HomeMy WebLinkAboutWWP2703628.15ACCESS HATCH LID 4" x 4" X 1/4" STAINLESS STEEL ANGLE IRON. SECURE TO WET WELL INTERIOR ACCESS HATCH FRAME WITH STAINLESS STEEL HARDWARE. SPACE FOR FUTURE FLOAT > PROVIDE A HOOK AT EACH FLOAT CONNECTION TO MOUNTING BRACKET FOR ADJUSTING FLOAT HEIGHT HIGH LEVEL FLOAT 4'-6" ABOVE WET WELL FLOOR WET WELL ROOF NOTE: PUMP START FLOAT S-6" FLOAT ELEVATIONS FIELD ABOVE WET WELL FLOOR ADJUSTED PER ENGINEER AT STARTUP PUMP STOP FLOAT 1'-6" ABOVE WET WELL FLOOR FLOAT MOUNTING DETAIL NOT TO SCALE PROPOSED 2" SQUARE GALVANIZED STEEL UNISTRUT POSTS, Y4" THICK WITH TOP CAP. MAIN DISCONNECT SWITCH PROPOSED 2" SQUARE GALVANIZED STEEL UNISTRUT POSTS, 1/4" THICK. ATTACH HORIZONTAL UNISTRUT MEMBERS AS REQUIRED FOR SUPPORTING ELECTRICAL EQUIPMENT. NOT ALL MEMBERS SHOWN. 4'-0" TO BOTTOM OF LOWEST PANEL (MINIMUM) ELECTRICAL EQUIPMENT PAD PROPOSED CONCRETE FOOTING, TYR. PROPOSED BRUSHED STAINLESS STEEL PLATE MOUNTED TO VALVE FLANGE. PROPOSED LIMIT SWITCH. NOTE: SIZE UNISTRUT WIDTH TO FUTURE EQUIPMENT AS SHOWN ON DWG. NO E04 WIDTH TO FIT ALL EQUIPMENT - L GENERATOR POWER RECPTACLE MANUAL TRANSFER SWITCH, "MTS" UTILITY METER I I a a II e II a 3'-0" a I G a a 41 a e I) A ELECTRICAL ELECTRICAL PEDESTAL FRONT ELEVATION Y ' z 8'-0" INTRUSION DISABLE 1: SWITCH SHELTER ,\ LIGHT SWITCH OUTDOOR DUPLEX ---- RECEPTACLE CHECK VALVE LIMIT SWITCH DETAIL NOT TO SCALE MOTOR CONTROL CENTER, "MCC" EXTERIOR DOORS SO CORD CONNECTOR (TYPICAL). SURFACE MOUNTED J-BOX. SO TYPE CORD. � GRS CONDUIT STRAPPED TO WALL WITH MINIMUM OF (2) STAINLESS STEEL PIPE CLAMPS SPACED EQUALLY APART. 4 LIQUID LEVEL SWITCH. SET TO p REFER TO DWG SWITCH WITH 1/2" OF WATER K NO. E02 FOR ON FLOOR. \ EQUIPMENT SCHEDULE VAULT FLOOD SWITCH DETAIL UNISTRUT AS REQUIRED FOR ELECTRICAL ENCLOSURE ATTACHMENT ELECTRICAL EQUIPMENT PAD PROPOSED DRIVEWAY #5 012" O.C. TOP AND BOTTOM E.W. ��0%° 2.0% ti. � a II • MIN. 6" OF CRUSHED SURFACING BASE / e COURSE I 6,_0„ 12'-0" r ELECTRICAL PEDESTAL SIDE ELEVATION Y z' FINISHED GRADE NOT TO SCALE WELD BRACKET AS TO NOT INTERFERE WITH PUMP REMOVAL AND HATCH CLOSING PUMP GUIDE RAIL 6"x2" PIPE CLAMP (TYPICAL). CONTRACTOR SHALL PROVIDE A MINIMUM OF 3 PIPE CLAMPS SPACED EQUALLY ALONG THE LENGTH OF 2" PIPE FOR SUPPORT. S-6" HANDHOLE GROUND LUG #6 AWG COPPER GROUND CONDUCTOR QUARE x 20'H, SQUARE STRAIGHT L OUTDOOR LIGHTING POLE. \LL PLUMB. OUTDOOR LIGHTING SHALL BE HUBBELL MODEL NO. -20-50-7—TA—BZ, OR EQUAL. 10R BOLTS. INSTALL PER MANUFACTURER'S ZUCTIONS PROPOSED LIGHT POLE BASE PLATE. GROUT BASE PLATE WITH NON —SHRINK GROUT AND SILICONE CAULK AT EDGE. 12" DIAMETER CONCRETE CYLINDER FOR ANCHORING STEEL POLE. 45' CHAMFER AROUND EDGE. 1 24" MIN CONDUIT AS SHOWN ON SITE PLAN (6) #4 VERT EVENLY SPACED #4 HOOPS GROUND ROD - 12" 0. C. OUTDOOR SITE LIGHT FOOTING AND MOUNTING DETAIL NOT TO SCALE 2"x1/4" STAINLESS STEEL SUPPORT 1/2"0 STAINLESS STEEL BOLT AND NUT (TYPICAL). WET WELL HATCH L 79TER��� 'IONAL SIGNED. 05123112 SIGNED. 05123112 ♦N/� 0 W W y 0 crU. LL Raft J Q O U c NNW Um W s Wftj RH2 ENGINEERING, INC. http://www.rh2.com mailbox0rh2.com 1.800.720.8052 BEW NGHAM 3eo.e�6 os 454 West Horton Road 2%2" PIPE CLAMP (TYPICAL) BOTHELL azs.ssi.s,aoo 22722 29th Drive SE, Suite 210 EAST WENATCHEE sos.sas.2sa 300 Simon Street, Suite 5 RICHLAND sos.snas ai 114 Columbia Point Drive, Suite C SILVERDALE 360.876.79M 2021 NW Mhyre Rd, Suite 107 PROPOSED 6" TACOMA 2S3.272.3os9 FORCE MAIN, TYP. 621 Pacific Avenue Suite 104 2" SCH 80 PVC PIPE. PIPE SHALL EXTEND FROM 4" FROM BASE OF SCALE: SHOWN INTERIOR WET WELL TO MOUNTING POINT BETWEEN PUMP RAIL GUIDES. 0 1" 2" DRAWING IS NOT TO SCALE LEVEL TRANSMITTER SLEEVE DETAIL - IF BAR IS NOT 2" LONG _ RECORD DRAWING PLOT: 1 DWG N0. NOT TO SCALE REVISED TO CONFORM ENGINEER: CCA E07 TO SCONSTRUCTIO RECORDS REVIEWED: MLM 362815 r 04/25/12 DATE: Jul 15, 2013 SHEET N0. RH2 RING INC. DATE cuENT: REN 15 REVISED TO CONFORM TO CONSTRUCTION RECORDS AHF EH 04/25/13 Boa NO.: 112-033 17 NO. REVISION BY REVIEW DATE FILENAME: LIBHS—D—EO6.DWG