' Know whats below
Call before you dig.
BUILDING CODE COMPLIANCE
ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN ACCORDANCE WITH THE
CURRENT CONDITIONS OF THE FOLLOWING CODES AS ADOPTED BY THE LOCAL GOVERNING
AUTHORITIES. NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMIT WORK NOT
CONFORMING TO THESE CODES:
WASHINGTON STATE AND LOCAL BUILDING CODES:
2015 INTERNATIONAL BUILDING CODE
2012 SEATTLE BUILDING CODE
2014 NATIONAL ELECTRIC CODE
TIA-222-G OR LATEST EDITION
PROJECT INFORMATION
PROJECTION DESCRIPTION:
AT&T PROPOSES TO INSTALL A NEW 60' STEEL POLE (30"¢) IN EXISTING PARKING LOT AND
MODIFY AN EXISTING ROOFTOP TELECOMMUNICATIONS FACILITY BY REMOVING (6) EXISTING LTE
ANTENNAS (3 PER SECTOR) AND ALL RELATED EQUIPMENT ON ROOFTOP. (2) RRHs & (4)
DIPLEXERS SHALL BE RELOCATED TO NEW CONCEALMENT POLE FROM ROOFTOP. AT&T ALSO
PROPOSES THE INSTALLATION OF (4) NEW PANEL ANTENNAS, (8) DIPLEXERS, (6) TMAs, (4)
RRHs.
APPLICANT: RFDS
AT&T MOBILITY RFDS V 3.0 DATED 06/06/16
RTC BUILDING 3
16221 NE 72ND WAY PROPERTY OWNER:
REDMOND, WA 98052 PAIK SEUNG
2439 MAPLE VALLEY HWY, SUITE B
CODE INFORMATION: RENTON, WA 98055
ZONING CLASSIFICATION: COR
JURISDICTION: CITY OF RENTON SITE ACQUISITION:
BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE MASTEC
1203 114TH AVE SE
SITE LQQATION (BASED ON NAD 83}: BELLEVUE, WA 98004
LATITUDE: 47" 28' 39" N (47.4775) CONTACT: DANIEAL KELLY .
LONGITUDE: 122" 11' 12.984" W ( 122.18694) PH: ( 425) 214""'.97'1§L .. ,,c •
TOP OF STRUCTURE AGL: ±60.0' .. DANIEL.KELLY@MASTEC.COM
BASE OF STRUCTURE ASML: ±60.0' CONSTRUQTIQN MANAGER:
PARQEL. NUMBER(S}: MASTEC
1203 114TH AVE SE 1723059140 & 1723059147 BELLEVUE, WA 98004
GENERAL INFORMATION: CONTACT: MICHAEL MILSAP
1. TRAFFIC IS UNAFFECTED. MICHAEL.MILSAP@MASTEC.COM
PERMITTING:
RYKA CONSULTING
CONTACT: JENNIFER TAYLOR
EMAIL: JTAYLOR@RYKACONSULTING.COM
PHONE: (206) 523-1941
AT&T PROJECT MANAGER:
CONTACT: JOSHUA ADIAR
EMAIL: JA635M@ATT.COM
PHONE: (971) 266-9770
CONTACT INFORMATION
ENGINEER: GPD GROUP PROFESSIONAL CORPORATION
400 NORTH 34TH STREET, SUITE 216
SEATTLE, WASHINGTON 98103
CONTACT: JAMES GRANT
PHONE: (206) 204-7398
i
,.
