HomeMy WebLinkAboutWTR2703123.4o °' WATER UTILITY NOTES & SPECIFICATIONS �- 00 o 001. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS I'- ado ;m 3 w� OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST J w a EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION. 2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE DEPARTMENT OF PUBLIC WORKS AT 235-2631. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE DEPARTMENT OF PUBLIC WORKS 73 HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY. J 3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID Z Q DAMAGE OR DISTURBANCE. FOR UTILITY LOCATE CALL 48-HOURS LOCATORS, p W 1-800-424-5555. 4. ALL WATER MAIN PIPE TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AWWA - C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. PIPE JOINTS TO BE 0 PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND W Z FITTINGS SHALL BE POLYETHYLENE WRAPPED PER ANSI/AWWA C105/A21.5-93 STANDARDS. 00 5. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED o g z I-- ONON PLANS, AND IN ACCORDANCE WITH ANSI/AWWA Cl 1 O/A21,10-87. CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/A21.4-90. IF FITTINGS ARE 3 INCHES TO 12 WINCHES ry Z INCHES IN DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL BE IN ACCORDANCE N Z WITH EITHER ANSI/AWWA C110/A21.10-87 OR ANSI/AWWA C153/A21.53-94. 3 INCH TO O 12 INCH DIAMETER FITTINGS WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED JOINTS SHALL I`_ Lij BE IN ACCORDANCE WITH ANSI/AWWA C 1 10/A21.10.87 OR A COMBINATION OF ANSI/AWWA W Q C110/A21.10.87 AND ANSI/AWWA C153/A21.53-94 SUCH THAT THE PORTION OF THE FITTING WITH A MECHANICAL JOINT(S), MAY BE IN ACCORDANCE WITH ANSI/AWWA C153/A21.53-94 AND THAT PORTION OF THE FITTING WITH FLANGED JOINTS) SHALL BE IN ACCORDANCE WITH ANSI/AWWA C 1 10/A21.10-87. ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION 53.53 OF ANSI/AWWA C 153/A21.53-94 OR WITH SECTION 10-4.3 OF ANSI/AWWA C110/A21.10-87 SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO the owner. 6. GATE VALVES SHALL BE IRON BODY, BRONZED -MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O-RING STUFFING BOX (AWWA C500) OR OF RESILIENT SEATED TYPE (AWWA C509). VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO A2380, OR M & H. Q) ALL VALVES 12" IN DIAMETER AND LARGER, SHALL BE INSTALLED IN A VAULT. SEE WATER a N STANDARD DETAIL FOR 12" GATE VALVE ASSEMBLY VAULT AND 1" BYPASS INSTALLATION. 7. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE) CONFORMING TO AWWA C-502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCHES, TWO 2-1/2 INCH HOSE NOZZLES WITH NATIONAL STANDARD THREADS 7-1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLES WITH THE NEW SEATTLE PATTERN 6 THREADS PER INCH, 60 DEGREES V. THREADS, OUTSIDE DIAMETER OF MALE TREAD 4.875 AND ROOT DIAMETER 4.6263. HYDRANTS SHALL HAVE A 1-1/4" PENTAGON OPERATING NUT OPENED BY TURNING J COUNTER CLOCKWISE (LEFT). THE TWO 2-1/2" HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS c' SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS UNDER TEST PRESSURES. THE 4" PUMPER NOZZLE SHALL BE FITTED WITH A STORTZ ADAPTER, 4" SEATTLE THREAD X 5" STORTZ. STORTZ ADAPTER SHALL BE FORGED AND/OR EXTRUDED 6061-T6 ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND 2 SET SCREWS 180 DEGREES APART. STORTZ FACE TO BE METAL, NO GASKET TO WEATHER. STORTZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET, AND SHALL BE ATTACHED TO HYDRANT ADAPTER WITH �^ 1 /8" COATED STAINLESS STEEL AIRCRAFT CABLE. Q_ a zz E< Q FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, �a o LATEST REVISIONS. 8. ALL WATER MAIN 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATER MAIN 12 INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATER MAINS ARE TO BE LOWERED TO CLEAR. 9. ALL WATER MAINS SIX (6) INCHES IN DIAMETER AND LARGER SHALL BE CLEANED WITH PIPE 3 p CLEANING "PIGS" PRIOR TO DISINFECTION. THE "POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA _ Z Z o - O V SWAB -AS OR APPROVED EQUAL, 2 LB/CU FT. DENSITY FOAM WITH 90A DUROMETER URETHANE cn Q RUBBER COATING ON THE REAR OF "PIG" ONLY. "PIGS" SHALL BE CYLINDER SHAPED WITH N BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING OPERATION. A) ALL WATER MAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS & SPECIFICATIONS 7-11.3(11). THE LOSS IN PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST } Z Z a Y PERIOD. 3 o O B) ALL WATER MAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM (MINIMUM CONCENTRATION) CHLORINE/WATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL Of NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE METERED/INJECTED IN 0- ACCORDANCE WITH SECTION 7-1 1 .3(12)E OR 7-1 1.3(12)F OF THE STANDARD SPECIFICATIONS i Q REFERENCED IN 1 ABOVE. o w 10. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM N Q OF 3 (THREE) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING. PRIOR TO SCHEDULING THE M PRECON A PERMIT INFORMATION SHEET MUST BE SUPPLIED TO THE UTILITY ENGINEER'S OFFICE. x TWENTY-FOUR HOUR NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. m 11. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. 12. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON. 13. ALL CONNECTION TO EXISTING MAINS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE DEPARTMENT OF PUBLIC WORKS. ALL NECESSARY EXCAVATION AND MATERIALS TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS. 14. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE CONTRACTOR AS WELL AS THE ENGINEERS o SHALL KEEP AS -BUILT DRAWINGS. U' 15. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND w PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN. 16. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO OR EQUAL APPROVED IN WRITING BY THE DEPARTMENT OF PUBLIC WORKS. 17. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT, „ SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT TO A MINIMUM 9 J DEPTH OF TWO INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT. i 18. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL a EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO CITY OF RENTON POLICY, WITHIN TEN DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH. di 19. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE w o SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 UNDER IMPROVED AREAS. ALL z CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE. RENTON PLACE DIVISION III THE NORTHWEST QUARTER OF SECTION 18, T23N, RSE, W.M. CITY OF RENTON, KING COUNTY, WASHINGTON 12"x 22" CONCRETE METER BOX WITH 3/16" STEEL DIAMOND PLATE COVER EQUAL TO FOG TITE METER SEAL CO. B-10 METER BOX. 6" MIN FINISH GRADE 9" MAX NEW DUCTILE IRON L- LOOP DOWN TO CENTERLINE WATERMAIN OF WATER MAIN TO PROVIDE SLACK IN COPPER SERVICE LINE TO METER. CORPORATION STOP. FORD TAPERED THREAD (CC). PACK JOINT (3/4" F1000) (1 " F1000) EXISTING CAST IRON OR DUCTILE IRON WATERMAIN 1 /2' R SERVICE FROM ISTING STEEL ASBESTOS CEMENT OR PVC WATER MAINS INSTALL DOUBLE STRAP SERVICE CLAMP EQUAL TO MUELLER CO. NOTE: I I W IN UNIMPROVED RIGHT OF WAY W, z INSTALL METER BOX AT Z PROPERTY LINE. G_ a o• o a SIDEWALK a ,I TOUCHREAD WATER METER TO 12" MIN BE SUPPLIED BY THE CITY 36" MIN COVER TYPE "K" SOFT COPPER TUBING FORD COPPERSETTER VH 72-15W-44-33G (FOR 5/8" x 3/4" METER) VH 72-15W-44-44G (FOR 1" METER) BOTH INLET AND OUTLET WITH PACK JOINT WITH GRIPPER. PADLOCK WINGS ON KEY VALVE SINGLE CHECK VALVE ON OUTLET. ALL PACK -JOINT FITTINGS SHALL BE WITH GRIPPER. IF SERVICE LINE TO HOUSE IS TO BE INSTALLED IN THE FUTURE INSTALL FORD C14-33 OR 44 FIDT x COMPRESSION COUPLING A -A THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM UNDERNEATH RIBS UNLESS THE RIB SPACING ALLOWS THE NUT TO TIGHTEN AGAINST THE OPEN SIDE OF MORE THAN 1 RIB. 6/27/02 ADD HOLE ON METER LID FOR TOUCHREAD 10/15/96 Edited text. 3/4" WATER SERVICE EXISTING 8" D.I. WATERLINE 8"x8" TAPPING TEE (MJxFL)/W CONC. BLOCK 8" TAPPING GATE VALVE (FLxMJ) TEMP. 8" PLUG (MJ) WITH 2" TAP & 2" BLOW -OFF ASSEMBLY CONC, BLOCKING TESTING DETAIL /1 M INSERT CLEANING 8" "POLY -PIG" IN VERTICAL CROSS 8'A" VERTICAL CROSS (MJxFL) 1-8" BLIND FLANGE ON TOP W/2" TAP & 2" PLUG 1-8" BLIND FLANGE ON BOTTOM 1-8" PLUG (MJ) W/2" TAP & 2" BLOW -OFF TEMP. BLOCK NEW 8" D.I. WATERLINE DRILL 1-3/4" DIA HOLE 3/4" OR 1" GALVANIZED PLUG FOR TOUCHREAD DEVICE 2-1/2" MIN. FROM NEAREST AND FRONT EDGE OF PIT LID } 3/4" & 1" WATER SERVICE TYPICAL RIB y ADOPTED CITY OF RENTON STANDARD PLANS F N LST DATE: 6/02 LC AG DCV AG BY APPR DWG. NAME: BR41-TR SP PAGE: B106 NOTE: ALL WATER SERVICES SHALL BE 3/4" AND CONFORM TO THIS DETAIL EXCEPT THAT METER AND METER BOX SHALL BE LOCATED BEHIND SIDEWALK AS SHOWN ON PLAN. FINAL CONNECTION DETAIL EXISTING 8" D.I. WATERLINE AFTER ALL TESTING, CLEANING AND DISINFECTION, REMOVE TEMP. BLOCK & BLOW -OFF & CONNECT WITH 8" SLEEVE (MJ) & 8" D.I. SPOOLS. FINAL CONNECTION BY CITY FORCES NEW 8" D.I. WATERLINE NOTES: 1. TAPPING TEES SHALL BE MADE OF DUCTILE IRON OR EPDXY -COATED STEEL. 2. NO SIZE ON SIZE TAPS ON CAST-IRON WATER LINES. 