HomeMy WebLinkAboutWTR2702953.115c
CS
N
C\1
►i
i
I
8
J
m
s
w
¢
5
J
E
0
co
0
A B I C D I E F
UNION
FOR LINES LARGER THAN
4" USE 1 " NI PT WELDOL�_T
FACTORY FILLED CAPILLARY TUBE
W/SS JACKET (NOTE 1) OR
NIPPLE TO INSTRUMENT.
DIAPHRAGM SEAL (NOTE 1)
1 BALL VALVE (NOTES 2, 4)
1 " NPT CLOSE NIPPLE 1 4
CINii innrn `) VALVE
ANIFOLD
SURFACE
MOUNT GAGE OR
INSTRUMENT
(NOTES 2, 3 L
(NOTE
2)
v vu vv
2—VALVE MANIFOLD
NOTE
3
(BLOCK &
BLEED)
NOTE 4 1 /2" LINE
CLASS VALVE
0
(SECTION
15050)
NOTE 1
NOTES:
1. KEEP CAPILLARY TUBES AS SHORT AS POSSIBLE. CLOSE
COUPLE
NOTES:
INSTRUMENT OR GAGE TO DIAPHRAGM SEAL WHERE
SHOWN ON DRAWING.
1.
A ROOT VALVE IS REQUIRED IF THE 2—VALVE MANIFOLD
IS NOT CLOSE
2. USE 1/2" NIPPLE AND VALVE FOR CONNECTION TO
SYSTEM
-COUPLED TO THE LINE.
PIPING 4 INCHES AND LESS. USE 1" ELSEWHERE.
2.
SNUBBER IS REQUIRED FOR VIBRATION SERVICE.
3. USE A LINE —SIZE TEE FOR 2" AND SMALLER.
3.
USE STAINLESSSTEEL TUBING & FITTINGS IN CORROSIVE AREA.
4. TYPICAL PRESSURE TAP
4.
FOR LOCATION OF TAP SEE DETAIL 1.
DIAPHRAGM
SEAL
PROTECTOR
DETAIL
TYPICAL
PRESSURE
INSTRUMENT
r2_"�
LIQUID
STEAM, VAPOR OR SLURRY
AIR OR GAS
cn
w
PREFERRED
o
0 oCA
PREFERRED
ALTERNATE
PREFERRED
ALTERNATE
LTERNATE
ALTERNATE
LIQUID OR SLURRY
STEAM, VAPOR, AIR OR GAS
cn
PREFERRED
J
ALTERNATE
ALTERNATE
Q
PREFERRED
ALTERNATE
ALL FLUIDS
NOTE: PREFERRED
THIS ORIENTATION FOR TEMPERATURE ALTERNATE
w
INSTRUMENTS WILL NOT APPLY IF THE ALTERNATE
°-
PIPE DIAMETER IS SMALL AND REQUIRES
Lij
A TEE OR ELBOW TO BE USED.
CONNECTIONS IN HORIZONTAL MAIN LINE
ORIENTATION OF INSTRUMENT
CAPPED INDICATING TYPE
WALL TRANSMITTER
2,, GRS PIPE
0 3—VALVE MANIFOLD
I -
�c� cV 6"
