HomeMy WebLinkAbout310.1CL
A HYDRANT
COMPRESSION TYPE HYDRANT (SEE APPROVED MATERIALS LIST) WITH 6" MJ INLET WITH LUGS, 5 1 4" MVO,
1 1 4" PENTAGON OPERATING NUT, TWO (2) 2 1 2" NST HOSE NOZZLES, AND 4.875" SST PUMPER NOZZLE
EQUIPPED WITH 5" STORZ ADAPTER AND 1/8" STAINLESS STEEL CABLE, WITH EXTENSION IF NECESSARY.
TEE MAIN LINE TEE WITH 6" FLANGE SIDE OUTLET
VALVE 6" GATE VALVE (FLxMJ)
VALVE BOX VALVE BOX AND LID PER STD PLAN 330.7
PIPE CLASS 52 DI, LENGTH TO FIT
JOINT RESTRAINT MECHANICAL JOINT RESTRAINT WITH CONCRETE BLOCKING OR (2) 3/4" CORTEN STEEL TIE RODS
GRAVEL 1 1 4" WASHED DRAIN ROCK, MINIMUM 1' ABOVE BOOT FLANGE WITH 8-MIL POLYETHYLENE SHEETING
AROUND TOP AND SIDES OF GRAVEL
CONCRETE BLOCK MINIMUM 16"x8"x4" CONCRETE BLOCKS UNDER FIRE HYDRANT AND GATE VALVE
BLOCKING CONCRETE BLOCKING PER STD PLAN 330.1
SHEAR BLOCK 4'x4'x6" CONCRETE SHEAR BLOCK AROUND FIRE HYDRANT, SEE STANDARD DETAIL 310.2
PAVEMENT MARKER BLUE REFLECTIVE PAVEMENT MARKER PER STD PLAN 310.3
BE
K
MAIN ROADWAY OR NEAREST LANE CHANNELIZATION1'
MIN
A1' MIN
4"4" MINIMUM
F
MATERIALS
NOTES:
1.FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF SAFETY YELLOW DTM ACRYLIC GLOSS OR ENAMEL PAINT.
2.PUMPER NOZZLE TO FACE ROADWAY OR AS DIRECTED BY RRFA.
3.A MINIMUM 3' RADIUS UNOBSTRUCTED WORKING AREA SHALL BE PROVIDED AROUND THE OUTSIDE OF THE HYDRANT.
H
H
J
G
D
C I
B
C
D
E
F
G
H
I
J
K
F
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
FIRE HYDRANT ASSEMBLY
STD. PLAN - 310.1
6/28/2023