HomeMy WebLinkAboutWWP2703628.15ACCESS HATCH LID
4" x 4" X 1/4" STAINLESS
STEEL ANGLE IRON. SECURE TO
WET WELL INTERIOR ACCESS
HATCH FRAME WITH STAINLESS
STEEL HARDWARE.
SPACE FOR
FUTURE FLOAT
>
PROVIDE A HOOK AT EACH FLOAT
CONNECTION TO MOUNTING BRACKET
FOR ADJUSTING FLOAT HEIGHT
HIGH LEVEL FLOAT 4'-6"
ABOVE WET WELL FLOOR
WET WELL ROOF
NOTE:
PUMP START FLOAT S-6" FLOAT ELEVATIONS FIELD
ABOVE WET WELL FLOOR ADJUSTED PER ENGINEER AT
STARTUP
PUMP STOP FLOAT 1'-6"
ABOVE WET WELL FLOOR
FLOAT MOUNTING DETAIL
NOT TO SCALE
PROPOSED 2" SQUARE GALVANIZED
STEEL UNISTRUT POSTS, Y4" THICK
WITH TOP CAP.
MAIN DISCONNECT
SWITCH
PROPOSED 2" SQUARE GALVANIZED
STEEL UNISTRUT POSTS, 1/4" THICK.
ATTACH HORIZONTAL UNISTRUT
MEMBERS AS REQUIRED FOR
SUPPORTING ELECTRICAL EQUIPMENT.
NOT ALL MEMBERS SHOWN.
4'-0" TO BOTTOM OF
LOWEST PANEL (MINIMUM)
ELECTRICAL
EQUIPMENT PAD
PROPOSED CONCRETE
FOOTING, TYR.
PROPOSED BRUSHED
STAINLESS STEEL PLATE
MOUNTED TO VALVE
FLANGE.
PROPOSED LIMIT
SWITCH.
NOTE:
SIZE UNISTRUT WIDTH TO FUTURE
EQUIPMENT AS SHOWN ON DWG.
NO E04
WIDTH TO FIT ALL EQUIPMENT -
L GENERATOR POWER
RECPTACLE
MANUAL TRANSFER
SWITCH, "MTS"
UTILITY METER
I I a a
II e
II a
3'-0"
a I
G
a a 41 a
e I) A
ELECTRICAL ELECTRICAL PEDESTAL
FRONT ELEVATION
Y '
z
8'-0"
INTRUSION
DISABLE 1:
SWITCH
SHELTER ,\
LIGHT
SWITCH
OUTDOOR
DUPLEX ----
RECEPTACLE
CHECK VALVE LIMIT SWITCH DETAIL
NOT TO SCALE
MOTOR CONTROL CENTER,
"MCC" EXTERIOR DOORS
SO CORD CONNECTOR (TYPICAL). SURFACE MOUNTED J-BOX.
SO TYPE CORD. �
GRS CONDUIT STRAPPED TO
WALL WITH MINIMUM OF (2)
STAINLESS STEEL PIPE CLAMPS
SPACED EQUALLY APART.
4
LIQUID LEVEL SWITCH. SET TO p REFER TO DWG
SWITCH WITH 1/2" OF WATER K NO. E02 FOR
ON FLOOR. \ EQUIPMENT
SCHEDULE
VAULT FLOOD SWITCH DETAIL
UNISTRUT AS REQUIRED FOR
ELECTRICAL ENCLOSURE
ATTACHMENT
ELECTRICAL
EQUIPMENT PAD
PROPOSED DRIVEWAY #5 012" O.C. TOP AND
BOTTOM E.W.
��0%° 2.0%
ti. � a II •
MIN. 6" OF CRUSHED
SURFACING BASE / e
COURSE
I 6,_0„
12'-0" r
ELECTRICAL PEDESTAL
SIDE ELEVATION
Y z'
FINISHED
GRADE
NOT TO SCALE
WELD BRACKET AS TO NOT
INTERFERE WITH PUMP REMOVAL
AND HATCH CLOSING
PUMP GUIDE RAIL
6"x2" PIPE CLAMP (TYPICAL).
CONTRACTOR SHALL PROVIDE A
MINIMUM OF 3 PIPE CLAMPS
SPACED EQUALLY ALONG THE
LENGTH OF 2" PIPE FOR SUPPORT.
S-6"
HANDHOLE
GROUND LUG
#6 AWG COPPER GROUND
CONDUCTOR
QUARE x 20'H, SQUARE STRAIGHT
L OUTDOOR LIGHTING POLE.
\LL PLUMB. OUTDOOR LIGHTING
SHALL BE HUBBELL MODEL NO.
-20-50-7—TA—BZ, OR EQUAL.
10R BOLTS. INSTALL PER
MANUFACTURER'S
ZUCTIONS
PROPOSED LIGHT POLE BASE
PLATE. GROUT BASE PLATE WITH
NON —SHRINK GROUT AND SILICONE
CAULK AT EDGE.
12" DIAMETER CONCRETE CYLINDER
FOR ANCHORING STEEL POLE. 45'
CHAMFER AROUND EDGE.
1 24" MIN
CONDUIT AS SHOWN
ON SITE PLAN
(6) #4 VERT
EVENLY SPACED
#4 HOOPS
GROUND ROD -
12" 0. C.
OUTDOOR SITE LIGHT FOOTING AND
MOUNTING DETAIL
NOT TO SCALE
2"x1/4" STAINLESS STEEL
SUPPORT
1/2"0 STAINLESS STEEL BOLT
AND NUT (TYPICAL).
WET WELL HATCH
L
79TER���
'IONAL
SIGNED. 05123112
SIGNED. 05123112
♦N/�
0
W
W
y
0
crU.
LL
Raft
J
Q
O
U
c
NNW
Um
W
s
Wftj
RH2 ENGINEERING, INC.
http://www.rh2.com
mailbox0rh2.com 1.800.720.8052
BEW NGHAM 3eo.e�6 os
454 West Horton Road
2%2" PIPE CLAMP (TYPICAL)
BOTHELL azs.ssi.s,aoo
22722 29th Drive SE, Suite 210
EAST
WENATCHEE sos.sas.2sa
300 Simon Street, Suite 5
RICHLAND sos.snas ai
114 Columbia Point Drive, Suite C
SILVERDALE 360.876.79M
2021 NW Mhyre Rd, Suite 107
PROPOSED 6" TACOMA 2S3.272.3os9
FORCE MAIN, TYP. 621 Pacific Avenue Suite 104
2" SCH 80 PVC PIPE. PIPE SHALL
EXTEND FROM 4" FROM BASE OF SCALE: SHOWN
INTERIOR WET WELL TO MOUNTING
POINT BETWEEN PUMP RAIL GUIDES.
0 1" 2"
DRAWING IS NOT TO SCALE
LEVEL TRANSMITTER SLEEVE DETAIL - IF BAR IS NOT 2" LONG
_ RECORD DRAWING PLOT: 1 DWG N0.
NOT TO SCALE REVISED TO CONFORM ENGINEER: CCA E07
TO SCONSTRUCTIO RECORDS
REVIEWED: MLM 362815
r 04/25/12 DATE: Jul 15, 2013 SHEET N0.
RH2 RING INC. DATE cuENT: REN 15
REVISED TO CONFORM TO CONSTRUCTION RECORDS AHF EH 04/25/13 Boa NO.: 112-033 17
NO. REVISION BY REVIEW DATE FILENAME: LIBHS—D—EO6.DWG