HomeMy WebLinkAboutMFP23002494.pdfDEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Major Franchise Permit: MFP23002494
IVR Number: 23002494
Permit Information
Permit Name: Puget Sound Energy - Electric
Address/Location:05/11/2023Application Date:3345700220Parcel Number: 1825 NE 38TH ST
Permit Type:06/26/2023Issue Date:Franchise
Permit Work Class:06/25/2024Expiration Date:Major Utility
Job Number: 101136440Franchise Type:Electric
Description: Puget Sound Energy Electric Site
Overhead to Underground Conversion (2) Conductor Spans.
CREW TO INSTALL NEW POLE AT P1A (319469 166418) AND REMOVE POLE AT P02 (319465 166418). CREW TO
TRENCH IN ROW FROM P01A TO P03. Transfer OH conductors to lead pole. Remove OH conductors above trench
area. Dimensions of trench: L: 435' S (N) & 105' (W) W: 4', D: 4'. Truck Set up at (5) locations. P01, P1A, P02/V01,
P03, J01 and J02. Additional truck parking at P04, P05, P06 & P07 for OH work. P04 shoulder parking, P05
shoulder parking, P06 lane parking, P07 lane parking
Contacts
Name Address PhoneTypeBilling
Corrie Rydberg
Puget Sound Energy
3702 71st Ave W
University Place, WA 98466
C: (253) 905-5031ApplicantX
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
Puget Sound Energy Inc 10885 NE 4th Street, PSE08-N08
Bellevue, WA 98009
B: (888) 225-5773Emergency
Contact
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
Corrie Rydberg
Puget Sound Energy
3702 71st Ave W
University Place, WA 98466
C: (253) 905-5031Specialized
Billing
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 425.235.7736) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
DEPARTMENT OF PUBLIC WORKS
Page 1 of 3 | Published: 10/27/2021
Transportation Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN APPLICATION
Published: 10/27/2021
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL AT LEAST FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a traffic control
plan (TCP) and obtain city's approval of that plan when construction, repair, or maintenance work is to be conducted
within the city's right-of-way.
1. Fill out the Traffic Control Plan (TCP) Application form and prepare required submittal documents.
2. The following items are all required for submittal of the TCP Application:
☐Electronic Copy of the TCP Application
☐Electronic Copy of the TCP Layout, on 11” X 17” paper size format, which shall:
Include map(s) showing the location of the project and work area.
Be legible lettering and clear, contrasting, symbols of viewing or printing.
Must indicate street names, and north arrow and scale.
Types of plans required:
o Work hour plan – show all mobility impacts during construction hours.
o Non-work plan - show all mobility impacts after work hours when limited or no work is
happening in the right-of-way (ROW), if applicable.
o Changing construction phases – show construction sequence and each construction phase
change even if the traffic control is not modified, if applicable.
o Pedestrian access/detour plan, if applicable.
- Shall conform to the Washington State Traffic Control Flagger Certification handbook, by the
Evergreen Safety Council.
3. Submit Application via email to TCP@rentonwa.gov with the subject line “TCP Application – [Project Name].”
Project Name: Permit #:
Site Address:
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Construction Company:
Contact Name: Phone/Cell: _________________________
Business Address: City/State: Zip:
Description of Work:
Approval By: _________________________________________________ Date:____________________
Transportation Engineering
PLEASE SEE ATTACHED
POTELCO, INC
6905 S 228TH ST KENT, WA 98032
101136440
1825 NE 38TH ST
Randy Blackie 425.457.2614
MFP23002494
Monday - Friday 8:00AM - 3:00PM
Scott Warlick CED 6/26/2023
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 2 of 3 | Published: 10/27/2021
PERMIT HOLDER AGREES TO ALL THE FOLLOWING:
Must have approved Traffic Control Plan (TCP) prior to commencing the work.
Maintain existing pedestrian access. The work on pedestrian facilities, shall be limited to one corner at a time,
with the least possible inconvenience or delay to pedestrians.
WORK TIME begins when any street or travel lane is fully or partially closed. This includes set up within the
traveled way.
Comply with all traffic regulations of the City of Renton and the State of Washington.
Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for all street
and lane closures, and the plan shall be performed in compliance with the Manual on Uniform Traffic Control
Devices.
Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
Contractor or entity must call Renton School District (425-204-4455) or any public/private agency, including public
transit, to be affected by a temporary lane or road closure a minimum of five business days (excluding weekends
and holidays) prior to starting any work.
Contractor or entity must notify King County Metro in writing at construction.coord@kingcounty.gov a minimum
of five business days (excluding weekends and holidays) prior to starting any work impacting bus stops, a
temporary lane or road closure. Work requiring removing a bus shelter or sign requires notification in writing a
minimum of 30 business days (excluding weekends and holidays). Please call King County Metro at 206-477-1140
with any questions.
Any lane or street closures not in conformance with the approved traffic control plan and/or without notification
of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200 Signs or Flaggers at
thoroughfare work sites and R.C.W. 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments, including all
costs of defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved traffic control plans including claims arising from towing of private vehicles and
the acts of the Permit Holder’s agents and employees.
The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and in
such event shall indemnify and hold harmless the City for any such claims paid, including the City’s reasonable
attorney’s fees and litigation costs incurred resulting from such claim.
In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder will pay for
legal counsel chosen by the City to defend against same.
Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic or
pedestrian safety or travel.
All permit conditions shall be met.
NOTES:
Total road closure lasting more than twenty-four (24) hours is subject to the approval by the City Council.
Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by a traffic control plan layout or reference to WSDOT.
Approved Temporary Traffic Control Plan must be at the work site during work hours.
Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded to safely redirect pedestrians around a work zone.
Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or slippery
road conditions during work and non-work hours.
Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a company
logo or any legally acceptable sign showing the company name, address, and telephone number at a conspicuous
place on the vehicle or equipment.
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 3 of 3 | Published: 10/27/2021
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
seventy-two (72) hours in advance of effective date and time.
The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop (3555
NE 2nd Street).
I certify that the information on this application and within the submittal documents are accurate to the best of my
knowledge and I acknowledge all the requirements on this application.
Applicant’s Signature Date
Applicant’s Name (Print)
CORRIE RYDBERG
P01
P1A
V01
P03
J02
J01
LINCOLN CT NE
NE 38TH ST LINCOLN AVE NELINCOLN AVE NE1010 991313
1414
1010LINCOLN AVE NE1414
STOP
FLAGGER
STOP
FLAGGER
PLACE SIGNS ALONG
WORK AREAFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PARKW20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORK
AHEAD W20-1RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE
P02ROADWORKAHEADW20-1
THE CREW SHALL CEASE
WORK FOR A FLAGGER/SPOTTER
TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
1 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
VAULTVault
TRENCH
MFP23002494
P01
P1A
V01
P03
J02
J01
LINCOLN CT NE
NE 38TH ST LINCOLN AVE NELINCOLN AVE NELINCOLN AVE NE1010 991313
1414
1010LINCOLN AVE NE1414
STOP
FLAGGER
STOP
FLAGGER
PLACE SIGNS ALONG
WORK AREAFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PARKW20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1P02
W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROAD
WORK
AHEAD W20-1W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4X'X'X'
USE MAXIMUM AVAILABLE
SPACE FOR SIGNSSTREETCLOSEDBARRICADER11-2R007-LR007-RS/WCLOSEDR9-9FLAGGERS SHALL STOP TRAFFIC IN ALL
DIRECTIONS TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
CREW SHALL SHIFT CONES AND
EQUIPMENT FOR EMERGENCY
VEHICLES ACCESS
RESIDENT(S) WILL BE INFORMED
BY CUSTOMER OUTREACH OF ROAD
CLOSURE 10 DAYS IN ADVANCE.
