HomeMy WebLinkAboutW-422905A PORTION OF THE NW 1/4 OF SECTION 19, TOWNSHIP 23 NORTH, RANGE 5 EAST, W.M., KING COUNTY, WASHINGTON
N
N
N
^^I
n
LL
I—
3
I
I
1
3
I
I
W �
..� W
1
1 �
\ 1
1 3
1
3 W
1
wJ�
ENLARGED DOUBLE DETECTOR CHECK VALVE
.` J SCALE: N.T.S.
KEY NOTES
1� 6" DDCV ASSMBLY WITH STANDPIPE OUTSIDE CONNECTION PER STD.
PLAN 360.2/C5.3C
P� 6" D.I. CLASS 52 SERVICE PIPING, LENGTH PER PLAN
B� 6" D.I. 90 DEGREE FITTING WITH CONCRETE THRUST BLOCK
8"X6" TAPPING TEE (MJxFL) WITH CONCRETE THRUST BLOCK
:� 6" GATE VALVE (FLxMJ)
4" x 2 Y2" FIRE DEPARTMENT DOUBLE CONNECTION
7� SUMP PUMP PER 520/C5.3C
8� INSTALL FIRE HYDRANT PER STD. PLAN 310.1/C5.4C
REMOVE EXISTING HYDRANT AND PIPE
GENERAL NOTES
1. SEE STD. PLAN 330.2/C5.3C FOR CONCRETE THRUST BLOCKS.
2. SEE STD. PLAN 360.2/C5.3C FOR ALL APPURTENANCES AND
DIMENSIONS ASSOCIATED WITH DDCV ASSEMBLY.
• Call 811
• ® two business days
before you dig NO.
5
REVISION
HORIZONTAL SCALE: 1"=5'
0 5 10
TESTING DETAIL
TAPPING TEE (MJxFL)
TAPPING GATE VALVE (FL XMJ)
TEMPORARY PLUG (MJ) WITH 2-INCH TAP
AND 2-INCH BLOW -OFF ASSEMBLY
CONCRETE BLOCKING
VERTICAL CROSS(MJxFL) FOR POLYPIGGING
1-BLIND FLANGE ON TOP WITH 2" TAP AND 2" PLUG
1-BLIND FLANGE ON BOTTOM
1-PLUG(MJ) WITH 2"TAP & 2" BLOW -OFF
TEMPORARY BLOCK
FINAL CONNECTION DETAIL
' O NEW D.I. WATER LINE
(AFTER ALL CLEANING BY POLYP G, PRESSURE TESTIN
G
AND DISINFECTION, REMOVE TEMPORAY BLOCK & BLOW -OFF
AND CONNECT TO VALVE WITH D.I. SLEEVE (MJ) & D.I. SPOOLS
FINAL CONNECTION BY CITY FORCES
NOTES:
1. TAPPING TEES SHALL BE MADE OF CAST IRON, DUCTILE IRON OR
EPDXY -COATED STEEL. BOLTS AND NUTS SHAL BE COR-TEN. ALL TEES
AND VALVES SHALL BE WATER TESTED BEFORE TAP
2. NO SIZE ON S1ZE TAPS ON CAST-IRON WATER LINES. TAP SHALL BE AT
LEAST 2" SMALLER DIAMETER THAN THE EXISTING MAIN.
3. NO WET TAP ON ASBESTOS CEMENT LINE OR STEEL LINE
4. WET -TAPPING OF EXISTING CITY OF RENTON WATER MAINS WILL BE DONE BY
SPEER TAP OR SUPERIOR TAPPING INC.
5. CONTRACTOR SHALL POTHOLE AND VERIFY THE HORIZONTAL AND VERTICAL
ALIGNMENT OF EXISTING LINE OR STUB AND SHALL START LAYING THE NEW
LINE AT THE SAME HORIZONTAL AND VERTICAL ALIGNMENT OF THE EXISTING
STUB.
6. CITY FORCES WILL PERFORM THE FINAL CONNECTION FROM THE WATER LINE
TO THE TAPPING VALVE WITH D.I. SLEEVE AND D.I. SPOOL.
tip'
PUBLIC WORKS CONNECTION TO WATER MAIN WITH STD. PLAN — 300.1
i DEPARTMENT TAPPING TEE & VALVE MARCH 2O10
F
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR
COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER
SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL
JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2"
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR,
4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS
STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE
PAINT No. 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO
BE USED IF REQUIRED.
MIN. 18" TO 20" BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
3'
SIDEWALK THAT IS ADJACENT TO
CURB
x x 5" STORZ
5'x5'x5x6" THICK CONCRETE PAD AROUND
HYDRANT. FINISH TO MATCH SIDEWALK
O
2
EXPANSION JOINT AT
BACK OSIDEWALK
�fCRETE SIDEWALK
ORNPLANTING STRIP
36" MIN
COVER
TWO-PIECE CAST IRON VALVE BOX WITH LUG
TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO.
STANDARD 8" TOP SECTION WITH REGULAR BASE
SECTION LENGTH TO FIT. VALVE NUT EXTENSION
AS REQUIRED.
