HomeMy WebLinkAboutWTR2703185.1STTLWAUSG 17
GENERAL NOTES
1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
CONTRACTOR - SPECIFIED CONTRACTOR PER SCOPE OF WORK
SUBCONTRACTOR - GENERAL CONTRACTOR (CONSTRUCTION)
OWNER - AT&T WIRELESS SERVICES.
2. ALL SITE WORK SHALL BE COMPLETED AS INDICATED ON THE DRAWINGS AND PROJECT
SPECIFICATIONS.
3. DRAWINGS PROVIDED HERE ARE NOT TO BE SCALED AND ARE INTENDED TO SHOW OUTLINE ONLY.
4. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE
CODES, REGULATIONS, AND ORDINANCES. SUBCONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES
AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS, AND LAWFUL ORDERS OF ANY
PUBLIC AUTHORITY REGARDING THE PERFORMANCE OF THE WORK.
5. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY
SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS.
6. UNLESS NOTED OTHERWISE. THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT.
APPURTENANCES. AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE
DRAWINGS.
7. THE SUBCONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
B. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE
SUBCONTRACTOR SHALL PROPOSE AN ALTERNATIVE INSTALLATION SPACE FOR APPROVAL BY THE
CONTRACTOR.
9. THE SUBCONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS,
LANDSCAPING AND STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT SUBCONTRACTOR'S
EXPENSE TO THE SATISFACTION OF OWNER.
10. THE SUBCONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF
CONSTRUCTION_
11. ALL. EXISTING ACTIVE SEWER. WATER, GAS, ELECTRIC, AND OTHER UTILITIES WHERE ENCOUNTERED
IN THE WORK, SHALL BE PROTECTED AT ALL TIMES, AND WHERE REQUIRED FOR THE PROPER
EXECUTION OF THE WORK, SHALL BE RELOCATED AS DIRECTED BY ENGINEERS. EXTREME
CAUTION SHOULD BE USED BY THE SUBCONTRACTOR WHEN EXCAVATING OR DRILLING PIERS AROUND
OR NEAR UTILITIES. SUBCONTRACTOR SHALL PROVIDE SAFELY TRAINING FOR THE WORKING CREW.
THIS WILL INCLUDE BUT NOT BE LIMITED TO A) FALL PROTECTION B) CONFINED SPACE C)
ELECTRICAL SAFETY D) TRENCHING do EXCAVATION.
12. ALL FASTING INACTIVE SEWER, WATER. GAS, ELECTRIC AND OTHER UTILITIES, WHICH INTERFERE WITH
THE EXECUTION OF THE WORK, SHALL BE REMOVED AND/OR CAPPED. PLUGGED OR OTHERWISE
DISCONTINUED AT POINTS WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK. AS
DIRECTED BY THE RESPONSIBLE ENGINEER, AND SUBJECT TO THE APPROVAL OF THE OWNER AND/OR
LOCAL UTILITIES.
13. THE AREAS OF THE OWNER'S PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER,
EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT
EROSION,
14. SUBCONTRACTOR SHALL MINIMIZE DISTURBANCE TO EXISTING SITE DURING CONSTRUCTION. EROSION
CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION. SHALL BE IN CONFORMANCE WITH THE
LOCAL GUIDELINES FOR EROSION AND SEDIMENT CONTROL
15. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUND. FROZEN MATERIALS.
SNOW OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
16. THE SUB GRADE SHALL. BE COMPACTED AND BROUGHT TO A SMOOTH UNIFORM GRADE PRIOR TO
FINISHED SURFACE APPLICATION.
17. THE SITE SHALL BE GRADED TO CAUSE SURFACE WATER TO FLOW AWAY FROM THE BTS EQUIPMENT
AND TOWER AREAS.
18. IF NECESSARY. RUBBISH, STUMPS. DEBRIS. STICKS. STONES AND OTHER REFUSE SHALL. BE
REMOVED FROM THE SITE AND DISPOSED OF LEGALLY.
19. THE SUBCONTRACTOR SHALL PROVIDE SITE SIGNAGE IN ACCORDANCE WITH THE TECHNICAL
SPECIFICATION FOR SITE SIGNAGE.