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
2 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
P01
P1A
V01
P03
J02
J01
P07
NE 36TH ST
LINCOLN CT NE
NE 38TH ST LINCOLN AVE NELINCOLN AVE NELINCOLN AVE NELINCOLN AVE NE1616 16161010 991313
1414
1010NE 35TH PL1616P02
STOP
FLAGGER
STOP
FLAGGER
STOP
FLAGGER
PLACE SIGNS ALONG
WORK AREAFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PAR
KW20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4X'X'X'
USE MAXIMUM AVAILABLE
SPACE FOR SIGNS
STOP
FLAGGER
W20-7A
W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORK
AHEAD W20-1100'ROADWORKAHEADW20-1S/W
CLOSEDR9-9FLAGGERS SHALL STOP TRAFFIC IN ALL
DIRECTIONS TO ESCORT PEDESTRIANS
AROUND THE WORK AREA
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
3 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
P1A
V01
P03
J02
J01
P07
NE 36TH ST
LINCOLN CT NE
NE 38TH ST LINCOLN AVE NELINCOLN AVE NELINCOLN AVE NE1616 16161010 991313
1414
1010NE 35TH PL1616P02
STOP
FLAGGER
STOP
FLAGGER
PLACE SIGNS ALONG
WORK AREAFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PARKW20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4X'X'X'
USE MAXIMUM AVAILABLE
SPACE FOR SIGNS
STOP
FLAGGER
W20-7AW20-4ONE LANE
ROADAHEAD100'100'100'ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4100'100'100'
1616LINCOLN AVE NEProject Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
4 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
V01
P03
J02
P07
NE 36TH ST
LINCOLN CT NELINCOLN AVE NELINCOLN AVE NELINCOLN AVE NE1616 16161010 991313
NE 35TH PL
LINCOLN
AVE
NE16161616
P02
STOP
FLAGGER
STOP
FLAGGER
PLACE SIGNS ALONG
WORK AREAFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PA
R
K
RESIDENT(S) WILL BE INFORMED OF
TEMPORARY DRIVEWAY CLOSURE ROADWORKAHEADW20-1100'
STOP
FLAGGER W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4100'100'100'W20-7AW20-4ONE LAN
E
ROAD
AHEAD
100'100'100'
ROAD
WORK
AHEAD W20-1W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4100'100'100'W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
5 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
P04NE 43RD ST 110TH AVE SELINCOLN AVE NE1212151512121312111112 12
PLACE SIGNS ALONG
WORK AREAFROMTOTOW AWAY AREAPHONE 888-9999INFRASOURCE LLC 000 0000000NO PARKINGNO-PA
R
K
SHOULDER
WORK W21-5100'100'ROAD
WORK
AHEAD W20-1100'ROADWORKAHEADW20-1 100'ROADWORKAHEADW20-1Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
6 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
P05
LINCOLN AVE NELINCOLN AVE NE1212
1212
STOP
FLAGGER
STOP
FLAGGER
W20-7AW20-4ONE LANE
ROADAHEAD100'100'100'ROAD
WORK
AHEAD W20-1W20-7AW20-4ONE LANEROADAHEAD100'100'100'ROADWORKAHEADW20-1Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
7 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
P06
NE 40TH ST
NE 40TH STMON
T
E
R
E
Y
P
L
N
ELINCOLN AVE NELINCOLN AVE NE1414 LINCOLN AVE NE661212 1414
8812121212
1212
STOP
FLAGGER
STOP
FLAGGER
STOP
FLAGGERW20-7AW20-4ONE LANEROADAHEADX'X'X'ROADWORKAHEADW20-1USE MAXIMUM AVAILABLE
SPACE FOR SIGNS
W20-7AROAD
WORK
AHEAD W20-1BE
PREPARED
TOSTOP W3-4100'100'100'W20-7ABEPREPAREDTOSTOPW3-4X'X'ROADWORKAHEADW20-1100'ROAD
WORK
AHEAD W20-1100'
USE MAXIMUM AVAILABLE
SPACE FOR SIGNS
Project Address:
Page
PSE PUGETSOUNDENERGY
Designer:
Job #
REV
Flaviana Nunes
425-424-7386
flaviana.rodriguesnunes@pse.com
8 OF 81825 NE 38th St, Renton
0
510743155
04/07/2023
Puget Sound Energy
Traffic Control Supervisor:Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
TEMPORARY TRAFFIC CONTROL PLAN
N
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 10' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
VAULTVault
TRENCH
MFP23002494
N
Vicinity Map
47.5252, -122.1937
Owner / Developer Contact Info
officeATTN:
GILL HOMES, LLC
PO BOX 98468
DES MOINES, WA 98198
NAVDEEP S. GILL.253.261.4455
GAS
PHONE
CABLE TV
101136440
N/A 108128058
N/A 583066599
N/A 593233597
N/A 594142437
N/A 593246377
N/A -
N/A -
N/A -
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Pole Removal
XFMR Removal
OH Misc
UG Misc
System O&M
Distribution
Service Stubs
HP Svc/MSA
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. BLACKIE 425.457.2614 3.10.21
A.TOLENTINO -8.10.22
---
A.TOLENTINO -8.10.22
REDT # (RW-121253)CITY OF RENTON
KP DEVELOPMENT SCH73
SCHEDULE 73 OH-UG CONVERSION - 2 SPANS
1825 NE 38TH ST, RENTON, WA 98056
PUGET SOUND ENERGY
N/A N/A
N/A 101136440
AS SHOWN 1 OF 5
KING 469E -QCSOKE
32NE-T24N-R05E N/A N/A
2405E125 2405E136 2405E125 HAZ-15
COMCAST
JAMES COHN
253.569.0636
LUMEN TECH
ALEX HARB
206.345.4476
RIGHT OF WAY
FABIANA DODSON
425.456.2293
.
.
.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:RANDY BLACKIE
425.457.2614
randy.blackie@pse.com
NAVDEEPGILL@MSN.COM
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
x
###
###
###
OVERHEAD CIRCUIT MAP (2405E136) - EXISTING
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
LEGEND
EXISTING PROPERTY LINE
EXISTING UG RISER
NEW UG RISER
SVC STUB
J-BOX
NEW TRENCH LINE
EXIST. 3Ø WIRE
EXISTING CENTER LINE
EXISTING CONDUCTOR TO BE REMOVED
DISCONNECT - FUSED
EXIST. 1Ø WIRE
EXISTING RIGHT OF WAY
PROPOSED PULL VAULT
EXISTING POLE
DOWN GUY
EXISTING SECONDARY SERVICE LINE
DISCONNECT - UNFUSED
EXISTING STREETLIGHT
NEW POLE
PROPOSED PADMOUNT TRANSFORMER
EXISTING PADMOUNT TRANSFORMER
PROPOSED TOTAL UNDERGROUND TRANSFORMER
EXISTING TOTAL UNDERGROUND TRANSFORMER
HANDHOLE
PRIMARY METERING POINT
NOTE:
DEVELOPER TO PROVIDE ALL CIVIL WORK: TO AND INCLUDING EXCAVATION, BACKFILL, SHORING,
TRENCH MAINTENANCE, SANDING FOR DUCT, SELECT 5/8" CRUSH FOR UNDER VAULTS, COMPACTION,
ALL HARDSURACE RESTORATION AND RELATED LANDSCAPING RESTORATION. DEVELOPER TO
PROVIDE TEMPORARY EXCAVATION PLATING (IF REQUIRED).
x
x
KP DEVELOPMENT
SCHEDULE 73
OH TO UG CONVERSION
GENERAL 1.
