Roth Hill, LLC Tel 425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
NUMBER
FROM
TO
SIZE
POWER
CONTROL
SIGNAL
COMMENTS
POWER
P-PSE
UTILITY VAULT
UTILITY TRANSFORMER
CONDUIT AND MV CONDUCTORS BY UTILITY (PSE)
P-SL
UTILITY TRANSFORMER
CT ENCLOSURE
4"
4 #600 KCMIL, #3G
COORDINATE WITH UTILITY
P-CT
CT ENCLOSURE
UTILITY METER BASE
COORDINATE WITH UTILITY
P-SE
CT ENCLOSURE
MOTOR CONTROL CENTER
4"
4 #600 KCMIL, #3G
COORDINATE WITH UTILITY
P-ATSA
MOTOR CONTROL CENTER
STANDBY GENERATOR
3"
4 #350 KCMIL, #3G
P-PGEN
MOTOR CONTROL CENTER
PORTABLE GENERATOR PLUG
3"
4 #350 KCMIL, #3G
MOTOR CONTROL
P-P210
MOTOR CONTROL CENTER
POWER JUNCTION BOX
2"
3 #1, #6G
2#14
P-P220
MOTOR CONTROL CENTER
POWER JUNCTION BOX
2"
3 #1, #6G
2#14
HVAC
P-EH1
LIGHTING PANEL L1
EH-1 ELECTRIC HEATER
3/4"
2 #12, #12G
P-EF1
LIGHTING PANEL L1
EF-1 EXHAUST FAN
3/4"
2 #12, #12G
P-CD
LIGHTING PANEL L1
CD-1 CONTROL DAMPER
3/4"
2 #12, #12G
INSTRUMENTATION
P-MCP
LIGHTING PANEL L1
MAIN CONTROL PANEL
3/4"
2 #12, #12G
C-CONTROL
MAIN CONTROL PANEL
FLOATS JUNCTION BOX
1"
20#14
1#18 TSP
LEVEL SWITCHES, LIT, INTRUSION SWITCHES
C-GEN
MAIN CONTROL PANEL
GENERATOR CONTROL PANEL
3/4"
10 #14
C-MCC
MAIN CONTROL PANEL
MOTOR CONTROL CENTER
2"
50#14
C-ATSGEN
MOTOR CONTROL CENTER
GENERATOR CONTROL PANEL
3/4"
6 #14
S-FIT
MAIN CONTROL PANEL
FLOW TRANSMITTER
3/4"
1#18 TSP
P-FIT
MAIN CONTROL PANEL
FLOW TRANSMITTER
3/4"
2 #12, #12G
S-FE
FLOW TRANSMITTER
FLOW METER IN VALVE VAULT
3/4"
VENDOR SENSOR CABLES
P-VAULTS
LIGHTING PANEL L1
VAULT LIGHTING AND SUMP PUMP
1"
4 #12, 2#12G
VIA SWITCHES ON EQUIPMENT STAND
C-VAULT1
FLOATS JUNCTION BOX
VALVE VAULT
1"
8 #14
LIMIT SWITCHES, INTRUSION SWITCHES AND FAS
C-VAULT2
FLOATS JUNCTION BOX
WET WELL INTRUSION SWITCHES
3/4"
2#14
C-VAULT3
FLOATS JUNCTION BOX
OVERFLOW VAULT INTRUSION SWITCHES
3/4"
2#14
C-SD
MAIN CONTROL PANEL
SMOKE DETECTOR
3/4"
2#14
C-DOOR
MAIN CONTROL PANEL
DOOR INTRUSION SWITCH
3/4"
2#14
MISCELLANEOUS
MAIN CONTROL PANEL
OUTSIDE ANTENNA
3/4"
COAXIAL
P-GENACC
LIGHTING PANEL L1
STANDBY GENERATOR
3/4"
4 #12, 2#12G
BLOCK HEATER AND CHARGER
NOTE: WHERE ALLOWED AND WHERE CONTRACTOR CHOOSES TO GROUP CONDUCTORS IN A HOMERUN CONDUIT, THE HOMERUN CONDUIT SHALL BE SIZED SO THAT THE CONDUIT FILL DOES NOT EXCEED THAT ALLOWED BY THE NEC.