3. NO WET TAP ON ASBESTOS CEMENT LINE OR STEEL LINE. 4. WET TAP SHALL BE DONE ONLY BY CITY APPROVED CONTRACTORS. 5. CONTRACTOR SHALL POTHOLE AND VERIFY THE HORIZONTAL AND VERTICAL ALIGNMENT OF EXISTING LINE OR STUB AND SHALL START LAYING THE NEW LINE AT THE SAME HORIZONTAL AND VERTICAL ALIGNMENT OF THE EXISTING STUB. CITY FORCES WILL PERFORM THE FINAL CONNECTION FROM THE WATER LINE TO THE TAPPING VALVE WITH DI SLEEVE AND DI SPOOL. WET TAP CONNECTION TO EXISTING 8" D.I. WATERLINE. RECOMMENDED FOR APPROVAL BY BY p BY e CALL 48 HOURS 1 AS -BUILT BEFORE YOU DIG 1-800-424-5555 NO. FIRE SPRINKLER NOTE WHERE THE UNDERGROUND WATER SUPPLY TEES OFF TO SERVE ONLY A FIRE SPRINKLER SYSTEM, A SEPARATE DETAILED PLAN MUST BE SUBMITTED AND APPROVED BY THE FIRE MARSHAL PRIOR TO INSTALLATION. FIRE PROTECTION NOTES THE FIRE PROTECTION SYSTEM INCLUDING MATERIALS, SIZING, G, AND CONFIGURATION IS SUBJECT TO A CONTRACTOR PROVIDED DESIGN BY A FIRE PROTECTION ENGINEER, AND AS SUCH, THE FINAL DESIGN OF THE FIRE PROTECTION SYSTEM, INCLUDING HYDRANT LOCATIONS, MAY DEVIATE FROM THE SYSTEM SHOWN. THE FINAL DESIGN SHALL BE SUBMITTED TO AND APPROVED BY THE FIRE MARSHALL. CONTRACTOR'S BID SHALL REFLECT THE CONDITIONS OF THE FIRE PROTECTION ENGINEER'S DESIGN. CONTRACTOR SHALL COMPLY WITH ALL NATIONAL FIRE PROTECTION ASSOCIATION REQUIREMENTS AS SET FORTH BY "NFPA 13", ITS AMENDMENTS, AND LOCAL REQUIREMENTS, INCLUDING BUT NOT LIMITED TO ACQUISITION OF ALL PERMITS. ?30$ RECORD NOTE THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION SUBMITTED, IN PART, BY OTHERS. WHILE THIS INFORMATION IS BELIEVED TO BE RELIABLE, AHBL IS NOT RESPONSIBLE FOR ITS ACCURACY, OR ERROR OR OMISSIONS WHICH MAY HAVE BEEN INCORPORATED INTO THIS DOCUMENT AS A RESULT. THOSE RELYING ON THIS RECORD DOCUMENT ARE ADVISED TO OBTAIN INDEPENDENT VERIFICATION OF ITS ACCURACY BEFORE APPLYING IT FOR ANY PURPOSE. CHECKED FOR COMPLIANCE TO CITY STANDARDS DATE DATE DATE MW 1 3/12/04 REVISION BY I APPR. I DATE 29010 �EGISTLfR�p' �sSIONALG`ti EXPIRES Q / 6 / 0.5 REUSE OF DOCUMENTS THIS DOCUMENT HAS BEEN SIGNED ELECTRONICALLY N ACCORDANCE MITH WAC 196-23-070 AND CHAPTER 19.34 ROW. UNAUTHORIZED ALTERATION OF ANY OF THE INFORMATION ON THIS DOCUMENT MALL INVALIDATE THE DOCUMENT, NY CERTIFICATION AND SIGNATURE. THE IDEAS AND DESIGNS INCORPORATED HER", AS AN INSTRUMENT OF PROFESSIONAL SERVICE, 15 THE PROPERTY OF AHBL AND IS NOT TO BE USED, IN %HOLE OR IN PART, FOR ANY OTHER PROJECT VATHOIT THE %BITTEN AUTHORIZATION OF A EIL 0 ri c cd L_ O � � L) °0 Z-1-! - q z C: )N) N =mac £pW� �� 0 Q�Z0 QZ 0 U00 0z a�- gQ �C�C)�� -j 0 S2 c C< @ L. 0 0 0 CO -� U T' > 3 QC Qi 0_� 0cd0 aii00 mmcr- 5::2 lq0_0m Z O Q uj U 2; O 0 iu J J W O Cn > 0 Q Cn W f- 0 z Ir w Q Q W � Q � Z O z W V) 14 WUU) ora Z I.- Of - ' 3 Z =0 J U W �Q>o �Ld� WQC) WUZ ZoQ o �0Zi ZQ W J CITY OF RENTON DEPARTMENT OF PUBLIC WORKS r 1 L�J WATER NOTES & DETAILS 18 0 DESIGNED: DATE: 3 f 12/04 DRAWN: CHECKED: SCALE: AS SHOWN I APPROVED: DIRECTOR OF PUBLIC VOWS m O FILE NAME: ;???_ FIELD 800K:- PAGE:- W SHEET: 18 OF: 19 SCANNED OCT 0 8 �aa4