HomeMy WebLinkAbout320.2A TEE 2" TAPPED REDUCING TEE (MJxFIPT)2" TAPPED REDUCING TEE (MJxFIPT)
PIPE 2" BRASS NIPPLE (MIPT), 4" LENGTH 2" BRASS NIPPLE (MIPT), 4" LENGTH
VALVE 2" GATE VALVE (FIPT) WITH SQUARE OPERATING
NUT AND EXTENSION PER STD PLAN 330.7
2" GATE VALVE (FIPT) WITH SQUARE OPERATING
NUT AND EXTENSION PER STD PLAN 330.7
VALVE BOX VALVE BOX AND LID PER STD PLAN 330.7 VALVE BOX AND LID PER STD PLAN 330.7
COUPLING 2" x 1 1 2" BRASS COUPLING (MIPT x PACK JOINT),
FORD C44-76-Q-NL OR EQUAL
2" BRASS COUPLING (MIPT x PACK JOINT), FORD
C84-77-Q-NL OR EQUAL
TUBING 1 1 2" TYPE "K" SOFT COPPER TUBING 2" TYPE "K" SOFT COPPER TUBING
BEND
1 1 2" 90° BRASS BEND (PACK JOINT x PACK JOINT OR
PACK JOINT x FIPT), FORD L44-66-Q-NL OR
L41-66-Q-NL OR EQUAL
2" 90° BRASS BEND (PACK JOINT x PACK JOINT OR
PACK JOINT x FIPT), FORD L44-77-Q-NL OR
L41-77-Q-NL OR EQUAL
METER SETTER
1 1 2" VERTICAL METER SETTER WITH BYPASS,
FLANGED ANGLE BALL VALVE AND PADLOCK WINGS
ON INLET, ANGLE CHECK VALVE ON OUTLET, AND
BALL VALVE ON BYPASS WITH PADLOCK WINGS,
FORD VBH86-12B-11-66-Q-NL, A.Y. MCDONALD
730B-612WDFF665, OR MUELLER B-2427N (1 1 2"),
BYPASS NOT PERMITTED ON IRRIGATION METERS
2" VERTICAL METER SETTER WITH BYPASS, FLANGED
ANGLE BALL VALVE AND PADLOCK WINGS ON INLET,
ANGLE CHECK VALVE ON OUTLET, AND BALL VALVE
ON BYPASS WITH PADLOCK WINGS,
FORD VBH87-12B-11-77-Q-NL, A.Y. MCDONALD
730B-612WDFF665, OR MUELLER B-2427N (2"),
BYPASS NOT PERMITTED ON IRRIGATION METERS
METER SPREADER 13 3 16" RIGID METER SPREADER (TEMPORARY)17 3 16" RIGID METER SPREADER (TEMPORARY)
WATER METER AMI WATER METER WITH RADIO AND BATTERY UNIT,
TO BE SUPPLIED AND INSTALLED BY CITY FORCES
AMI WATER METER WITH RADIO AND BATTERY UNIT,
TO BE SUPPLIED AND INSTALLED BY CITY FORCES
METER BOX
17"X30" METER BOX, ARMORCAST A6001640PCX18,
WITH METER BOX LID, ARMORCAST
A6001947RCI-H7, TO READ "RENTON WATER"
17"X30" METER BOX, ARMORCAST A6001640PCX18,
WITH METER BOX LID, ARMORCAST
A6001947RCI-H7, TO READ "RENTON WATER"
COUPLER
1 1 2" COUPLER (PACK JOINT x PACK JOINT), FORD
C4#-6#-Q-NL OR EQUAL, WITH GALVANIZED PLUG IF
PRIVATE SERVICE LINE IS NOT YET INSTALLED
2" COUPLER (PACK JOINT x PACK JOINT), FORD
C4#-7#-Q-NL OR EQUAL, WITH GALVANIZED PLUG IF
PRIVATE SERVICE LINE IS NOT YET INSTALLED
GRAVEL CRUSHED ROCK BASE TO SUPPORT METER BOX,
METER BYPASS TO BE EXPOSED
CRUSHED ROCK BASE TO SUPPORT METER BOX,
METER BYPASS TO BE EXPOSED
B
C
D
E
F
G
H
I
J
K
L PROPERTY LINEPROPERTY LINEFINISHED GRADE SIDEWALK
21" TO 30"24" TO 30"12"
IN UNIMPROVED ROW
INSTALL METER BOX AT
PROPERTY LINE WITH
12" COPPER TAILPIECE
CITY
PIPING PIPING
PRIVATE
A B C
D
G
H
I
JK
F
L
M
MAIN
MATERIALS 1 1/2" SERVICE 2" SERVICE
9" TO 12"
F
E
M
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
1 1 2" AND 2" WATER SERVICE
IN PLANTING STRIP
STD. PLAN - 320.2
6/28/2023