Pre-construction Notify appropriate City or County 48 to 72 hours or as required by
permitting agency before starting work on any right-of-way involving a permit.
Follow all requirements as outlined by the permitting agency.
Locate and mark all underground utilities prior to start of construction. If there is a
conflict with the intended trench route as shown on the site plan and existing utilities or
obstructions, trench route may need to be moved to opposite side of street.
Cooperation with Quality Inspector, Puget Sound Energy Contractor, City or County
authorities during Pre-construction meeting will determine the final trench route.
2. Existing Utilities
Hand excavate (pothole) all marked utility crossings to verify exact location and depth
at point of crossing. Protect underground utilities during excavation. Use hand
excavation methods if necessary to avoid damage. Fabricate and install adequate
temporary structures to support and protect underground utilities while exposed during
construction.
Maintain 6" minimum clearance at crossings between existing utilities and new duct
installations. Transition trench or tunnel profile gradually as required at crossings.
Maintain 24" minimum separation between new trench or tunnel and parallel existing
utilities or as required by the permit agency.
In the event of damage to an underground utility, notify Puget Sound Energy at once.
Contractor agrees to make work force and resources available at once to Puget Sound
Energy or municipal authorities to repair damage at no cost.
3. Work Drawings
Maintain on site, in good condition, a complete file of all work drawings. These
drawings shall be available at all times to a Puget Sound Energy representative.
Corrections and changes made during the job shall be recorded continuously on these
drawings. All underground electrical facilities shall have a minimum of 36 inches of
cover. Any change must be approved by the PSE engineer or project manager.
Furnish Puget Sound Energy a complete set of as built prints (foreman's copies) at the
end of the job.
4. Safety
Provide signs, barricades, and traffic control in conformance with local jurisdictions and
regulations. Provide flagging and or other vehicle traffic control as needed in
conformance with local regulations. (see SPM # 100.4000) Provide adequate signage
and protection to traffic during non-working hours. Maintain traffic flow as required by
permitting agency. Provide signs and barricades to warn pedestrians, motorcycles and
bicycles.
Install warning barricades at least every 50 feet along the trench route from the time the
trench is opened until the trenching is complete.
5. Existing Systems
Maintain existing electrical system in service until new system is complete, tested, and
ready for service. Disable existing system only to make cutovers and connections as
directed by Puget Sound Energy's representative.
Provide temporary wiring and connections to maintain existing systems in service during
construction; if a scheduled outage is not possible. When work must be performed on
energized equipment or circuits, use qualified personnel for such operations.
EARTHWORK
See Puget Sound Energy SPM 6800.4050
1. Back hoe, Hand Dug Excavations
Paved Surfaces
Cut the edges of the trench prior to digging. Use the narrowest bucket practical or plow
off the edge of paved surface far enough to minimize asphalt disturbance. Repair any
blow out areas (where edge has been broken) by sawing. The depth of the trench shall
be enough to allow 36" of cover . Backfill material shall be Controlled Density Fill (CDF)
cover or select fill (5/8" minus) to meet permit requirements.
Unpaved Surfaces
Conduit/cable trenches are to be excavated just off the existing road edge or in the
shoulder of the road behind the existing ditch line. Contractor shall use a back hoe with
the narrowest width bucket practical or plow. Trench shall be deep enough to allow a
minimum of 36" of cover over the top most cable. All ditch crossings shall have a
minimum of 36" cover from the lowest point within the existing ditch line.
Culverts; when installing facilities under a culvert, excavation must be filled with packed
crush rock. If any culvert is damaged it will be repaired or replaced in accordance with
permitting agency and contractors responsibility.
Spoils shall be removed quickly to minimize blocking of traffic. All spoils and wastes
become the property of the contractor immediately upon removal. Remove spoils and
wastes promptly to an approved disposal site. Remove spoils containing asphalt or
concrete to a disposal site specifically approved for such materials. Provide Puget
Sound Energy with a disposal receipt for all spoils.
2. Backfill
Unpaved Road Surfaces
Backfill for unpaved road crossings shall consist of 1-1/2" to 2-1/2" material compacted
to 95% density. Backfill for unpaved road sections shall consist of native material
compacted to 95% density.
At the end of each workday, backfill or plate all trench, remove all spoils and clean
roadway surface of large hazardous debris.
3. Surface Restoration
Unpaved Surfaces
Restore ground surface to original contour. Restore to original condition or better.
4. Landscaping
Arrange and perform work to minimize impact to existing landscaping. Restore
landscaping that has been disturbed during the course of work, including seeding of
banks and fills. Vaults set in bank areas may require re-sloping the surrounding land to
avoid sloughing. Leave area in its original state or better at the end of construction.
Hand dig if required to prevent damage to tree roots.
ELECTRICAL
1. Conduit
Conduit for installation in unpaved areas shall be 2", 3", 4", or 6" SCH80 PVC direct burial.
Maintain 36" minimum cover above top conduit at all times or as required by the permitting
agency.
Where conduit is routed from road edge to vault location, maintain 36" minimum cover above top
conduit at all times or as required by the permitting agency. Bends shall be made with as long a
radius as possible (48" minimum). Avoid making sharp bends or kinks in conduit during
installation. Obtain exact location of conduit entrance into vault from Puget Sound Energy before
penetrating vault. Penetrate the vault using existing knockout or use core drilled holes. Stub the
4" or 6" PVC 2"-3" into vault interior and grout between the conduit and vault wall. Leave a 10'
minimum of extra pull rope in each end of installed conduit where 4" or 6" PVC is installed and
cap conduit to prevent the entry of dirt and moisture.
Arrange work so conduit plays directly off reel into trench. Place the conduit in the trench as
straight as possible. Avoid vertical and horizontal "snaking" of the conduit. Multiple conduit runs
may be stacked vertically. Where conduit must be pulled through a trench to allow a crossing
under an existing utility, cap conduit end before pulling to avoid contamination. If a kink occurs,
cut the conduit ahead of kink and splice to new conduit to continue run.
2. Underground Primary Cable
Primary cable shall be 1/O Alum Sol Jacketed Cable rated for 15 KV service with a polyethylene
jacket. Primary cable shall be 61 strand 750 MCM aluminum conductor rated for 15 KV service
with a copper tape neutral conductor and polyethylene jacket. A 4/0 copper neutral shall be run
with each 3 phase circuit of 750 MCM.
Install cable into existing or new conduit systems using approved installation equipment.
Approved equipment includes either cable pullers and/or cable pushers. Pulling socks shall be
non-conductive or similar material. Steel pulling socks are prohibited. Bare steel cable shall not
be used to pull cable. Cable pulling equipment (winches, hoist, driven reels, etc.) shall be
equipped with instrumentation to continually monitor and record peak tension encountered during
a pull. Before installing cable, obtain rated pulling tension for cable from Puget Sound Energy.
Do not exceed rating at any time during installation. Notify Puget Sound Energy immediately if
pulling tension equals or exceeds rating (828/1657lbs for 1/0 or 5000lbs for 750 .) Do not exceed
minimum bend radius of cable or impose kinks or sharp bends on cable during pulling operations.
