HomeMy WebLinkAboutPN_Scope Letter_092017_V1FIRE PROTECTION, INC.
PO BOX 12642
MILL CREEK, WA 98082
(425) 290-9600 OR 1-800-681-1125 FAX (425) 353-4546 September 15, 2017
City of Renton - PLAN REVIEW
RE; FIRE ALARM TENANT IMPROVEMENT
Please find enclosed FIRE ALARM TENANT IMPROVEMENT DESIGN
Fire Protection Inc. will add (1) Remote Power Supply, (1) heat
detector, (5) A/V notification devices and (1) pull-station per
plan for the tenant improvement area per plan (the fire alarm
system existing). The system has been designed per NFPA 72, IBC,
IFC, NEC and your current codes & standards. A full pre-test and
NFPA form shall be conducted and completed prior to calling the
AHJ for acceptance testing.
INSTALLATION COMPANY
Fire Protection, Inc.
1730 Gibson Rd. Everett, WA 98204
WSCL# FIREPI*021ML UL CERT #608242-002
JOB Site;
AHIPOKI BOWL
727 N. 10th Street *Suite G*
Renton, WA 98057
CONTRACTUAL RESPONSIBLE PARTIES
Installation;
Fire Protection, Inc.
AMBIENT TEMPERATURES
No area with alarm service equipment shall
fall below 40 degrees, common areas shall
be at 68 degrees per builder
RECEIVED
09/25/2017 striplett
BUILDING DIVISION
F17004475
AMBIENT NOISE RANGE
Tenant Improvement area is serviced by the Existing Fire
Alarm Control and notification system will be as listed for
per UBC listings, per builder.
SEQUENCE OF OPERATIONS
All Alarm and Trouble conditions shall enunciate at FACP as well
as remote notify listed Central Station. Zones of alarm shall
cause for all notification circuits to activate, send alarm zone
to CS and re-dispatch to Fire Service. Trouble and supervisory
signals shall transmit to CS, (no notification circuits shall
activate.) Opens on any zones shall cause for a trouble signal.
Should you have any further questions, please feel free to contact
me directly.
David Mow
VP of Operations/Designer
*NICET-3 #120904*
*CITY OF REDMOND DESIGNER OF RECORD #16-B-141*