HomeMy WebLinkAbout360.1NOTES: 1.THE RPBA MUST BE LISTED ON THE LATEST VERSION OF "BACKFLOW ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY THE STATE OF WASHINGTON DEPARTMENT OF HEALTH. 2.THE RPBA MUST BE TESTED BY A WASHINGTON STATE CERTIFIED BACKFLOW ASSEMBLY TESTER UPON INSTALLATION AND ANNUALLY THEREAFTER. ASSEMBLY TO BE MAINTAINED BY PROPERTY OWNER. A COPY OF THE TEST REPORT SHALL BE SENT TO THE CITY OF RENTON WATER UTILITY CROSS CONNECTION CONTROL SPECIALIST, FAX 425-430-7207, EMAIL BACKFLOW@RENTONWA.GOV. 3.RPBA AND ENCLOSURE SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE WATER METER. TO OWNER'S ELECTRICAL PANEL 24" MIN 2" 12" MIN SERVICE FROM METER SERVICE TO BUILDING REDUCED PRESSURE BACKFLOW ASSEMBLY LINE-SIZED WASHINGTON STATE-APPROVED RPBA WITH TWO (2) RESILIENT-SEATED SHUT-OFF VALVES AND FOUR (4) RESILIENT-SEATED TEST COCKS. RPBA SHALL BE INSTALLED CENTERED IN THE HEATED ENCLOSURE WITH MINIMUM 3" CLEARANCE IN ALL DIRECTIONS PIPE AND FITTINGS SIZE AND MATERIALS AS REQUIRED PER UPC REQUIREMENTS ELECTRICAL OUTLET 120-VOLT OUTDOOR ELECTRICAL OUTLET WITH COVER, INSTALL HEAT TAPE FOR FREEZE PROTECTION ELECTRICAL CONDUIT RIGID CONDUIT PER ELECTRICAL PERMIT REQUIREMENTS ENCLOSURE INSULATED ENCLOSURE SIZE TO FIT RPBA, ASSE 1060 CERTIFIED, SAFE-T-COVER OR EQUAL DRAIN ENCLOSURE DRAIN SIZED IN ACCORDANCE WITH AWWA CROSS CONNECTION CONTROL MANUAL STANDARDS: ≤1" RPBA = 3" DRAIN, 1 1 2" & 2" RPBA = 4" DRAIN CONCRETE SLAB CONCRETE SLAB SIZED TO FIT RPBA AND ENCLOSURE PER MANUFACTURER BOLTS 3/8"X4" ANCHOR BOLTS PER MANUFACTURER GRAVEL 1 1 4" WASHED GRAVEL 4" MIN FINISHED GRADE A C B D E F G IPROPERTY LINEA MATERIALS B C D E F G H I 6" MIN H PUBLIC WORKS DEPARTMENT APPROVED: DATEMartin Pastucha Public Works Administrator 3/4" TO 2" RPBA HEATED ENCLOSURE INSTALLATION DOMESTIC AND IRRIGATION SERVICES STD. PLAN - 360.1 6/28/2023