Install cable directly off reel without dragging it on the ground. Apply Puget Sound Energy
approved lubricant to cable continually during pulling to reduce pulling tension and to permit future
removal.
Install adequate amounts of 3/4 " plywood on existing sidewalk areas to support pulling equipment
and prevent un-necessary damage to sidewalks.
Train and coil cables in vaults as required to form a smooth transition from conduit to termination.
if terminations are to be performed by others, coil 15' of cable in vault and cap end.
3. Terminations and Splices
Install approved terminations on cables in accordance with Puget Sound Energy SPM 2247.5115-
5119. Unless otherwise directed, approved terminations will be load break elbows in vaults and
cold shrink pin terminals on pole risers per Puget Sound Energy SPM 2247.9317.
Splice cable with approved splice kits in vaults, hand holes or similar enclosures. Do not splice
cables in runs between vaults. See Puget Sound Energy SPM 2233.2075-2076.
4. Concrete Vaults
Excavate, install base material, and compact base material in accordance with Puget Sound
Energy SPM 6775.0040.
Install and seal precast sections in accordance with Puget Sound Energy SPM 6775.0040. Use
precast neck and shaft sections to bring manhole entrance to proper elevation. Install manholes
plumb. Set the top of each manhole to finished elevation or no higher than 6" above existing road
elevation. Install hillholders as required on sketch or by construction notes.
5. Grounding
Install ground rod per Puget Sound Energy SPM 6275.6100 at each vault in which primary cable
is terminated. Locate rod in trench excavation wherever possible to obtain maximum driven depth
in undisturbed soil. Connect each ground individually to ground loop inside vault with bare no. 2
copper jumper or to Concentric neutral at each splice vault location. Minimum grounding
requirement is 4 grounds per mile.
6. Existing Underground Primary Cable (if applicable)
Abandon existing primary cable in place. Cut off old cable ends inside vault flush with wall.
Before cutting, pigtail concentric neutral strands and connect to ground loop inside vault. Return
scrap cable and existing cable tags to Puget Sound Energy. Remove or fill existing vaults as
required by permitting agency.
7. Traffic Control
All traffic control to comply with current specifications in M.U.T.C.D.
GENERAL OVERHEAD NOTES:
1. Poles, conductors, devices to be installed per PSE Standards & Specifications.
2. Poles are to be installed or relocated as staked.
3. All new poles set shall be the class indicated on the sketch or better.
4. Install ground plate assembly on all new poles.
5. Install grid numbers on all new and existing poles as shown on sketch.
6. Treat all field-drilled poles with copper Naphthenate wood preservative.
7. Customer/Developer to coordinate between utilities.
8. All new and relocated poles -locations- to be approved by City of Renton
JOB
SITE
101136440FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
x
SCALE: 6" = 1 MILE
SITE
ELEC LEGEND - PROPOSEDNORMAL OPENN.O. WILL NOT PHASESECONDARYREMOVALPRIMARYOH TPXGAS LEGEND - PROPOSEDCASINGNEW SVC.LP MAINIP MAINHP MAINANODEBOTTOM OUT STOPPERCP TEST STATIONCUT & CAPDRIP (FUSE TIE-IN EXT.)ELBOWGAUGE TEEINLINE TEEIP VALVE LABELPIPE LINE MARKERMETERREDUCERSERVICE TEE STOPPERHVTT (HIGH VOL. TAPPING TEE)POLYVALVETEST LEAD (END OF MAIN)TEST LEAD/TRANSITION FITTINGTWIN SVC STUBSINGLE SVC STUBEFVSVC.TRANSFORMERJ-BOXSWITCHMETERE - MARKERMETERHH/PEDESTALSTUBKEYNOTECONDUITPSE POLEOH SOLID BLADERISER SOLID BLADERISER FUSEDSEC. RISERSPAN GUYDOWN GUYLABELSPOLE REMOVALPSE POLEOH FUSESPLICEFOREIGN POLE1Ø OH/UGTPX.2Ø OH/UG3Ø OH/UGLABELSHH/PEDESTALST LIGHTKEYNOTEJ-BOXXFMRSWITCHCOMBO PM XFMRPULL/SPLICE VAULTCOMBO VAULT XFMRCMB. TUT XFMRCMB. TUT XFMRSPLICE55KV TRANSMISSION115KV TRANSMISSION230KV TRANSMISSIONGAS LEGEND - EXISTINGIP MAINELEC LEGEND - EXISTINGX-ING KEYNOTEST LIGHT LABELQUAD.DUPLEXST LIGHTKEYNOTEKEYNOTEVALVEREDUCERCUT & CAPHVTTB.O. STOPPERSTOPPERSVC TEEBRANCH SADDLEDIST. REGULATORIP VALVELP VALVE
510743155
P04
P05
P06
P07
MFP23002494
This permit is for Major construction work in the ROW and will be billed at an additional
$158/HR for inspections. After hours and weekend work will be billed at $175/HR
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. BLACKIE 425.457.2614 3.10.21
A.TOLENTINO -8.10.22
---
A.TOLENTINO -8.10.22
REDT # (RW-121253)CITY OF RENTON
KP DEVELOPMENT SCH73
SCHEDULE 73 OH-UG CONVERSION - 2 SPANS
1825 NE 38TH ST, RENTON, WA 98056
PUGET SOUND ENERGY
N/A N/A
N/A 101136440
AS SHOWN 2 OF 5
KING 469E -QCSOKE
32NE-T24N-R05E N/A N/A
2405E125 2405E136 2405E125 HAZ-15
COMCAST
JAMES COHN
253.569.0636
LUMEN TECH
ALEX HARB
206.345.4476
RIGHT OF WAY
FABIANA DODSON
425.456.2293
.
.
.
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
###
###
###
UNIVERSAL MAP - EXISTING (2405E125)UNDERGROUND CIRCUIT MAP - EXISTING (2405E125)
SCALE: 1" = 100'
JOB
SITE
SCALE: 1" = 100'
JOB
SITE
ELEC LEGEND - PROPOSEDNORMAL OPENN.O. WILL NOT PHASESECONDARYREMOVALPRIMARYOH TPXGAS LEGEND - PROPOSEDCASINGNEW SVC.LP MAINIP MAINHP MAINANODEBOTTOM OUT STOPPERCP TEST STATIONCUT & CAPDRIP (FUSE TIE-IN EXT.)ELBOWGAUGE TEEINLINE TEEIP VALVE LABELPIPE LINE MARKERMETERREDUCERSERVICE TEE STOPPERHVTT (HIGH VOL. TAPPING TEE)POLYVALVETEST LEAD (END OF MAIN)TEST LEAD/TRANSITION FITTINGTWIN SVC STUBSINGLE SVC STUBEFVSVC.TRANSFORMERJ-BOXSWITCHMETERE - MARKERMETERHH/PEDESTALSTUBKEYNOTECONDUITPSE POLEOH SOLID BLADERISER SOLID BLADERISER FUSEDSEC. RISERSPAN GUYDOWN GUYLABELSPOLE REMOVALPSE POLEOH FUSESPLICEFOREIGN POLE1Ø OH/UGTPX.2Ø OH/UG3Ø OH/UGLABELSHH/PEDESTALST LIGHTKEYNOTEJ-BOXXFMRSWITCHCOMBO PM XFMRPULL/SPLICE VAULTCOMBO VAULT XFMRCMB. TUT XFMRCMB. TUT XFMRSPLICE55KV TRANSMISSION115KV TRANSMISSION230KV TRANSMISSIONGAS LEGEND - EXISTINGIP MAINELEC LEGEND - EXISTINGX-ING KEYNOTEST LIGHT LABELQUAD.DUPLEXST LIGHTKEYNOTEKEYNOTEVALVEREDUCERCUT & CAPHVTTB.O. STOPPERSTOPPERSVC TEEBRANCH SADDLEDIST. REGULATORIP VALVELP VALVE
MFP23002494
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. BLACKIE 425.457.2614 3.10.21
A.TOLENTINO -8.10.22
---
A.TOLENTINO -8.10.22
REDT # (RW-121253)CITY OF RENTON
KP DEVELOPMENT SCH73
SCHEDULE 73 OH-UG CONVERSION - 2 SPANS
1825 NE 38TH ST, RENTON, WA 98056
PUGET SOUND ENERGY
N/A N/A
N/A 101136440
AS SHOWN 3 OF 5
KING 469E -QCSOKE
32NE-T24N-R05E N/A N/A
2405E125 2405E136 2405E125 HAZ-15
COMCAST
JAMES COHN
253.569.0636
LUMEN TECH
ALEX HARB
206.345.4476
RIGHT OF WAY
FABIANA DODSON
425.456.2293
.
