =
Applied Design Shear 26.033 psi
240.0Allowable Shear psi
0.1085 : 1 Bending Compression Tension
Location of max.above base 0.0 ft
: 1
At maximum location values are . . .
Applied My 0.0 k-ft
Maximum SERVICE Lateral Load Reactions . .Top along Y-Y 0.2386 k Bottom along Y-Y 0.2386 k
Top along X-X 0.0 k Bottom along X-X 0.0 kGoverning NDS Forumla Comp + Mxx, NDS Eq. 3.9-3
Maximum SERVICE Load Lateral Deflections . . .
Along Y-Y 2.218 in at 8.898 ft above base
for load combination :W Only
Along X-X 0.0 in at 0.0 ft above base
Fc : Allowable 253.413 psi Other Factors used to calculate allowable stresses . . .
for load combination :n/a
.
Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCDCLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus
Load Combination Results
D Only 0.900 PASS PASS0.0 0.0 17.677 ft0.193 ft0.1698+D+S 1.150 PASS PASS0.0 0.0 17.677 ft0.152 ft0.4255+D+0.750S 1.150 PASS PASS0.0 0.0 17.677 ft0.152 ft0.3611+D+0.60W 1.600 PASS PASS8.779 0.1085 0.0 ft0.111 ft0.6249+D-0.60W 1.600 PASS PASS8.779 0.1085 0.0 ft0.111 ft0.6249+D+0.70E 1.600 PASS PASS8.779 0.06093 0.0 ft0.111 ft0.3631+D-0.70E 1.600 PASS PASS8.779 0.06093 0.0 ft0.111 ft0.3631+D+0.450W 1.600 PASS PASS8.779 0.08135 0.0 ft0.111 ft0.4756+D-0.450W 1.600 PASS PASS8.779 0.08135 0.0 ft0.111 ft0.4756
Wood Column
Licensee : ELR EngineeringLic. # : KW-06010691
Description :090618)> Plan review comment #9 for 2X6 HF2 at 16" oc at B.F. walls
ELR Engineering
1915 Dayton Ave NE
Renton, WA 98056
phone: 206.200.8764
email: elreng33@gmail.com
Project Title:Engineer:ELRProject ID:
Printed: 6 SEP 2018, 8:56AM
Project Descr:
File = C:\Dropbox\ELRENG~1\ELR_PR~1\2018\1_RUEP~1\JKMONA~1\RENTON~1\LOTS10~1\2335-L~1\Enercalc\2342.ec6 .
Software copyright ENERCALC, INC. 1983-2018, Build:10.18.8.25 .
Maximum Axial + Bending Stress Ratios Maximum Shear RatiosCDCLoad Combination Stress Ratio Location Stress Ratio Status LocationPStatus
Load Combination Results
+D+0.750S+0.450W 1.600 PASS PASS8.779 0.08135 0.0 ft0.111 ft0.7040+D+0.750S-0.450W 1.600 PASS PASS8.779 0.08135 0.0 ft0.111 ft0.7040+D+0.750S+0.5250E 1.600 PASS PASS8.779 0.04570 0.0 ft0.111 ft0.4514+D+0.750S-0.5250E 1.600 PASS PASS8.779 0.04570 0.0 ft0.111 ft0.4514+0.60D+0.60W 1.600 PASS PASS8.779 0.1085 0.0 ft0.111 ft0.5644+0.60D-0.60W 1.600 PASS PASS8.779 0.1085 0.0 ft0.111 ft0.5644+0.60D+0.70E 1.600 PASS PASS8.779 0.06093 0.0 ft0.111 ft0.3214+0.60D-0.70E 1.600 PASS PASS8.779 0.06093 0.0 ft0.111 ft0.3214
.Sketches