Loading...
HomeMy WebLinkAbout330.2NOTES: 1.CONCRETE BLOCKING SIZES BASED ON 200 PSI HYDROSTATIC PRESSURE AND 3,000 PSI CONCRETE. 2.ALL CONCRETE SHALL BE MECHANICALLY MIXED. JOB SITE MIXING, HAND-MIXED CONCRETE, AND MOBILE CONCRETE MIXERS ARE NOT ALLOWED. 3.PIPE CLAMPS AND ANCHOR RODS SHALL BE INSTALLED PER STD PLAN 330.4. 4.FITTINGS SHALL BE POLYWRAPPED AFTER INSTALLATION OF PIPE CLAMPS AND ANCHOR RODS PRIOR TO POURING CONCRETE BLOCKING. 5.WATER MAIN SHALL NOT BE PRESSURIZED UNTIL ALL TRENCHING WITHIN 100' OF VERTICAL BEND IS BACKFILLED AND COMPACTED TO MINIMUM 3' COVER. 6.CONCRETE BLOCKING SHALL BE LEFT OPEN OR SHEETED FOR MINIMUM 24 HOURS. MINIMUM DIMENSIONS PIPE SIZE BEND VOLUME (CF)A D *L 4" 11 1 4°8 2.0'3 4"1.5' 22 1 2°11 2.2' 3 4"2.0' 45°30 3.1' 6" 11 1 4°11 2.2' 3 4"2.0'22 1 2°25 2.9' 45°68 4.1' 8" 11 1 4°16 2.5' 3 4"2.0'22 1 2°47 3.6' 45°123 5.0' 12" 11 1 4°32 3.2' 3 4" 2.0' 22 1 2°88 4.5'3.0' 45°232 6.1'2.5' 16" 11 1 4°70 4.1'1"3.0' 22 1 2°184 5.7' 1 1 8"4.0' 45°478 7.8' 20" 11 1 4°91 4.5' 1 1 4" 3.0' 22 1 2°225 6.1' 4.0' 45°560 8.2' 24" 11 1 4°128 5.0'1 1 4"3.5' 22 1 2°320 6.8' 1 3 8"4.5' 45°820 9.4' * D = ANCHOR ROD DIAMETER 45° BEND L L A A A A L L 11 1 4° AND 22 1 2 ° BENDS PIPE CLAMP AND ANCHOR ROD PIPE CLAMP AND ANCHOR ROD PUBLIC WORKS DEPARTMENT APPROVED: DATEMartin Pastucha Public Works Administrator CONCRETE BLOCKING FOR VERTICAL FITTINGS STD. PLAN - 330.2 6/28/2023