N
mobility
CEDAR RIVER
SD24
10097913
2439 SE MAPLE
VALLEY HWY
RENTON, WA 98055
LOCAL MAP
DRIVING DIRECTIONS
DIRECTIONS FROM REGIONAL OFFICE ( 16221 NE 72ND WAY, REDMOND, WA 98052):
GET ON WA-520 W FROM BEAR CREEK PKWY AND LEARY WAY NE 4 MIN (1.1 Ml), HEAD SOUTHEAST ON NE 72ND
WAY TOWARD 164TH AVE NE 427 FT, TURN RIGHT ONTO 164TH AVE NE 203 FT, TURN RIGHT ONTO BEAR CREEK
PKWY 0.3 Ml, TURN LEFT ONTO LEARY WAY NE 0.3 Ml, USE THE MIDDLE 2 LANES TO TAKE THE RAMP ONTO
WA-520 W 0.4 Ml, FOLLOW WA-520 W AND 1-405 S TO WA-900/SUNSET BLVD N IN RENTON. TAKE EXIT 4 FROM
1-405 S 17 MIN (15.2 Ml), MERGE ONTO WA-520 W 4.6 Ml, TAKE THE INTERSTATE 405 S EXIT TOWARD RENTON
0.2 Ml, MERGE ONTO 1-405 S 3.2 Ml, KEEP LEFT TO STAY ON 1-405 S 6.9 Ml, TAKE EXIT 4 FOR WA-900 W
TOWARD WA-169 S/RENTON/ENUMCLAW 0.2 Ml, FOLLOW WA-900/SUNSET BLVD N AND WA-169 S TO YOUR
DESTINATION 4 MIN (1.1 Ml), MERGE ONTO WA-900/SUNSET BLVD N 0.4 Ml, USE THE LEFT 2 LANES TO TURN
LEFT ONTO WA-169 S 0.7 Ml, TURN RIGHT 128 FT, TURN LEFT, DESTINATION WILL BE ON THE LEFT 89 FT
PROPRIETARY INFORMATION
THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION
DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE
OTHER THAN THAT WHICH RELATES TO CARRIER SERVICES IS
STRICTLY PROHIBITED.
LEGAL DESCRIPTION
POR GL 8-BEG AT INTSN OF E LN WITH SLY MGN OF MAPLE VALLEY HWY TH NWLY ALG HWY 167.48 FT
TO TPOB TH S 01-14-13 W 117.96 FT TH N 56-43-47 W 201.14 FT TH N 33-16-13 E TO SLY MGN
OF HWY TH TO TPOB LESS SR 169
DRAWING INDEX
SHEET NO: SHEET TITLE
\-:
T-1 TITLE SHEET ''\
.
GN-1 LEGENDS, ABBREVIATIONS & CONSTRUCTION INSPECflQNS
GN-2 GENERAL NOTES '1
,_., • ' .. C-1 OVERALL SITE PLAN •.
'"
.
C-2 COMPOUND PLAN & EQUIPMENT LAYOUT . I
'. -..
C-3 SOUTH TOWER ELEVATION I
' •. \ ,.
C-4 NORTH TOWER ELEVATION /;>
.• "i
1A SURVEY CERTIFICATION C
. ' -' . ..
. .r·· t • . .
l
• ' ~ .
. ,. .
.
' . .
.
.
APPROVAL DATE SIGNATURE APPROVAL DATE SIGNATURE
RF ENGINEER: LANDLORD:
.
RF MANAGER: SITE ACQUISITION:
OPPS MANAGER: ZONING AGENT:
CONSTR. MANAGER: PROJECT MANAGER:
NSB MANAGER: CONSTR. MANAGER:
TRANSPORT:
EQUIP. ENGINEER:
COMPLIANCE:
REVIEWERS SHALL CLEARLY PLACE INITIALS ADJACENT TO EACH REDLINE NOTE AS DRAWINGS ARE BEING REVIEWED
.
11"x17" PLOT WILL BE HALF SCALE UNLESS OTHERWISE NOTED
GENERAL NOTES
THE FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION. A TECHNICIAN WILL VISIT THE
SITE AS REQUIRED FOR ROUTINE MAINTENANCE. THE PROJECT WILL NOT RESULT IN ANY
SIGNIFICANT DISTURBANCE OR EFFECT ON DRAINAGE: NO SANITARY SEWER SERVICE, POTABLE
WATER, OR TRASH DISPOSAL IS REQUIRED AND NO COMMERCIAL SIGNAGE IS PROPOSED.
CONTRACTOR SHALL VERIFY ALL PLANS & EXISTING DIMENSIONS & CONDITIONS ON
THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE ENGINEER IN WRITING OF ANY DISCREPANCIES
BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME
·.