20. SUBCONTRACTOR SHALL. LEAVE PREMISES IN CLEAN CONDITION,
DETAIL_ 300
BECHTEL TELECOMMUNICATIONS
12131 113TH AVENUE NE
iv KIRKLAND. WASHINGTON 98034
wpP - 2 7 - A/SS
2ooy v� ( rct �Z ecd rA �r�w;
PROJECT INFORMATION
SCOPE OF WORK: UNMANNED TELECOMMUNICATIONS FACILITY MODIFICATIONS
SITE ADDRESS:
12603 82ND AVE SOUTH A -
RENTON. WA 98055 • -
LATITUDE
47. 29' 24" 9rmZj }A*01(irts
LONGITUDE:
JURISDICTION:
-122' 13' 49-
KING COUNTY GL�YtYS �i>1
CURRENT USE:
PROPOSED USE:
TELECOMMUNICATIONS FACILITY
TELECOMMUNICATIONS FACILITY
Jf/
/'
i
AT&T
UMTS
SEATTLE MARKET
AT&T WIRELESS
SITE NUMBER: STTLWASG17
SITE NAME: RENTON HILLS
I DRAWING INDEX I REVI APPLICABLE BUILDING CODES AND STANDARDS
STTLWASGI7-T01
TITLE SHEET - NORTEL UMTS IBTS
0
STTLWASGI7-AO1
POWER, GROUNDING & TELCO PLAN UMTS 18TS (INDOOR)
0
STTLWASGI7-AO2
CONSTRUCTION DETAILS UMTS iBTS (INDOOR)
0
STTLWAS13I7-A03
ANTENNA CONFIGURATION
0
STTLWASGI7-A04
RF NOTES & BILL OF MATERIALS
0
STTLWASGI7-AO5
ANTENNA ELEVATION
0
STTLWASGI7-E01
+24VDC POWER INDOOR SINGLE LINE DIAGRAM
0
STTLWASGI7-EO2
ELECTRICAL DETAILS
0
VICINITY MAP
DIRECTIONS: TAKE THE INTERSTATE 405 SOU."d TOWARDS RENTON TO EXIT #4. SUNSET BLVD. NORTH.
CONTINUE SOUTH ON SUNSET TO BRONSON NA.`:' NORTH. CONTINUE SOUTH ON BRONSON TO
SOUTH 2NO ST. CONTINUING WEST ON S.2ND ST. TURN RIGHT ONTO RAINIER AVE. SOUTH AND LEFT
ONTO RENTON AVE. SOUTH. TAKE RENTON TO 128TH ST AND TURN RIGHT ONTO 128TH BACK TO
82ND AVE. SO. TURN LEFT ONTO 82ND TO WATER TOWER SITE.
PROJECT ( cLj
SITE * S. 126TH PL RENTON
MUNICIPAL
N AIRPORT
S. 128TH ST.
S. 132ND ST. AIRPORT WAY S.
RENTON AVE. S-
S, 2ND ST.
SITE NAME: RENTON HILLS AT&T
SITE #: STTLWAS0I7 JA
12603 82ND AVE. SOUTH RENTON, WA 98055 a
AT&T WIRELESS SERVICES, INC.
As sraMne
5 3
SUBCONTRACTOR'S WORK SHALL COMPLY WITH ALL APPLICABLE NATIONAL STATE, AND LOCAL
CODES AS ADOPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ) FOR THE LOCATION.
THE EDITION OF THE AHJ ADOPTED CODES AND STANDARDS IN EFFECT ON THE DATE OF
CONTRACT AWARD SHALL GOVERN THE DESIGN.
BUILDING CODE: [INTERNATIONAL BUILDING CODE (IBC), 2000]
ELECTRICAL CODE. [NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 70 - 1999, NATIONAL
ELECTRICAL CODE. AS ADOPTED BY AW]
b
LIGHTNING PROTECTION CODE: (NFPA 780 - 1995, LIGHTNING PROTECTION CODE)
w
SUBCONTRACTOR'S WORK SHALL COMPLY WITH THE LATEST EDITION OF THE FOLLOWING
0
AMERICAN CONCRETE INSTITUTE (ACI) 318. BUILDING CODE REQUIREMENTS FOR STRUCTURAL
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC). MANUAL OF STEEL CONSTRUCTION, ASD.
0
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA) 222-F. STRUCTURAL STANDARD FOR
STRUCTURAL ANTENNA TOWER AND ANTENNA SUPPORTING STRUCTURES
INSTITUTE FOR ELECTRICAL. AND ELECTRONICS ENGINEERS (IEEE) 81, GUIDE FOR MEASURING FAI
RESISTIVITY, GROUND IMPEDANCE, AND EARTH SURFACE POTENTIALS OF A GROUND SYSTEM
IEEE 1100 (1999) RECOMMENDED PRACTICE FOR POWERING AND GROUNDING OF ELECTRONIC
IEEE C62.41, RECOMMENDED PRACTICES ON SURGE VOLTAGES IN LOW VOLTAGE AC POWER
CIRCUITS (FOR LOCATION CATEGORY "C3" AND "HIGH SYSTEM EXPOSURE)
TIA 607 COMMERCIAL BUILDING GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS
TELCORDIA GR-63 NETWORK EQUIPMENT -BUILDING SYSTEM (NEBS): PHYSICAL PROTECTION
TELCORDIA GR-347 CENTRAL OFFICE POWER WIRING
TELCORDIA GR-1275 GENERAL INSTALLATION REQUIREMENTS
TELCORDIA CR-1503 COAXIAL CABLE CONNECTIONS
FOR ANY CONFLICTS BETWEEN SECTIONS OF LISTED CODES AND STANDARDS REGARDING MATERIAL,
METHODS OF CONSTRUCTION, OR OTHER REQUIREMENTS. THE MOST RESTRICTIVE REQUIREMENT
SHALL GOVERN. WHERE THERE IS CONFLICT BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL. GOVERN.
DETAIL 303
AT&T WIRELESS
TITLE SHEET
NORTEL UMTS 187S
SITE DRAWING
RVASlas I BY Icw doe MAW
or sow4m 9Y: 7DDt Dave BY. IYFd 24897-512-H
2
GAWM WAIM R[v
STTLWASGI7-TOf 0
22 x 34 T S9
A '