HomeMy WebLinkAbout320.4ELEVATION
PIPE SLEEVE
V
H
O
P
T
S
J K L M N
E D
C
A B
U
EB
C
D
T
Q
PVC PIPE SLEEVE
EPOXY SEALANT
EPDM MODULAR SEAL,
LINK-SEAL MODEL C
WITH 316SS BOLTS AND NUTS
PIPE
6"
MIN
6"
MIN
12" MIN
6"
MIN
6"
MIN
12"
MIN
6"
MIN
6"
MIN
R
PLAN
C
F
G
I
Q
PIPE SLEEVE
SEE DETAIL, THIS SHEET
R
Q
PIPE SLEEVE
SEE DETAIL THIS SHEET
S
A
12"
MIN
W
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
3", 4", AND 6" WATER METER
STD. PLAN - 320.4 Sht. 1 of 2
6/28/2023
MATERIALS
NOTES:
1.VAULTS SHOULD NOT BE INSTALLED IN AREAS WITH VEHICLE TRAFFIC.
2.ALL INTERIOR METAL INCLUDING PIPE, VALVES, AND FITTINGS TO BE PAINTED WITH TWO COATS OF EPOXY AS APPROVED BY THE
ENGINEER. USE TNEMEC SERIES 135 CHEMBUILD MODIFIED POLYAMIDE EPOXY. APPLY PER MANUFACTURERS INSTRUCTIONS.
3.VAULT AND HATCH MODELS ARE PROVIDED AS REFERENCE. SHOP DRAWINGS SHALL BE SUBMITTED TO THE CITY FOR APPROVAL.
4.FOR 3" AND 4" METERS, USE 2" BYPASS MATERIALS, AND FOR 6" METERS, USE 3" BYPASS MATERIALS, AS INDICATED BELOW.
5.INSTALL WATER METER RADIO & BATTERY UNITS IN ACCESS HATCH PANELS WITH MINIMUM 6" SEPARATION.
A
VAULT MODEL NUMBERS
METER SIZE VAULT BASE PIECE CENTER PIECE TOP PIECE ACCESS HATCH
3"676-WA NO. 676-BL NO. 676-MLW NO. 676-TL-2-332P HHD-1C
4"676-WA NO. 676-BL NO. 676-MLW NO. 676-TL-2-332P HHD-1C
6"4484-LA NO. 4484-BL NO. 4484-ML NO. 4484-TL-2-332P HHD-2D
METER AMI WATER METER (SENSUS OMNI WITH INTERNAL STRAINER) WITH RADIO AND BATTERY UNIT
METER TEST PORT
2" BRASS NIPPLE (MIPTxMIPT), 6" LONG, CONNECTED TO TEST PORT OF COMPOUND METER
1" BALLCORP (MIPTxFIPT), FORD FB1700-4-NL OR EQUAL, FOR 3" METER
OR 1 1 2" BALLCORP (MIPTxFIPT), FORD FB1700-6-NL OR EQUAL, FOR 4" AND 6" METERS
2"X2 1 2" ADAPTER (MIPTxMNST)
2 1 2" CAP (FNST)
ADAPTER FLANGED COUPLING ADAPTER, MEGAFLANGE SERIES 2100, OR EQUAL
PIPE CLASS 53 DI PIPE (PExFL)
VALVE (2) GATE VALVE (FLxFL) WITH HANDWHEEL
PIPE SUPPORT ADJUSTABLE PIPE SADDLE SUPPORT, GRINNELL FIG 264 OR EQUAL, WITH BASE, BOLTED TO FLOOR
SERVICE SADDLE (2) 2" NPT SADDLE, SMITH-BLAIR MODEL 313 OR EQUAL OR (2) 6"X3" TEE (MJxFL)
BYPASS VALVE (2) 2" BRASS GATE VALVE (IPT) OR (2) 3" GATE VALVE (FLxFL) WITH 3" THREADED (IPT) FLANGE
BEND (2) 2" 90° BEND OR (2) 3" 90° BEND
BYPASS PIPE 2" GALVANIZED PIPE, EPOXY COATED, OR 3" GALVANIZED PIPE, EPOXY COATED
BYPASS METER VALVE 2" STRAIGHT FLANGE BALL VALVE (FLxFIPT) WITH PADLOCK WINGS, FORD BF31-777W-NL OR EQUAL
OR 3"x2" REDUCER WITH 2" BRASS NIPPLE
BYPASS METER 2" AMI BYPASS METER WITH RADIO AND BATTERY UNIT, TO BE PROVIDED BY THE CITY
METER FLANGE 2" METER FLANGE (FLxFIPT), FORD CF31-77-NL OR EQUAL, OR 3"x2" REDUCER WITH 2" BRASS NIPPLE
UNION 2" TWO-PART UNION OR 3" TWO-PART UNION
TEE 2" TEE OR 3" TEE
BUSHING 2"x3/4" BUSHING OR 3"x3/4" BUSHING WITH 3/4" PLUG
WATER MAIN CLASS 52 DI PIPE WITH RESTRAINED JOINTS
WALL FLANGE MIDSPAN PIPE RESTRAINT WITH CONCRETE BLOCKING PER STD PLAN 350.7
CONCRETE VAULT OLDCASTLE PRECAST VAULT, MODEL NUMBERS PER TABLE BELOW, OR EQUAL
DRAIN MINIMUM 4" PVC FLOOR DRAIN, SLOPE TO STORM DRAIN OR DAYLIGHT TO DRAINAGE DITCH WITH WIRE
MESH RODENT SCREEN AT DRAIN OUTLET, SEAL PIPE PENETRATION WITH WATER-TIGHT GROUT
ACCESS HATCH TWO LOCKING HINGED ALUMINUM DOORS, TRAFFIC-RATED, WITH SLIP-RESISTANT TREATMENT, MARKED
"WATER", LW PRODUCTS MODEL NUMBERS PER TABLE BELOW, OR EQUAL.
LADDER GALVANIZED STEEL LADDER SECURED TO VAULT PER STD PLAN 350.8
GRAVEL FOUNDATION GRAVEL PER WSDOT STANDARD SPECIFICATIONS, 12" MINIMUM ALL DIRECTIONS
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
3", 4", AND 6" WATER METER
STD. PLAN - 320.4 Sht. 2 of 2
6/28/2023