...
'
· . ·~-~-
'. '"" '"'
at&t
mobility
·=·r'I a sTe c
Network Solutions
•.:. GPDGROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 4431-1
330.572.2100 Fax: 330.572.2102
PROJECT NO: 2016723.04.11566.01
.
DRAWN BY: CJM
CHECKED BY: JG
B 09/13/16 REVISED PER CLIENT COMMENTS
A . 07/29/16 ISSUED FOR REVIEW
IT JS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
LTE -STEALTH POLE
SHEET TITLE
TITLE SHEET
SHEET NUMBER
T-1
l'i'.t: !:. ! V ,-iJ
NOV O 9 2016
EXOTHERMIC CONNECTION
MECHANICAL CONNECTION
CHEMICAL ELECTROLYTIC GROUNDING SYSTEM
TEST CHEMICAL ELECTROLYTIC GROUNDING SYSTEM
EXOTHERMIC WITH INSPECTION SLEEVE
GROUNDING BAR
GROUND ROD
TEST GROUND ROD WITH INSPECTION SLEEVE
SINGLE POLE SWITCH
DUPLEX RECEPTACLE
DUPLEX GFCI RECEPTACLE
FLUORESCENT LIGHTING FIXTURE
(2) TWO LAMPS 48-T8
SMOKE DETECTION (DC)
EMERGENCY LIGHTING (DC)
SECURITY LIGHT W/PHOTOCELL LITHONIA ALXW
LED-1-25A400/51 K-SR4-120-PE-DDBTXD
CHAINLINK FENCE
WOOD/WROUGHT IRON FENCE
WALL STRUCTURE
LEASE AREA
PROPERTY LINE (PL)
SETBACKS
ICE BRIDGE
CABLE TRAY
WATER LINE
UNDERGROUND POWER
UNDERGROUND TELCO
OVERHEAD POWER
OVERHEAD TELCO
UNDERGROUND TELCO/POWER
ABOVE GROUND POWER
ABOVE GROUND TELCO
ABOVE GROUND TELCO/POWER
WORKPOINT
SECTION REFERENCE
DETAIL REFERENCE
r------------,
I I
I F I I I
I I L ___________ _J
G
~
D
-x--x--x--x--,--,--,--,--,-
--
----------------------
I++++++++·+·++·+++++++++ •••••••••• :I
+ + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + + +
-w-w-w-w-w-w-w-w-w-w-
--.... --... --.. --UGP--UliJP e. UGll",_-UO, __ ,,, __
. ·~ ,-
-Clf' --OHP --OHP --OHP --Clf' --OHP --OHP -
--------------------------------------------------------------------
-------------------
$
W.P.
@ x-x
@
LEGEND 1
AB
ABV
AC
ADDL
AFF
AFG
AIC
ANCHOR BOLT
ABOVE
ALTERNATING CURRENT
ADDITIONAL
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERAGE INTERRUPTION CAPACITY
ALUM ALUMINUM
ALT ALTERNATE
ANT ANTENNA
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BATI BATIERY
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM
BTC
BOF
CAB
CANT
CEC
CHG
CLG
CLR
COL
COMM
BEAM
BARE TINNED COPPER CONDUCTOR
BOTIOM OF FOOTING
CABINET
CANTILEVERED
CALIFORNIA ELECTRIC CODE
CHARGING
CEILING
CLEAR
COLUMN
COMMON
CONG CONCRETE
CONSTR CONSTRUCTION
DBL DOUBLE
