HomeMy WebLinkAbout330.3NOTES: 1.NO CHANGE IN PIPE DIRECTION OR DIAMETER SHALL OCCUR WITHIN 36' OF THE VERTICAL BEND. BENDS, TEES, REDUCERS, ETC. BEYOND THE 36' LIMIT MAY BE RESTRAINED BY STANDARD CONCRETE BLOCKING PER STD PLANS 330.1 AND 330.2. 2.FITTINGS SHALL BE POLYWRAPPED AFTER INSTALLATION OF PIPE CLAMPS AND ANCHOR RODS PRIOR TO POURING CONCRETE BLOCKING. 3.PIPE CLAMPS AND ANCHOR RODS SHALL BE INSTALLED PER STD PLAN 330.4. 4.JOINT RESTRAINT SHALL BE MEGALUG SERIES 1100 OR EQUAL. 5.WATER MAIN SHALL NOT BE PRESSURIZED UNTIL ALL TRENCHING WITHIN 100' OF VERTICAL BEND IS BACKFILLED AND COMPACTED TO MINIMUM 3' COVER. 6.90° VERTICAL BENDS SHALL ONLY BE INSTALLED WHERE GIVEN PRIOR APPROVAL BY THE CITY. 7.ALL CONCRETE SHALL BE MECHANICALLY MIXED. JOB SITE MIXING, HAND-MIXED CONCRETE, AND MOBILE CONCRETE MIXERS ARE NOT ALLOWED. 8.BACKFILL TRENCH BEYOND 90° VERTICAL BLOCK WITH CRUSHED SURFACING TOP COURSE MATERIAL COMPACTED TO 95% MDD. CRUSHED BACKFILL SHALL EXTEND 20' BEYOND BLOCK OR TO FIRM BEARING TRENCH WALL, WHICHEVER IS LESS. 9.CONCRETE BLOCKING SHALL BE LEFT OPEN OR SHEETED FOR MINIMUM 24 HOURS. MINIMUM DIMENSIONS PIPE SIZE BEND VOLUME (CF)A D *L 4" 11 1 4° BLOCKING NOT REQUIRED22 1 2° 45° 90°16 2.5'3 4"2.0' 6" 11 1 4° BLOCKING NOT REQUIRED 22 1 2° 45°13 2.3'3 4"2.0' 90°43 3.5'3 4"2.0' 8" 11 1 4° BLOCKING NOT REQUIRED 22 1 2° 45°33 3.2'3 4"2.0' 90°86 4.4'3 4"2.0' 10" 11 1 4°BLOCKING NOT REQUIRED 22 1 2°13 2.3'3 4"2.0' 45°64 4.0'3 4"2.0' 90°141 5.2'1"3.5' 12" 11 1 4°BLOCKING NOT REQUIRED 22 1 2°20 2.7'3 4"2.0' 45°111 4.8'3 4"2.0' 90°206 5.9'1 1 8"4.0' * D = ANCHOR ROD DIAMETER MINIMUM DIMENSIONS BASED ON FOLLOWING CONDITIONS: • PIPE RESTRAINED MINIMUM 36' ON EACH SIDE OF BEND • SAFE BEARING LOAD = 1,000 SF • CONCRETE STRENGTH = 3,000 PSI • CONCRETE WEIGHT = 150 PCF • HYDROSTATIC PRESSURE = 200 PSI • TRENCH = TYPE 2 FLAT BOTTOM TRENCH WITH LIGHTLY CONSOLIDATED BACKFILL PER ANSI/AWWA C150/A21.50 • FACTOR OF SAFETY = 1.5 • SOIL FRICTIONAL RESISTANCE BASED ON COHESIVE GRANULAR SOIL (GC+SC), SAND, GRAVEL, CLAY MIXTURE CONCRETE BLOCKING DESIGN MUST BE ADJUSTED FOR VARIANCES IN ANY OF THESE CONDITIONS. 45° BEND L L A A A A L L 11 1 4° AND 22 1 2 ° BENDS PIPE CLAMP AND ANCHOR ROD PIPE CLAMP AND ANCHOR ROD A A L L 90° BEND PIPE CLAMP AND ANCHOR ROD PUBLIC WORKS DEPARTMENT APPROVED: DATEMartin Pastucha Public Works Administrator CONCRETE BLOCKING FOR VERTICAL FITTINGS WITH RESTRAINED JOINTS STD. PLAN - 330.3 6/28/2023