HomeMy WebLinkAbout370.250' MAX NOTES: 1.FIRE SPRINKLER SYSTEM SHALL BE LOCATED ON DEDICATED FIRE SERVICE SEPARATE FROM DOMESTIC SERVICE TO THE BUILDING. 2.PIV MUST BE LOCATED ON THE FIRE SERVICE BETWEEN THE ROW AND THE FDC. 3.FIRE MARSHAL SHALL APPROVE FDC AND/OR PIV LOCATION IF LESS THAN 50' FROM BUILDING. 4.THE DCDA OR RPDA MUST BE TESTED BY A WASHINGTON STATE CERTIFIED BACKFLOW ASSEMBLY TESTER UPON INSTALLATION AND ANNUALLY THEREAFTER. ASSEMBLY TO BE MAINTAINED BY PROPERTY OWNER. A COPY OF THE TEST REPORT SHALL BE SENT TO THE CITY OF RENTON WATER UTILITY CROSS CONNECTION CONTROL SPECIALIST, FAX 425-430-7207, EMAIL BACKFLOW@RENTONWA.GOV. 5.THE FDC AND PIV MAY BE LOCATED WITHIN THE VAULT WITH THE BACKFLOW ASSEMBLY PER STD PLAN 370.3. CONNECTION TO WATER MAIN (1) TEE (FLxFL) (3) GATE VALVES (FLxMJ) WITH CONCRETE BLOCKING APPROVED DCDA OR RPDA PER STD PLAN 350.3 OR 360.4 PIV SEE NOTE 2 FLOOR FLANGE CONCRETE BLOCKING MECHANICAL ROOM ROW PRIVATE PROPERTY FIRE HYDRANT ASSEMBLY W W 50' MAX FDC ASSEMBLY TO BE LOCATED DOWNSTREAM OF BACKFLOW ASSEMBLY 50' MIN SEE NOTE 3 BUILDING PUBLIC WORKS DEPARTMENT APPROVED: DATEMartin Pastucha Public Works Administrator COMMERCIAL FIRE SPRINKLER SYSTEM 3" TO 10" DCDA OR RPDA OUTSIDE INSTALLATION STD. PLAN - 370.2 6/28/2023