HomeMy WebLinkAbout330.1NOTES: 1.MINIMUM BEARING AREA MUST BE ADJUSTED FOR PIPE SIZE, PRESSURE, AND SOIL CONDITIONS. 2.FITTINGS SHALL BE POLYWRAPPED PRIOR TO POURING CONCRETE BLOCKING. 3.CONCRETE BLOCKING SHALL BE CAST IN PLACE AND SHALL HAVE A MINIMUM OF 0.25 SF BEARING AREA AGAINST THE FITTING. 4.CONCRETE BLOCKING SHALL BEAR AGAINST FITTINGS ONLY AND SHALL BE CLEAR OF JOINTS TO PERMIT TAKING UP OR DISMANTLING JOINT. 5.CONTRACTOR SHALL INSTALL BLOCKING ADEQUATE TO WITHSTAND FULL HYDROSTATIC TEST PRESSURE AS WELL AS TO CONTINUOUSLY WITHSTAND OPERATING PRESSURE UNDER ALL CONDITIONS OF SERVICE. 6.ALL CONCRETE SHALL BE MECHANICALLY MIXED. JOB SITE MIXING, HAND-MIXED CONCRETE, AND MOBILE CONCRETE MIXERS ARE NOT ALLOWED. 7.IN MUCK OR PEAT, ALL THRUSTS SHALL BE RESTRAINED BY PILES OR TIE RODS TO SOLID FOUNDATION OR MUCK OR PEAT SHALL BE REMOVED AND REPLACED WITH BALLAST OF SUFFICIENT STABILITY TO RESIST THRUST. 8.CONCRETE BLOCKING SHALL BE LEFT OPEN OR SHEETED FOR MINIMUM 24 HOURS. MINIMUM BEARING AREA AGAINST UNDISTURBED SOIL (SF) * PIPE SIZE PRESSURE (PSI) 4"200 300 2/(1) 3/(2) 1/(NONE ) 2/(2) 1/(NONE ) 2/(1) NONE 1/(1) NONE NONE 6"200 300 4/(3) 6/(4) 3/(2) 4/(3) 3/(1) 3/(2) 1/(1) 2/(1) 1/(NONE ) 1/(NONE ) 8"200 300 7/(5) 11/(8) 5/(3) 8/(5) 4/(3) 6/(4) 2/(2) 3/(2) 1/(1) 2/(1) 10"200 275 11/(8) 16/(11) 8/(6) 11/(7) 6/(4) 9/(6) 3/(2) 5/(3) 2/(1) 3/(2) 12"200 250 16/(11) 24/(16) 11/(8) 17/(11) 9/(6) 13/(9) 5/(3) 7/(5) 3/(2) 4/(3) 14"200 250 22/(13) 33/(22) 16/(11) 23/(16) 12/(8) 18/(12) 6/(4) 9/(6) 3/(2) 5/(3) 16"200 225 29/(19) 32/(21) 21/(14) 23/(16) 16/(11) 17/(12) 8/(6) 9/(6) 5/(3) 5/(3) 18"200 36/(24)26/(17)20/(13)10/(7)5/(4) 20"200 45/(29)32/(21)24/(16)13/(8)7/(4) 24"200 64/(43)46/(30)35/(23)18/(12)9/(6) * VALUES BASED ON SAFE BEARING LOAD OF 2,000/(3,000) PSF SOIL TYPE SAFE BEARING LOAD (PSF) MUCK OR PEAT 0 SOFT CLAY 1,000 SAND 2,000 SAND AND GRAVEL 3,000 CEMENTED WITH CLAY 4,000 HARD SHALE 10,000 E B D A C B A B C D E 11 1 4° BEND 22 1 2° BEND 45° BEND90° BEND CAP / PLUG TEE PUBLIC WORKS DEPARTMENT APPROVED: DATEMartin Pastucha Public Works Administrator CONCRETE BLOCKING FOR HORIZONTAL FITTINGS STD. PLAN - 330.1 6/28/2023