.
.
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
###
###
###
ELEC LEGEND - PROPOSEDNORMAL OPENN.O. WILL NOT PHASESECONDARYREMOVALPRIMARYOH TPXGAS LEGEND - PROPOSEDCASINGNEW SVC.LP MAINIP MAINHP MAINANODEBOTTOM OUT STOPPERCP TEST STATIONCUT & CAPDRIP (FUSE TIE-IN EXT.)ELBOWGAUGE TEEINLINE TEEIP VALVE LABELPIPE LINE MARKERMETERREDUCERSERVICE TEE STOPPERHVTT (HIGH VOL. TAPPING TEE)POLYVALVETEST LEAD (END OF MAIN)TEST LEAD/TRANSITION FITTINGTWIN SVC STUBSINGLE SVC STUBEFVSVC.TRANSFORMERJ-BOXSWITCHMETERE - MARKERMETERHH/PEDESTALSTUBKEYNOTECONDUITPSE POLEOH SOLID BLADERISER SOLID BLADERISER FUSEDSEC. RISERSPAN GUYDOWN GUYLABELSPOLE REMOVALPSE POLEOH FUSESPLICEFOREIGN POLE1Ø OH/UGTPX.2Ø OH/UG3Ø OH/UGLABELSHH/PEDESTALST LIGHTKEYNOTEJ-BOXXFMRSWITCHCOMBO PM XFMRPULL/SPLICE VAULTCOMBO VAULT XFMRCMB. TUT XFMRCMB. TUT XFMRSPLICE55KV TRANSMISSION115KV TRANSMISSION230KV TRANSMISSIONGAS LEGEND - EXISTINGIP MAINELEC LEGEND - EXISTINGX-ING KEYNOTEST LIGHT LABELQUAD.DUPLEXST LIGHTKEYNOTEKEYNOTEVALVEREDUCERCUT & CAPHVTTB.O. STOPPERSTOPPERSVC TEEBRANCH SADDLEDIST. REGULATORIP VALVELP VALVE
J- BOX CABLE ENTRY DETAIL
Not to scale
CLEAR WORKING SPACE FOR VAULTS
NOT TO SCALE
FIELD SIDE (PREFERRED)
ROAD SIDE (PREFERRED)
6' MIN
3'
MIN
3'
MIN
3' MIN
Standoff Bracket
15" Min Length
Conduit Clamp
Conduit Field Face
Quadrant
Climbing
SpaceRoad Face
Quadrant
Climbing
Space
5" Min
CL LCDirection of Vehicular Traffic
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
NOT TO SCALE
NOT TO SCALE
TYPICAL POLE WITH RISER DETAIL (P1A, P03)
Schedule 80 Bend
Ground Line
10' (Overall)
Schedule 80
Conduit8'
Min.
20'
DB 120
Conduit
36" Primary
24" Secondary
Note: Schedule 80 conduit shall
extend a minimum of 8' above
and 12" below ground line.
Ground Line
Common Neutral
6" Minimum above common neutral.
even with the common neutral for secondary.
12
13
10
11
3
5"
Min.
5
6 7
1
4
2
CL
Climbing
Space
Climbing
Space
Direction of Vehicular Traffic
5" Min.
Conduit
Conduit Clamp
Standoff Bracket
15" Min Length
Field Face
Quadrant
Road Face
Quadrant
JOINT TRENCH DETAIL
NOTES:
1. If the final backfill contains rocks greater than 8 inches in diameter, install 12 inches compacted sand shading across the full width of the trench. *
If the final backfill contains rocks 8 inches in diameter or smaller, install 6 inches compacted sand shading across the full width of the trench. *
2. Rocks greater than 10 inches diameter are not permitted in the final backfill.
3. Sand bedding is required under PSE gas pipe. Bedding is not required for the full width of the trench; it shall extend from the
side of the trench nearest to where the gas main/service is installed to a minimum of 6 inches on the opposite side of the gas line.
4. Utilities shall not be stacked over the gas line in the trench.
5. If wet utilities will be included in the trench, please contact PSE or local power company directly for clearance requirements.
6. Reduced clearance of 4 inches between power and communication, must have approval of the communications companies.
* Alternatives to full-width trench shading require PSE approval.
Primary & Secondary-Mainline Gas & Communications (NTS)
Primary
Dirt Pile
Final Grade
24" Min
36"
Min Cover
Over Power 48"
Max
Depth
Final Backfill
Gas
4" Sand Bedding
Property Line
intercept (depth varies).
SidewalkCurb
Location of roof drain
48" Typical
Width may vary per
Number of Utilities
and Conduits
6" or 12" Min Sand Shading
Over Gas after Compaction
12" Min
R/W or
Excavated
12" Typical
Power
Secondary
Power
TV & TEL
12" Min
12" Min
Separation
4,5
1,2
1
3
6
6" or 12" Min Sand Shading
Over Power after Compaction1
ROAD SIDE
MINIPAD
MINIPAD
FIELD SIDE
VAULT
6" of crushed rock
(base for vault)
P/L
Power
Secondary
Power
Primary
Gas
12" Min Horizontal Separation
Communications
48" Min
21"1'
Feeder
38"
2"
4" Sand Bedding
12" Sand
Cover
36"
Cover
4" Sand Bedding
42"
6" Additional depth when
Feeder is required
PSE 10' FRONTAGE EASEMENT
1'
TRANSFORMER
Final
Backfill
Initial
Backfill
Trench Depth
42" - 48"
Utility Pole Erosion Control
UTILITY POLE EROSION CONTROL DETAIL
NOT TO SCALE Drainage ditches or Dry vegetated sites
TOP VIEW
DRY DRAINAGE DITCH or DRY VEGETATED SITE
SLOPE
Place gravel bags for
Sediment Trap
Place straw mulch
on disturbed areaExcavated or
Augered Hole
Pole
SLOPE
TOP VIEW
Excavation - 10-1/3 cubic yards
SIDE VIEW
Rock
Crushed
6"
4'-4"
2"
8'
8'
4'-8"
3'-6"
4'-8"
6"
VAULT DETAIL @ J01
NOT TO SCALE
TOP VIEW
SIDE
VIEW
EXCAVATION:
4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
FRONT
FRONTVAULT DETAIL @ V01
NOT TO SCALE
Cables should enter the vault so that all of
the cables will lay in the same direction.
