Loading...
HomeMy WebLinkAbout310.1CL A HYDRANT COMPRESSION TYPE HYDRANT (SEE APPROVED MATERIALS LIST) WITH 6" MJ INLET WITH LUGS, 5 1 4" MVO, 1 1 4" PENTAGON OPERATING NUT, TWO (2) 2 1 2" NST HOSE NOZZLES, AND 4.875" SST PUMPER NOZZLE EQUIPPED WITH 5" STORZ ADAPTER AND 1/8" STAINLESS STEEL CABLE, WITH EXTENSION IF NECESSARY. TEE MAIN LINE TEE WITH 6" FLANGE SIDE OUTLET VALVE 6" GATE VALVE (FLxMJ) VALVE BOX VALVE BOX AND LID PER STD PLAN 330.7 PIPE CLASS 52 DI, LENGTH TO FIT JOINT RESTRAINT MECHANICAL JOINT RESTRAINT WITH CONCRETE BLOCKING OR (2) 3/4" CORTEN STEEL TIE RODS GRAVEL 1 1 4" WASHED DRAIN ROCK, MINIMUM 1' ABOVE BOOT FLANGE WITH 8-MIL POLYETHYLENE SHEETING AROUND TOP AND SIDES OF GRAVEL CONCRETE BLOCK MINIMUM 16"x8"x4" CONCRETE BLOCKS UNDER FIRE HYDRANT AND GATE VALVE BLOCKING CONCRETE BLOCKING PER STD PLAN 330.1 SHEAR BLOCK 4'x4'x6" CONCRETE SHEAR BLOCK AROUND FIRE HYDRANT, SEE STANDARD DETAIL 310.2 PAVEMENT MARKER BLUE REFLECTIVE PAVEMENT MARKER PER STD PLAN 310.3 BE K MAIN ROADWAY OR NEAREST LANE CHANNELIZATION1' MIN A1' MIN 4"4" MINIMUM F MATERIALS NOTES: 1.FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF SAFETY YELLOW DTM ACRYLIC GLOSS OR ENAMEL PAINT. 2.PUMPER NOZZLE TO FACE ROADWAY OR AS DIRECTED BY RRFA. 3.A MINIMUM 3' RADIUS UNOBSTRUCTED WORKING AREA SHALL BE PROVIDED AROUND THE OUTSIDE OF THE HYDRANT. H H J G D C I B C D E F G H I J K F PUBLIC WORKS DEPARTMENT APPROVED: DATEMartin Pastucha Public Works Administrator FIRE HYDRANT ASSEMBLY STD. PLAN - 310.1 6/28/2023