HomeMy WebLinkAboutGateway - Elec E3 11.7.00ROUTE CONDUIT TO A
HEIGHT APPROX 12"
ABOVE THE HIGHEST
WiNVIOW OR DOOR
OPL' RING IN THE WALL.
CONDUITS FROM THE
THREE RECEPTACLE
BANKS ARE TO BE
ROUTED TOGETHER —,,
50A, 240V NEMA 14-50R RECEPTACLE
WEATHERPROOF WHEN IN USE, SPRING
LOADED COVER DOOR
ao�X c 6p'/C,5U
o��o
DEDICATED 20A, 120V, NEMA 5-20R
GFCI WEATHERPROOF WHEN IN USE,
SPRING LOADED COVER DOOR
I
MA 14-30R RECEPTACLE
WEA tFiLr i-, :,jOF WHEN IN USE, SPRING
LOADED COVER DOOR
SHED GRADE
1. SURFACE MOUNT RECEPTACLES TO BUILDING FACADE.
9 4i u, ut w u^ C l ocy
RECEPTACLE BANK - 112
SCALE: NONE
CONC VAULT !LAR TO UTIUTY
VAULT 3030-LA EQUIVALENT,
WITH DIAMOND PLA OCKING
COVER---`�-°.
50A, 240V RCPT
NEMA 14-50R, WEATHER-
PROOF WHEN IN USE,
SPRING LOADED COVER,
MOUNTED NEXT TO 30A,
240V RCPT NEMA 14-30R,
WEEATHERPROOF WHEN
IN USE, SPRING LOADED
COVER
CIRCUIT AS
SHOWN ON
DRAWING
RECEPTACLE BANK - 4
E21E3
FINISHED GRADE
20A, 150V RCPT
NEMA 5-20R, GFCI
WEATHERPROOF WHEN
IN USE, SPRING LOADED
COVER (TYP OF 2 RCPT)
PEA GRAVEL
N
FLAG NOTES
t`~ PROVIDE NEMA 3R ENCLOSURE AND SOCKET FOR UTILITY METER.
COORDINATE WITH UTILITY FOR EXACT REQUIREMENTS.
EXTEND CONDUIT AND CABLE TO UTILITY OWNED VAULT AS SHOWN.
PROVIDE 5' ADDITIONAL CABLE LENGTH TO ALLOW FOR TERMINATION
BY UTILITY. COORDINATE WITH UTILITY COMPANY FOR EXACT
REQUIREMENTS AND CONDUIT ENTRY INTO VAULT.
PROVIDE NEMA TYPE 3R, PAD -LOCKABLE ENCLOSURE. SIZE AS
REQUIRED.
SHEET NOTES
1. COORDINATE TRENCHING REQUIREMENTS WITH UNDERGROUND
EQUIPMENT. CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL
EXISTING UNDERGROUND EQUIPMENT. LOCATE TRENCHES TO
MINIMIZE IMPACT TO EXISTING LANDSCAPING. RESTORE TO
ORIGINAL CONDITION WITH LIKE MATERIALS.
2. ALL EXPOSED CONDUIT TO BE RGS. ALL UNDERGROUND
CONDUIT TO BE PVC WITH RGS BENDS. SIZE AS SHOWN ON
DRAWINGS.
3. ALL RACEWAYS SHOWN TO BE 3/4-C WITH 2#10,1#10G
THHN/THWN STRANDED COPPER CONDUCTOR UNLESS NOTED
OTHERWISE.
4. ALL DUPLEX RECEPTACLES TO BE WEATHERPROOF AND
GROUND FAULT INTERRUPTING.
0
SCALE, 1/81 • 1'-0'
CITY OF RENTON
THE BERGER
PARTNERSHIP, P
LANDSCAPE ARCHITECTURE
SITE PLANNING
2021 Minor East
Seattle, WA 98102
(206) 325-6877
(206) 323-6867 Fa;
ABACUS
Engineered Systems
401 Second Ave. So. Suite 201
Seattle, Woshin ton 98104
(206)583-0200 F=x 206)583-8826
I EXPIRES: 11-27-00 1
DRAWN BY ti.iE
CHECKED BY RLV. DLL
REVISIONS
AS-- I 1/-7 //M
11n; 0?
LIGHTING &
pp
t-"OY11Eh
LAYOUT
SCALE: NONE
E2IE3