TOP VIEW
TYPICAL NOTCH-OUT FOR TRANSFORMER,
NOT TO SCALE
& SECONDARY PEDESTAL/HANDHOLE
BACK OF EASEMENT
STANDARD
EASEMENT
LINE
ROW
10'
PL
1'
4' - 5'
Min.
1'
7'7'
TRANSFORMER
(WHEN PRESENT)
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
OIL-FILLED EQUIPMENT
TRANSFORMER
APPROVED
AREA
COMBUSTIBLE BUILDING WALLS & ROOF10'
10'
10'
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
3' MIN
Distribution Pole Steel Casing - Material ID (9997493) (P1A)
Length 10', Diameter 3', Wall Thickness 0.375
MFP23002494
NE 38TH ST LINCOLN AVE NEJOINT USE DRIVEWAY
(ACCESS & UTILITY TRACT
LOT 1
LOT 2
LOT 3
LOT 6LOT 7LOT 8
LOT 5 LOT 4
#4CUB#6CU#6CULINCOLN CT NE
'A'
FUSE @ 40T
SW#:T85194
POLE TO REMAIN
BØACG872
30'
BØ32896 FEEDHAZ
15
FEEDHAZ
15#6CUSOLID BLADE
SW#: T85315
TRANSFER
60'
60'DEDICATED 2' ROW3636
BN
B
TO BE REMOVED
3613
3617
3621
3616
3601
OH
UG
UG
ST LIGHT
1826
POLE TO REMAIN
NEW FUSE @ 65T
'B'
'C'
'D'
'E'
'F'
300A S.B.
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. BLACKIE 425.457.2614 3.10.21
A.TOLENTINO -8.10.22
---
A.TOLENTINO -8.10.22
REDT # (RW-121253)CITY OF RENTON
KP DEVELOPMENT SCH73
SCHEDULE 73 OH-UG CONVERSION - 2 SPANS
1825 NE 38TH ST, RENTON, WA 98056
PUGET SOUND ENERGY
N/A N/A
N/A 101136440
1" - 50'4 OF 5
KING 469E -QCSOKE
32NE-T24N-R05E N/A N/A
2405E125 2405E136 2405E125 HAZ-15
COMCAST
JAMES COHN
253.569.0636
LUMEN TECH
ALEX HARB
206.345.4476
RIGHT OF WAY
FABIANA DODSON
425.456.2293
.
.
.
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
###
###
###
ELEC LEGEND - PROPOSEDNORMAL OPENN.O. WILL NOT PHASESECONDARYREMOVALPRIMARYOH TPXGAS LEGEND - PROPOSEDCASINGNEW SVC.LP MAINIP MAINHP MAINANODEBOTTOM OUT STOPPERCP TEST STATIONCUT & CAPDRIP (FUSE TIE-IN EXT.)ELBOWGAUGE TEEINLINE TEEIP VALVE LABELPIPE LINE MARKERMETERREDUCERSERVICE TEE STOPPERHVTT (HIGH VOL. TAPPING TEE)POLYVALVETEST LEAD (END OF MAIN)TEST LEAD/TRANSITION FITTINGTWIN SVC STUBSINGLE SVC STUBEFVSVC.TRANSFORMERJ-BOXSWITCHMETERE - MARKERMETERHH/PEDESTALSTUBKEYNOTECONDUITPSE POLEOH SOLID BLADERISER SOLID BLADERISER FUSEDSEC. RISERSPAN GUYDOWN GUYLABELSPOLE REMOVALPSE POLEOH FUSESPLICEFOREIGN POLE1Ø OH/UGTPX.2Ø OH/UG3Ø OH/UGLABELSHH/PEDESTALST LIGHTKEYNOTEJ-BOXXFMRSWITCHCOMBO PM XFMRPULL/SPLICE VAULTCOMBO VAULT XFMRCMB. TUT XFMRCMB. TUT XFMRSPLICE55KV TRANSMISSION115KV TRANSMISSION230KV TRANSMISSIONGAS LEGEND - EXISTINGIP MAINELEC LEGEND - EXISTINGX-ING KEYNOTEST LIGHT LABELQUAD.DUPLEXST LIGHTKEYNOTEKEYNOTEVALVEREDUCERCUT & CAPHVTTB.O. STOPPERSTOPPERSVC TEEBRANCH SADDLEDIST. REGULATORIP VALVELP VALVE
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
P02
319465-166418
25kVA
CIRCUIT FEET REMOVED: 570
CIRCUIT FEET ADDED: 920
RETIREMENT POLE TABLE
SITE
#
POLE DATA POLE TRANSFERS REMARKS
GRID #HEIGHT CLASS YEAR XFMR CO.
ID#TOPPED RMVD TEL TV FIBER ST. LIGHT (ADDITIONAL INFORMATION)
P02 319465
166418 40'CL3 1960 LUMEN TECH/ COMCAST
1" - 50'
SITE PLAN
SITE SPECIFIC NOTES
P01 (319495-166420) 45' CL4, 2003
- POLE TO REMAIN (FIELD GRID 319495-166417)
P1A
- INSTALL 36" CASING (9997493), SET 2' FT BELOW NORMAL POLE SET DEPTH.
- INSTALL NEW 55' CL 1 POLE (PD551) 6010.1000, SEE EMBEDMENT METHOD #2 (6450.6100).
- INSTALL 12kV 1Ø PRI./NEUT. F.G. ARM DEADEND, (DEC0315) 6033.2030
ALUM "H" CONNECTOR (2167000), DEADENDS (2223000x2)
- INSTALL 1Ø TERM ON SINGLE F.G. ARM W/ L.I. C/O & SURGE ARRESTOR
(UTSU1L1) - 6043.1001
- INSTALL SOLID BLADE (9999110)
- INSTALL STIRRUPS (MID: 2254100)
- INSTALL SW#T85315
- INSTALL 2" PRI. RISER ON NEW STANDOFF BRACKETS (RIS2CSS) 6042.1000
- INSTALL 4" PRI. RISER, CAP 10' UP POLE (RIS4CSS) 6042.1000
- INSTALL GRID #319469-166418
P02 - (319465-166418) 1960 40' - CL3
- TO BE REMOVED
- REMOVE EX 25kVA TRF & LB CUTOUT
- COORDINATE EX. STREET LIGHT SLAR4548 FOR REMOVAL WITH POLE SVC
- RETAIN & RE-ROUTE EX. COMMERCIAL ST. LIGHT SVC TO PM V01
- REMOVE POLE AND ALL PSE RELATED FACILITIES
P03 (319434-166418) 1957 40' - CL3
- POLE TO REMAIN (FIELD GRID 319495-166420)
- INSTALL NEW 12 kV 1Ø (DE0115) 6031.1040 (S)
ALUM "H" CONN (2167000), DEADEND (2223000)
- INSTALL 12 kV 1Ø TERM, LB, (UTSU1C) 6043.1001
FUSE @ 40T (3412500)
- INSTALL SW#T85194
- ROTATE EX. OH XFMR TO SOUTH SIDE OF POLE
- INSTALL 4" PARTIAL PRI. RISER ON NEW BRACKETS (RIS4CSS) 6042.1000
- INSTALL 2" PRI. RISER ON NEW STANDOFF BRACKETS (RIS2CSS) 6042.1000
- INSTALL 1 - 3/8" DOWN GUY @ PRIMARY (GYD3SA) 6013.0100
- INSTALL 1 - 3/8" DOWN GUY @ NEUTRAL (GYD3SAN) 6013.0100
- INSTALL 10" SINGLE HELIX (ANDH1) 6012.1000 W/ 8FT LEAD (N)
CROSSING CONDUIT TABLE
X-ING
#
LOCATION GAS POWER
XING
LENGTH
ASBUILT
LOCATION
TYPE OF CROSSING
(Feeder, Primary, Secondary, etc.)FROM TO
SIZE
(IN)TYPE QTY LOCATION
SIZE
(IN)TYPE QTY
X01 'A''B'ELEC ONLY
4
SCH80
1 50 ( )'WCL
PRIMARY
2 1 50 ( )'WCL
X02 'B''F'4 40 1 S 2 SCH80 3 100 ( )'SCL GAS MAIN, PRIMARY
X03 'C''D'ELEC ONLY
4 SCH80 1 50 ( )'WCL
PRIMARY
2 SCH80 1 50 ( )'WCL
X04 'D''E'ELEC ONLY
4
SCH80
1 150 ( )'WCL PRIMARY
2 1 150
4" PVC PLUG /CAPS = 2 4" YELLOW SCH 40 PVC = 40 FT 2" SCH80 GREY PVC = 550 FT 2" PVC PLUG /CAPS = 12
4" SCH80 GREY PVC = 250 FT 4" PVC PLUG /CAPS = 6
CABLE/WIRE REMOVAL TABLE
SPAN ACTUAL LENGTH REMARKS
FROM TO CABLE TAG LENGTH CONDUIT WIRE
J02 P02 BØACG871 130 -
DEVELOPER RESPONSIBLE FOR ROUTING
STREETLIGHT CONDUCTORS FROM P02 TO
NEW PM TRANSFORMER LOCATION &
COORDINATION WITH CITY OF RENTON.
