HomeMy WebLinkAbout340.3CORPORATION STOP 1" BALLCORP WITH AWWA TAPERED (CC) INLET AND COPPER THREAD OUTLET, FORD FB600-4-NL OR EQUAL
SWING JOINT 1" BRASS SWING JOINT
PIPE 1" TYPE "K" SOFT COPPER TUBING
COUPLING 1" STRAIGHT COUPLING (MIPT x PACK JOINT), FORD C84-44, MUELLER H15428, OR EQUAL
GATE VALVE 1" BRONZE GATE VALVE, THREADED, RED-WHITE VALVE NO. 280, OHIO BRASS NO. 2500, OR EQUAL
UNION 1" BRASS UNION
PIPE 1" BRASS NIPPLE
AIR & VACUUM
RELEASE VALVE
ASSEMBLY
1" AIR AND VACUUM RELEASE VALVE ASSEMBLY, APCO NO. 143-C, VAL-MATIC NO. 201-C, OR CRISPIN UL10,
OR EQUAL
PIPE 1" GALVANIZED IRON NIPPLE
BEND 1" 90° GALVANIZED IRON BEND
UNION 1" GALVANIZED IRON UNION
PIPE 1" GALVANIZED IRON PIPE, LENGTH TO FIT
SWING JOINT (1) 2"X1" BELL REDUCER
(2) 2" 90° STREET ELLS
PIPE 2" GALVANIZED IRON PIPE, LENGTH TO FIT, FIELD LOCATE
BEND 2" 180° RETURN BEND, OPEN PATTERN
STRAINER 2" BEEHIVE STRAINER
METER BOX AND LID METER BOX, ARMORCAST A6001946PCX18, WITH METER BOX LID, ARMORCAST A6001969RCI-H7, TO READ
"RENTON WATER"
GRAVEL 1 1 4" WASHED GRAVEL
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
12"
MIN
A
B C
D
E
F
G B
G
H
I J K
L M
N
O
P
Q
6" MIN
5" TO 18"
NOTES:
1.AIR AND VACUUM RELEASE VALVE ASSEMBLY MUST BE INSTALLED AT THE HIGHEST POINT IN THE WATER MAIN. IF THE HIGH POINT FALLS
IN A LOCATION WHERE THE ASSEMBLY CANNOT BE INSTALLED, PROVIDE ADDITIONAL DEPTH OF MAIN TO CREATE THE HIGH POINT AT A
LOCATION WHERE THE ASSEMBLY CAN BE INSTALLED.
2.LOCATE METER BOX OUTSIDE OF TRAFFIC AREAS, BEHIND THE CURB.
MAIN
R
MATERIALS
FINISHED GRADE
PUBLIC WORKS
DEPARTMENT
APPROVED:
DATEMartin Pastucha
Public Works Administrator
1" AIR AND VACUUM RELEASE
VALVE ASSEMBLY
STD. PLAN - 340.3
6/28/2023