HomeMy WebLinkAbout340.1PLAN
PROFILE
TEE MAIN LINE TEE WITH 4" SIDE OUTLET (MJxFL) WITH PLUG (MJ)
GATE VALVE 4" GATE VALVE WITH 2" SQUARE OPERATING NUT AND VALVE OPERATING NUT EXTENSION AS REQUIRED
PER STD PLAN 330.1
VALVE BOX AND LID VALVE BOX AND LID PER STD PLAN 330.8
FLANGE 4"x2" TAPPED FLANGE (FLxFIPT)
PIPE 2" BRASS OR BRONZE NIPPLE, LENGTH TO FIT
BEND 2" 90° BRASS BEND (FIPT x PACK JOINT), FORD C14-77-Q-NL OR EQUAL
ADAPTER 2"x2 1 2" BRASS ADAPTER (FIPTxMNST)
CAP 2 1 2" CAP (FNST) WITH GASKET, NOT VENTED
METER BOX AND LID METER BOX, ARMORCAST A6001640PCX18, WITH METER BOX LID, ARMORCAST A6001947RCI-H7, TO READ
"RENTON WATER", EXPANSION JOINTS MUST BE INSTALLED 12" MINIMUM ON BOTH SIDES OF METER BOX
BLOCKING CONCRETE BLOCKING PER STD PLAN 330.1
FINISHED GRADE
MAIN
A
C
DB
F
E
6"
E
G
I
I
A
B
D
H
4" TO 6"
H
A
B
C
D
E
F
G
H
I
J
J
J
MATERIALS
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
2" BLOW-OFF ASSEMBLY
(PERMANENT)
STD. PLAN - 340.1
6/28/2023