LOAD SUMMARY
EQUIPMENT
NUMBER
DESCRIPTION
CONNECTED LOAD
DEMAND
FACTOR
HP
AMPERES
KVA
AMPERES
PUMP 210
PUMP 220
TRANSFORMER
85 HP WET WELL PUMP
85 HP WET WELL PUMP
TRANSFORMER 480-120/208
85
85
109
109
18.0
84
84
15.0
1.25
1.00
0.7
136
109
13
480/277V, 3-PHASE, 4-WIRE TOTALS:
258
PANEL-L1
208 /120 VOLTS, THREE PHASE, 4 WIRE BUS: 100A AIC: 101KA MAIN: 50A/3P
MOUNTING: SURFACE
CKT.
NO.
DESCRIPTION
CONNECTED
KVA
TRIP
AMPS/
POLES
CKT.
NO.
DESCRIPTION
CONNECTED
KVA
TRIP
AMPS/
POLES
A
B
C
A
B
C
1
RECEPTACLES
0.1
2 /1
0
2
VAULT WETWELL LIGHTING
U & G G
0 .4
2 /1
0
3
EF-1 EXHAUST FAN
0.6
20/1
4
GEN BATTERY CHARGER
20/1
5
MAIN CONTROL PANEL
1.5
20/1
6
GEN BLOCK HEATER
20/1
7
CONTROL BUILDING LIGHTING
0 5
20/1
8
EH-1 ELECTRIC HEATER
1.5
2 /2
0
9
S PARE
0 1
2 /1
0
1 0
H-1 ELECTRIC HEATER
E ELEC C1.5
20/2
VALVE VAULT SUMP PUMP, P-230
0.711
20/1
12
HOTBOX
00
20/1
1 30
YARD LIGHT
1
2 /1
0
14
S PARE
0 0
20/1
15
VALVE VAULT RECEPT.
00
20/1
PHASE SUBTOTALS (KVA):
0.71
0.7
2.2
1.9
1.7
1.0
PHASE TOTALS (KVA):
2.6
2.41
3.2
TOTAL KVA: 8.2 KVA
TOTAL AMPERES: 22 A
LIGHTING FIXTURE SCHEDULE
.SYMBOL
DESCRIPTION
CATALOG NO.
VOLTAGE
VA
LAMP TYPE
MOUNTING
REMARKS
F1
WRAP -AROUND, INDUSTRIAL, 2-LAMP, FIBERGLASS HOUSING, ACRYLIC DIFFUSER
DMW-2-32-120-ES
120
96
T8 FLUORESCENT
SURFACE
LITHONIA
F2
SUITABLE FOR CLASS 1 DIV 2 HAZARDOUS LOCATION. WALL MOUNT, WET LOCATION
PD-070HP-12-K-W-1-C
120
70
HPS
SURFACE (WALL)
HOLOPHANE PREDATOR SMALL
F3
POLE -MOUNTED HPS FIXTURE, ALUMINUM HOUSING. WITH PE CELL
1A-CCS17A5-150HPS120-DBP-A30
120
1150
IHPS
I PRA14-A-DBP POLE
KIM
F4
SUITABLE FOR CLASS 1 DIV 1 HAZARDOUS LOCATION. WALL MOUNT
PETM-070HP-12-SY-WL
120
170
HPS
SURFACE WALL
HOLOPHANE PETROLUME
F5
WALL PACK, CUT-OFF, 10OW METAL HALIDE, ALUMINUM HOUSING, POLYCARBONATE DIFFUSER, WET LOCATION
TWAC-100M-120-EP-DDB
120
1100
1 METAL HALIDE
SURFACE (WALL)
LITHONIA
Kennedy/Jenks Consultants
32001 32nd Avenue South, Suite 100
Federal Way, WA 98001
Ph. 253-835-6400
Fax 253-952-3435
SURVEYED: SCALE:
DESIGNED: AS NOTED
PAR
DRAWN:
BBH
1 RECORD DRAWING RFB 7/20/12 PAR CHECKED: ONE INCH
PAR AT FULL SCALE
IF NOT ONE INCH
NO. REVISION BY DATE AP P R APPROVED: SCALE ACCORDINGLY
PAR
VERTICAL NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
t j �6 'R CITY OF
RENTON
Planning/Building/Public Works Dept.
S=347339
RECORD DRAWING
These Record Drawings have been prepared based on information provided
by the contractor and others. Kennedy/Jenks Consultants has not verified the
accuracy or completeness of information provided to them and does not
warrant the accuracy or completeness of these Record Drawings. Users of
these Record Drawings assume all risk of loss resulting from their use.
STONEGATE
LIFT STATION REPLACEMENT
ELECTRICAL SCHEDULES
31892
ONIAL
05-24-20101
PAGE:
DRAWING NO:
E11
39 42