DC DIRECT CURRENT
DEPT
OF
DIA
DIAG
DIM
DWG
OWL
(E)
EA
EC
EL
ELEC
EMT
ENG
EQ
EXP
EXT
FAB
FF
FG
FIF
FIN
FLR
FON
FOC
FOM
FOS
FOW
FS
FT
FTG
GA
GEN
GFCI
GLB
GLV
GPS
GND
GSM
HOR
HGR
HVAC
HT
IGR
IN
DEPARTMENT
DOUGLAS FIR
DIAMETER
DIAGONAL
DIMENSION
DRAWING
DOWEL
EXISTING
EACH
ELECTRICAL CONDUCTOR
ELEVATION
ELECTRICAL
ELECTRICAL METALLIC TUBING
ENGINEER
EQUAL
EXPANSION
EXTERIOR
FABRICATION
FINISH FLOOR
FINISH GRADE
FACILITY INTERFACE FRAME
FINISH(ED)
FLOOR
FOUNDATION
FACE OF CONCRETE
FACE OF MASONRY
FACE OF STUD
FACE OF WALL
FINISH SURFACE
FOOT
FOOTING
GAUGE
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GLUE LAMINATED BEAM
GALVANIZED
GLOBAL POSITIONING SYSTEM
GROUND
GLOBAL SYSTEM FOR MOBILE
HEADER
HANGER
HEAT/VENTILATION/AIR CONDITIONING
HEIGHT
INTERIOR GROUND RING
INCH
INT
LB(S)
LF
MAS
MAX
MB
MECH
INTERIOR
POUND(S)
LINEAR FEET
MASONRY
MAXIMUM
MACHINE BOLT
MECHANICAL
MFR MANUFACTURER
MGB MASTER GROUND BAR
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
MTS MANUAL TRANSFER SWITCH
MW MICROWAVE
(N) NEW
NEC NATIONAL ELECTRIC CODE
NO.(#) NUMBER
NTS NOT TO SCALE
oc
OPNG
(P)
P/C
PCS
PCU
PRC
pp
PSF
PSI
PT
PWR
QTY
RAD
RECT
REF
REINF
REQ'D
RET
RMC
RRH
RRU
RWY
SCH
SHT
SIAD
SIM
SPEC
SQ
ss
STD
STL
STRUCT
TEMP
THK
TMA
TN
TOA
TOC
TOF
TOP
TOS
TOW
TVSS
TYP
UG
UL
UNO
UMTS
UPS
VIF
w
W/
WO
W.P.
WP
WT
ON CENTER
OPENING
PROPOSED
PRECAST CONCRETE
PERSONAL COMMUNICATION SERVICES
PRIMARY CONTROL UNIT
PRIMARY RADIO CABINET
POLARIZING PRESERVING
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PRESSURE TREATED
POWER CABINET
QUANTITY
RADIUS
RECTIFIER
REFERENCE
REINFORCEMENT
REQUIRED
REMOTE ELECTRIC TILT
RIGID METALLIC CONDUIT
REMOTE RADIO HEAD
REMOTE RADIO UNIT
RACEWAY
SCHEDULE
SHEET
SMART INTEGRATED DEVICE
SIMILAR
SPECIFICATION
SQUARE
STAINLESS STEEL
STANDARD
STEEL
STRUCTURAL
TEMPORARY
THICKNESS
TOWER MOUNTED AMPLIFIER
TOE NAIL
TOP OF ANTENNA
TOP OF CURB
TOP OF FOUNDATION
TOP OF PLATE (PARAPET)
TOP OF STEEL
TOP OF WALL
TRANSIENT VOLTAGE SUPPRESSION SYSTEM
TYPICAL
UNDERGROUND
UNDERWRITERS LABORATORY
UNLESS NOTED OTHERWISE
UNIVERSAL MOBILE TELECOMMUNICATIONS
SYSTEM
UNITERRUPTIBLE POWER SYSTEM
(DC POWER PLANT)
VERIFIED IN FIELD
WIDE
WITH
WOOD
WORK POINT
WEATHERPROOF
WEIGHT
ABBREVIATIONS 2 NOT USED
.
i
i
l
j
I
I
\
3
. _ .. ' '': ·:: .