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P1A 319469-166418 55 1 2022 PSE Equip #
WIRE REMOVAL TABLE
Location
Pri Sec Wire Size & Type Quantity
Length
(ft per
conductor)RemarksFromTo
P1A P02 X #6CU PRI & NEUT 2 155
P02 P03 X #6CU PRI & NEUT 2 280
Total Feet (#6CU) REMOVED 870
VAULT & EQUIPMENT TABLE
SITE #GRID #
VAULT SIZE &
COVER
TYPE & SIZE
EQUIPMENT IN
VAULT
PRIMARY
BUSHINGS TRANSFORMER ID NUMBERS
(COMPANY ID)
AS-BUILT INFORMATION
LB DC FOREMAN: INCLUDE PHASE TAPPED
V01 319451
166417
42"x48"x38"
Unistrut HH
Matid: 7663001
37kVA MP TRF
120/240
Matid: 6247050
1 1
MINU1SR 6045.1010 BØ
J01 319463
166407
4'8"x4'8"x3'6"
w/3' Sq Door
Matid: 7663900
Cover: 7656400
1PH J-Box
w/4 Pos J-Bus
Matid: 7625900
3 1 JBOX15S 6055.1010 BØ
CAP (7630600)
Existing
J02
319458
166414
4'8"x7'x5'
w/2-3' Sq Doors
Matid: Existing
J-Box Below Grade
w/4-Pos J-Bus x3
Matid: Existing
2 -
ELB10J 6041.1000 TAP BØ
SPAN NOTES
P1A TO P02
- REMOVE ± 160' OH #6 CU PRIMARY
- REMOVED ( ' ) #6 CU
- REMOVE ± 160' OH #6 CU NEUTRAL
- REMOVED ( ' ) #6 CU
P02 TO P03
- REMOVE ± 280' OH #6 CU PRIMARY
- REMOVED ( ' ) #6 CU
- REMOVE ± 280' OH #6 CU NEUTRAL
- REMOVED ( ' ) #6 CU
P02 TO J02
- REMOVE ± 130' 1Ø 1/O AL JKT CABLE
- REMOVED ( ' ) 1/O AL
1. POLES, CONDUCTORS, DEVICES TO BE INSTALLED PER PSE STANDARDS & SPECIFICATIONS.
2. POLES ARE TO BE INSTALLED OR RELOCATED AS STAKED.
3. ALL NEW POLES SET SHALL BE THE CLASS INDICATED ON THE SKETCH OR BETTER.
4. INSTALL GROUND PLATE ASSEMBLY ON ALL NEW POLES.
5. INSTALL GRID NUMBERS ON ALL NEW AND EXISTING POLES AS SHOWN ON SKETCH.
6. TREAT ALL FIELD-DRILLED POLES WITH COPPER NAPHTHENATE WOOD PRESERVATIVE.
GENERAL OVERHEAD NOTES:
OVERHEAD CONSTRUCTION
POLES & STRUCTURES
-POLES ARE TO BE INSTALLED OR RELOCATED AS STAKED. UNLESS OTHERWISE NOTED, ALL POLE
LOCATION MEASUREMENTS ARE FROM THE CENTER OF THE POLE.
-ALL NEW POLES SET SHALL BE THE CLASS INDICATED ON THE SKETCH, OR BETTER. DO NOT SET A
LOWER CLASS POLE THAN SPECIFIED.
-INSTALL GROUND PLATE ASSEMBLY ON ALL NEW POLES. INSTALL SWITCH GROUND ASSEMBLY PER
STANDARD SPECIFICATION 6014.1000 AT NEW GANG OPERATED SWITCH LOCATIONS.
-INSTALL GRID NUMBERS ON ALL NEW AND EXISTING POLES AS SHOWN ON SKETCH.
-STRAIGHTEN EXISTING POLES AS INDICATED OR AS NECESSARY.
-TREAT ALL FIELD-DRILLED POLES WITH COPPER NAPHTHENATE WOOD PRESERVATIVE.
-REMOVE OLD POLES AFTER COMMUNICATION COMPANIES HAVE TRANSFERRED OFF AND RETURN TO
PSE STOREROOM. FILL AND CROWN POLE HOLES AND RESTORE THE AREA SIMILAR TO ADJACENT
LANDSCAPING.
CONDUCTORS & EQUIPMENT
-TRANSFER ALL OVERHEAD AND UNDERGROUND PRIMARY, SECONDARY AND SERVICE CONDUCTORS
AND GUYS TO NEW POLES SET, UNLESS OTHERWISE INDICATED ON THIS SKETCH.
-TRANSFER EXISTING TRANSFORMERS TO NEW POLES UNLESS OTHERWISE INDICATED ON THIS
SKETCH.
-USE STIRRUPS TO CONNECT ALL OVERHEAD AND UNDERGROUND PRIMARY TAPS, AND
TRANSFORMERS ABOVE 25 KVA. INSTALL AT ALL SITES BEING WORKED WITHIN THE SCOPE OF THE
PROJECT WHERE THEY ARE CURRENTLY MISSING.
-FOR 12VK CONSTRUCTION, INSTALL AVIAN PROTECTION WITH #4 CU-COVERED JUMPERS
(MID#9998076) AND #4 SD ALUMINUM COVERED TIE-WIRE (MID#8309760). FOR 34VK CONSTRUCTION
USE BARE WIRE PRIMARY JUMPERS WITH PRE-FORMED HELICAL-GRIP TIES AND AVIAN PROTECTION
DEVICES WHEN REQUIRED PER STD. 6015.2000. JUMPERS FOR POLES THAT ARE DOUBLE DEAD
ENDED WITH TREE WIRE CAN BE EITHER THE SAME SIZE TREE WIRE CONDUCTOR OR COVERED CU.