RAISED PAVEMENT MARKER TYPE 88-A
STIMSONITE TWO-WAY BLUE REFLECTIVE
CONCRETE BLOCKING
CONCRETE J y�
THRUST BLOCK
MAIN LINE TEE. WITH 6" FLANGE SIDE OUTLET.
i
GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
i
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2-3/4" COR-TEN STEEL TIE RODS.
16" x 8" x 4" MININUM 1/2 YARD OF 1-1/4" WASHED DRAIN ROCK
CONCRETE BEARING 1' ABOVE BOOT FLANGE. PLACE 8 MIL
BLOCK UNDER HYDRANT POLYETHYLENE FILM AROUND TOP AND SIDES OF
GRAVEL.
FIRE HYDRANT ASSEMBLY
LEVEL ALL GROUND
LEVEL ALL GROUND
MIN 3' RADIUS
MIN 3' RADIUS
1 ONE MAN ROCK
s
6" CONCRETE PAD 16" CONCRETE PAD
CUT FILL
HYDRANT LOCATION IN CUT OR FILL
a PUBLIC WORKS FIRE HYDRANT ASSEMBLY STD. PLAN — 310.1
DEPARTMENT
�EV,�os MARCH 2O10
SURVEYED:
DESIGNED:
DKM/RJJ
DRAWN:
KLK/DKM
CHECKED:
DCD
BY DATE APPR APPROVED:
DCD
SCALE:
AS NOTED
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
w 120 VOLT ELECTRICAL OUTLET FOR
z HEAT TAPE. INSTALL HEAT TAPE
r FOR FREEZE PROTECTION
3 CENTER BACKFLOW
I PREVENTER IN
O o REDUCED PRESSURE ENCLOSURE
BACKFLOW ASSEMBLY
(RPBA) 3" MIN.
� O
3" MIN. INSULATED ENCLOSURE
3" MIN. "HOT BOX" OR EQUAL
3/8" X 4" ANCHOR
BOLTS PER
MANUFACTURER O
�— 3" MIN.
CONCRETE SLAB z UNION FINISHED
N GRADE
FINISHED
GRAD
00 VFW w DRAIN
z SEE NOTE 4
6" MINIMUM SLEEVE
FREE DRAINING (TYP.)
GRAVEL z
CONNECT TO N
WATER METER
IMMEDIATELY
ADJACENT TO
RPBA
FLOW
INSTALLED W/ APP'D. TO OWNERS ELECTRICAL PANEL. FRONT VIEW
MATERIAL PER UPC DIRECT BURIAL OR IN RIGID METER SIDE
(SIZE AS REQ.) CONDUIT PER ELECTRICAL
SIDE VIEW PERMIT REQUIREMENTS.
NOTES:
1. ALL REDUCED PRESSURE BACKFLOW ASSEMBLIES (RPBA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW
PREVENTION ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF
WASHINGTON DEPARTMENT OF HEALTH.
2. THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION
OF THE INSTALLATION OF THE RPBA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE
RPBA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN.
3. THE RPBA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL
INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST
REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., ATTN: WATER
UTILITY CROSS —CONNECTION CONTROL SPECIALSIT, FAX NO. 425-430-7241.
4. DRAIN SHALL BE SIZED IN ACCORDANCE WITH AWWA CROSS CONNECTION CONTROL MANUAL STANDARDS
3" DRAIN FOR 1" OR SMALLER RPBA's, 4" DRAIN FOR 1.5" TO 2" RPBA's, 6" FOR 3" RPBA's.
5. RPBA AND ENCLOSURE SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE
WATER METER.
2Y STD. PLAN — 350.2
�u PUBLIC WORKS REDUCED PRESSURE BACKFLOW
DEPARTMENT ASSEMBLY IN HOT BOX
'�'f� • MARCH 2O10
•
o CITY OF
R RENTON
vugv
Planning/Building/Public Works Dept.
�D C. sitts&hill
9
p� of �`9G
4 C rJp 6,UJA
CIVIL I STRUCTURAL I SURVEY
4815 CENTER STREET I TACOMA, WA. 98409
j V PHONE: (253) 474-9449 I FAX: (253) 474-0153
http://www.sittshill.com/
Project No.: 19480 Project Mgr.: DCD
46449 4
��ic�Str+ISi 99' G`�ik� �!4 Proj. Engineer: DKM/RJJ Proj. Drafter: KLK/DKM
SIpNpL
4M. W-422905
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
DEVELOPMENT ENGINEERINGAr% �'IL
NJanders '
CURRENT PLANNING
AMorganroth [05/09/20231 '
DATE:
BROTHERTON CADILLAC - RENTON
FIELDBOOK:
PAGE:
WASTEWATER AND WATER UTILITIES DETAILS C5.4C
(PRIVATE AND PUBLIC) SHEET: 3
1 OF:39
N
T
O
O
O
N
N
,.IN
N
T
O
O
O
N
Q
J
LO
CM
O
O
N
6 1
u