HomeMy WebLinkAboutResidential Alteration Energy Code ChecklistAre the windows and/or doors being replaced?
If yes,
New windows and doors (+frames) must have an area weighted average U-factor of ≤0.30
Will the heating or cooling system be replaced?
If yes,
New equipment must meet
current requirements and the
ducts need to be tested
Will the hot water system be altered?
If yes,
New water heating equipment must meet current code requirements
Are more than 10% of the light fixtures being changed?
If yes,
100% of all lamps must be high efficacy
Remodel / Alteration Worksheet
Will you be exposing the walls?
If yes,
2 X 4 wall studs require R-15 insulation
2 X 6 wall studs require R-21 insulation
If siding is replaced C.I. equal to R-5 will
need installed under the siding.
Will the roof/ceiling framing cavities or attic
be exposed?
If yes,
Exposed roof or ceiling assemblies must be insulated -
Vaulted ceilings, Insulate to the full
depth of the framing member
Flat ceilings, install R-60 insulation or
what the attic space can
accommodate based on the roof
pitch
Will the will the floor framing cavities be
exposed?
If yes,
Exposed floor cavities must be
insulated to R-30
Yes Yes Yes
Yes Yes Yes Yes
No No
No No No No
No
R503.1.1.1 Replacement fenestration.
Where some or all of an existing fenestration unit is replaced with a new fenestration product, including sash and glazing,
the replacement fenestration unit shall meet the applicable requirements for U-factor and SHGC in Table R402.1.3.
Where more than one replacement fenestration unit is being installed, an area-weighted average of the U-factor and
SHGC of all replacement fenestration shall be permitted to be used to demonstrate compliance.
R503.1.1 Building envelope.
Building envelope assemblies that are part of the alteration shall comply with Section R402.1.3 or R402.1.5, Sections
R402.2.1 through R402.2.11, R402.3.1, R402.3.2, R402.3.5 and R402.4.2.
Exception: The following alterations need not comply with the requirements for new construction provided the energy
use of the building is not increased:
1. Storm windows installed over existing fenestration.
2. Existing ceiling, wall or floor cavities exposed during construction provided that these cavities are filled with
insulation. 2x4 framed walls shall be insulated to a minimum of R-15 and 2x6 framed walls shall be insulated to a
minimum of R-21.
3. Construction where the existing roof, wall or floor cavity is not exposed.
4. Roof recover.
5. Roofs without insulation in the cavity and where the sheathing or insulation is exposed during reroofing shall be
insulated either above or below the sheathing.
6. Surface-applied window film installed on existing single pane fenestration assemblies to reduce solar heat gain
provided the code does not require the glazing fenestration to be replaced.
R503.2 Change in space conditioning. Any nonconditioned or low-energy space
that is altered to become conditioned space shall be required to be brought into
full compliance with this (WSEC-R) code.
R502.1.1.2 Heating and cooling systems.
New heating, cooling and duct systems that are part of the addition shall comply with Section R403.
Exception:
The following need not comply with the testing requirements of Section R403.3.3:
1. Additions of less than 750 square feet.
2. Duct systems that are documented to have been previously sealed as confirmed through field verification
and diagnostic testing in accordance with procedures in WSU RS-33.
3. Ducts with less than 40 linear feet in unconditioned spaces.
4. Existing duct systems constructed, insulated or sealed with asbestos.
R503.1.4 Lighting.
New lighting systems that are part of the alteration shall comply with Section R404.1.
Exception: Alterations that replace less than 10 percent of the luminaires in a space, provided that such
alterations do not increase the installed interior lighting power.
R503.1.3 Service hot water systems.
New service hot water systems that are part of the alteration shall comply with Section R403.5.
R503.1.2 Heating and cooling systems.
New heating, cooling and duct systems that are part of the alteration shall comply with Section R403.
Exceptions:
1. Where ducts from an existing heating and cooling system are extended, duct systems with less than 40 linear
feet in unconditioned spaces shall not be required to be tested in accordance with Section R403.2.2
2. Existing duct systems constructed, insulated or sealed with asbestos.