-APPLY GRIT INHIBITOR ON ALL AMPACT, STIRRUP, AND DEAD-END CONNECTIONS.
-CONNECT PRIMARY TAPS AND TRANSFORMERS TO SAME PHASE AS EXISTING UNLESS OTHERWISE
SHOWN ON THE DRAWING.
-ALL NEUTRAL CONNECTIONS TO BE MADE WITH SOLID COMPRESSION CONNECTORS. CONNECT ALL
POLE GROUNDS TO COMMON NEUTRAL.
-USE LOAD-INTERRUPTER CUTOUTS (WITH ARC SHIELDS) ON ALL PRIMARY OVERHEADS AND
UNDERGROUND TAPS WITH FUSED PROTECTION ABOVE 40T.
-INSTALL WILDLIFE PROTECTORS ON ALL TRANSFORMERS.
DEVELOPER RESPONSIBLE FOR
COORDINATION WITH PSE P.M., CITY OF
RENTON, & LAND OWNER ON TREE
REMOVAL/TRIMING AT 1826 LINCOLN AVE NE.
POTHOLE ALL EXISTING UTILITIES
RESTORATION PER CITY OF RENTON STANDARDS
MFP23002494
BØACG872
NEW 1/O AL
EJN632-BØ
NEW 1/O AL
EJN634-BØ
BØ32896
FUSE @ 40T
SW#:T85194
#4CUBFEEDHAZ
15#6CU BNFEEDHAZ
15
NEW 1/O AL
EJN631-BØ
NEW 1/O AL
EJN633-BØ
SOLID BLADE
SW#: T85315'A''B''F''C''D''E''A''B''F''C''D''E'FUSE @ 65T LINCOLN AVE NE MONTEREY PL
NE
300A S.B.LINCOLN AVE NE300A S.B.
FUSE AT 100T
NEW SW#: T88028
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
R. BLACKIE 425.457.2614 3.10.21
A.TOLENTINO -8.10.22
---
A.TOLENTINO -8.10.22
REDT # (RW-121253)CITY OF RENTON
KP DEVELOPMENT SCH73
SCHEDULE 73 OH-UG CONVERSION - 2 SPANS
1825 NE 38TH ST, RENTON, WA 98056
PUGET SOUND ENERGY
N/A N/A
N/A 101136440
AS SHOWN 5 OF 5
KING 469E -QCSOKE
32NE-T24N-R05E N/A N/A
2405E125 2405E136 2405E125 HAZ-15
COMCAST
JAMES COHN
253.569.0636
LUMEN TECH
ALEX HARB
206.345.4476
RIGHT OF WAY
FABIANA DODSON
425.456.2293
.
.
.
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
###
###
###
ELEC LEGEND - PROPOSEDNORMAL OPENN.O. WILL NOT PHASESECONDARYREMOVALPRIMARYOH TPXGAS LEGEND - PROPOSEDCASINGNEW SVC.LP MAINIP MAINHP MAINANODEBOTTOM OUT STOPPERCP TEST STATIONCUT & CAPDRIP (FUSE TIE-IN EXT.)ELBOWGAUGE TEEINLINE TEEIP VALVE LABELPIPE LINE MARKERMETERREDUCERSERVICE TEE STOPPERHVTT (HIGH VOL. TAPPING TEE)POLYVALVETEST LEAD (END OF MAIN)TEST LEAD/TRANSITION FITTINGTWIN SVC STUBSINGLE SVC STUBEFVSVC.TRANSFORMERJ-BOXSWITCHMETERE - MARKERMETERHH/PEDESTALSTUBKEYNOTECONDUITPSE POLEOH SOLID BLADERISER SOLID BLADERISER FUSEDSEC. RISERSPAN GUYDOWN GUYLABELSPOLE REMOVALPSE POLEOH FUSESPLICEFOREIGN POLE1Ø OH/UGTPX.2Ø OH/UG3Ø OH/UGLABELSHH/PEDESTALST LIGHTKEYNOTEJ-BOXXFMRSWITCHCOMBO PM XFMRPULL/SPLICE VAULTCOMBO VAULT XFMRCMB. TUT XFMRCMB. TUT XFMRSPLICE55KV TRANSMISSION115KV TRANSMISSION230KV TRANSMISSIONGAS LEGEND - EXISTINGIP MAINELEC LEGEND - EXISTINGX-ING KEYNOTEST LIGHT LABELQUAD.DUPLEXST LIGHTKEYNOTEKEYNOTEVALVEREDUCERCUT & CAPHVTTB.O. STOPPERSTOPPERSVC TEEBRANCH SADDLEDIST. REGULATORIP VALVELP VALVENEW PRIMARY UNDERGROUND CIRCUIT ONE-LINE DIAGRAM
NOT TO SCALE
NOT TO SCALE
NEW CONDUIT DIAGRAM
CONDUIT LEGEND
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT CABLE ASBUILT INFORMATION - FOREMAN COMPLETE
FROM TO SIZE
(IN)QTY.
DESIGN
LENGTH
(FT)
BENDS PULL
(LBS)
PULL
REV
(LBS)
CABLE
SIZE
DESIGN
LENGTH
(FT)
PHASE - ID TAG RECORD RECORD PHASE TAPPED & ACTUAL FOOTAGE INSTALLED LUBRICANT (Gal.)
90°45°22°11°A B C MANUFACTURER COMPOUND YEAR NOTES CONDUIT CABLE EST.ACTUAL
P1A J01 2 1 20 1 61 161 1/0 AL JKT 225 EJN631 -0.8
J01 J02 2 1 210 2 2 .382 285 1/0 AL JKT 380 EJN632 -1.4
J01 V01 2 1 125 1 .160 126 1/0 AL JKT 240 EJN633 -0.7
J02 P03 2 1 20 1 1 186 86 1/0 AL JKT 215 EJN634 -1.0
P1A P03 4 1 190 3 CONDUIT ONLY -
2" SCH80 PVC (FT) =375 5 3 0 0 1/0 AL JKT TOTAL (FT) =1060 TTL (Gal) =3.9
4" SCH80 PVC (FT) =190 0 3 0 0
PRIMARY 4"
PRIMARY 2"
ADDITIONAL PSE SYSTEM WORK
SITE SPECIFIC NOTES - CHARGE WO#593246377
P04 (319687-166431) 40' UNK, 1989
- POLE TO REMAIN
- CHANGE EX. FUSE TO 100T FUSE (3412700x3) NEW SW# T88028
P05 (319617-166431) 45' CL3, 1998
- POLE TO REMAIN
- CHANGE EX. FUSE TO SOLID BLADES (9999110x3), SW# X6898
P06 (319554-166420) 45' CL4, 1998
- POLE TO REMAIN
- CHANGE EX. FUSE TO 65T FUSE (3412600) SW: X6899
- CHANGE EX. CUTOUT TO 9999109 X3
P07 (319418-166415) UNK UNK, UNK
-POLE TO REMAIN
-CHANGE EX. FUSE TO SOLID BLADE (9999110), SW# X6899
BREAKLINE A-A (APPX. 730' SOUTH)
BREAKLINE B-B (APPX. 670' SOUTH)
BREAKLINE C-C (APPX. 1320' SOUTH; SEE RIGHT)
BREAKLINE D-D (APPX. 1320' NORTH; FROM BOTTOM LEFT)
BREAKLINE D-D (SEE LEFT)
BREAKLINE C-C (SEE LEFT)
MFP23002494