o PRESSURE LINE PORT
HIGH AND LOW
0 O
CC 0
1/47EEL
O 0
0 1 /4" GALVANIZED STEEL
0 0
MOUNTING PLAT MOUNTING BRACKET
LEVELING GROUT AS REQUIRED STAINLESS STEEL U-BOLT
FLOOR STAND WALL MOUNT
NOTES: 2" GRS PIPE
1 HOT DIP GALVANIZE AFTER FABRICATION.
2. TYP. MOUNTING PLATE: 6" x 6" x 3/16" WITH FOUR 5/8" HOLES.
3. PROVIDE FOUR 2" x 9/16" CAPSULE ANCHOR BOLTS.
INSTRUMENT MOUNTING 4 TRANSMITTER MOUNTING 5
I
SCALE: NONE 117
SCALE: NONE 117
117 SCALE: NONE
SCALE: NONE 117
SCALE: NONE 117
3/4" LIQUID TIGHT CONDUIT
TRANSMITTER
NEMA 4X ENCLOSURE
3" FF WELD NECK FLANAlELEVEL SWITCHES
STAINLESS STEEL
3/4" CONDUIT —
/
CONDUIT ANCHOR BOLT
DRILL 1" DIA. VENTS
TO PLC (TYP 2)
ON 1 FT CENTERS�z
S CABLE
TYPE X2 PIPE PENETRAT
LMFR
MATING 4" FF
STAINLESS STEEL
SEE M30
FLANGE (TYP)
4 FLAT FACED
ANGLE BRACKET -
a <-�
(NOTE 1)
NOZZLE (PART OF
Ll
3" SCH. 80
TANK) (NOTE 3)
STAINLESS STEEL ROD
PVC PIPE. CONC. DECK
N 3/4" NIPPLE (NOTE 3)
4" DIA 316 SS, SCH _40 PIPE DISPLACER FLOAT (TYP.)
CLOSED o 3/4" COUPLING (NOTE 3)
-
° N
RETAINER. SHIM PVC PIPE PVC COUPLING
TO CENTER WELL IN (AS REQ'D)
TANK
o
RETAINER
TEFLON FLOAT a �
2 SHIM - --- 2_ 1 "W x 41 SLOTS
SONIC PROBE
17 a
1-3
NOTE 2
NOTES
12" Ox 1 /4" THICK 316 SS
1. PROVIDE W/ INSTRUMENT.
a
PLATE W/ TWO 3/8"0 ° �►
2. LOCATE PER PROBE MFR'S INSTRUCTIONS TO PREVENT INTERFERENCE.
a °
EXPANSION ANCHORS <
3. USE CPVC SCH. 80 NIPPLES, COUPLING AND FLANGE IN CORROSIVE ATMOSPHERE.
NOTE:
4. LEVEL SENSOR (LSH) IS SIMILAR. POSITION SENSOR AS REQUIRED BY ENGINEER.
PROVIDE SIMILAR STILLING WELL FOR LEVEL TRANSDUCERS IN BELOW GRADE BASINS.
ULTRASONIC PROBE & SENSOR INSTALLATION
SUMP LEVEL FLOAT LEVEL SENSOR
STILLING WELL WITH LEVEL SWITCH
6
7
8
SCALE: NONE ! 17
SCALE: NONE 117
SCALE: NONE 117
N
cr
N
01
4
0
F.—
a
w
J
Q1...
3
En
3
3
O
U
a)
Y
(1)
C�
O
w
Un
3
0
0
O
O
rri
v7
0
N 1
/
CD
L.�
Y — RECORD DRAWING 12/05
w
Z NO. REVISION BY DATE APPR
J
10
a
7
0
W
4
3
W=2953124 2
RECORD DRAWING
These Record Drawings have been prepared based on information provided
by the contractor and others. Kennedy/Jenks Consultants has not verified the
accuracy or completeness of information provided to them and does not
warrant the accuracy or completeness of these Record Drawings. Users of
these _Record Drawings assume all risk of loss resulting from their use.
SURVEYED: SCALE: NONE
CITY OF RENTON DATE: 1
DESIGNED: MDL VERTICAL: NAVD 1988 � ECONOMIC AND ENGINEERING — Planning/Building/Public Works Dept. DEC 2005
DRAWN: LMM ONE INCH HORIZONTAL: NAD 1983/1991 Kennedy/Jenks PROJECT No.
CHECKED: MDL Consultants SERVICES, INC. MAPLEWOOD 3-01-358
AT FULL SCALE 10900 NE 4th STREET, SUITE 1110 REVISION No.
APPROVED: WATER TREATMENT AND GOLF COURSE IMPROVEMENTS -
32001 32nd Avenue South, Suite 100 BELLEVUE, WASHINGTON _ 98005
IF .NOT ONE INCH DATUM Federal Way, ,Washington 98001 sHT No.
SCALE ACCORDINGLY PORTLAND, OR / BELLEVUE, WA / KENNEWICK, WA / DLYMPIA, WA
INSTRUMENTATION DETAILS DWG No.
i17R
° E F G " ' J K L M A3 N WI-12.9 5 31A Al
0
L�
W-
J
VI
W