at&t
mobility
·=NasTec
Network Solutions
~:
GPDGROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
PROJECT NO: 2016723.04.11566.01
DRAWN BY: CJM
CHECKED BY: JG
B 09/13/16 REVISED PER CLIENT COMMENTS
A 07/29/16 ISSUED FOR REVIEW
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
LTE -STEALTH POLE
SHEET TITLE
LEGENDS, ABBREVIATIONS &
CONSTRUCTION INSPECTIONS
SHEET NUMBER
GN-1
l-.1~-i ···\\Ir.·,./ ~I~ ,..,...L :l' _1.~
NOV o 9 2016
GENERAL CONSTRUCTION
1. FOR THE PURPOSE OF CONSTRUCTION DRAWINGS, THE FOLLOWING DEFINITIONS SHALL APPLY:
. GENERAL CONTRACTOR -MASTEC
CONTRACTOR: (CONSTRUCTION)
OWNER -AT&T
ENGINEER -GPD GROUP
2. ALL SITE WORK SHALL BE COMPLETED AS INDICATED ON THE DRAWINGS AND AT&T PROJECT SPECIFICATIONS.
3. GENERAL CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH ALL CONDITIONS
AFFECTING THE PROPOSED WORK AND SHALL MAKE PROVISIONS. GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR FAMILIARIZING HIMSELF WITH ALL CONTRACT DOCUMENTS, FIELD CONDITIONS, DIMENSIONS,
AND CONFIRMING THAT THE WORK MAY BE ACCOMPLISHED AS SHOWN PRIOR TO PROCEEDING WITH
CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER PRIOR TO
THE COMMENCEMENT OF WORK.
4. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE CODES,
REGULATIONS, AND ORDINANCES. GENERAL CONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND
COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS, AND LAWFUL ORDERS OF ANY PUBLIC
AUTHORITY REGARDING THE PERFORMANCE OF WORK.
5. ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTILITY COMPANY
SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES, AND APPLICABLE REGULATIONS.
6. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT, APPURTENANCES,
AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE DRAWINGS.
7. PLANS ARE NOT TO BE SCALED. THESE PLANS ARE INTENDED TO BE A DIAGRAMMATIC OUTLINE ONLY
UNLESS OTHERWISE NOTED. DIMENSIONS SHOWN ARE TO FINISH SURFACES UNLESS OTHERWISE NOTED.
SPACING BETWEEN EQUIPMENT IS THE MINIMUM REQUIRED CLEARANCE. THEREFORE, IT IS CRITICAL TO FIELD
VERIFY DIMENSIONS, SHOULD THERE BE ANY QUESTIONS REGARDING THE CONTRACT DOCUMENTS, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A CLARIFICATION FROM THE ENGINEER PRIOR TO
PROCEEDING WITH THE WORK. DETAILS ARE INTENDED TO SHOW DESIGN INTENT. MODIFICATIONS MAY BE
REQUIRED TO SUIT JOB DIMENSIONS OR CONDITIONS AND SUCH MODIFICATIONS SHALL BE INCLUDED AS
PART OF WORK AND PREPARED BY THE ENGINEER PRIOR TO PROCEEDING WITH WORK.
8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE.
9. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR
SHALL PROPOSE AN ALTERNATIVE INSTALLATION SPACE FOR APPROVAL BY THE ENGINEER PRIOR TO
PROCEEDING.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE SAFETY OF WORK AREA, ADJACENT AREAS AND
BUILDING OCCUPANTS THAT ARE LIKELY TO BE AFFECTED BY THE WORK UNDER THIS CONTRACT. WORK
SHALL CONFIRM TO ALL OSHA REQUIREMENTS AND THE LOCAL JURISDICTION.
11. GENERAL CONTRACTOR SHALL COORDINATE WORK AND SCHEDULE WORK ACTIVITIES WITH OTHER DISCIPLINES.
12. ERECTION SHALL BE DONE IN A WORKMANLIKE MANNER BY COMPETENT EXPERIENCED WORKMAN IN
ACCORDANCE WITH APPLICABLE CODES AND THE BEST ACCEPTED PRACTICE. ALL MEMBERS SHALL BE LAID
PLUMB AND TRUE AS INDICATED ON THE DRAWINGS.
13. SEAL PENETRATIONS THROUGH FIRE RATED AREAS WITH UL LISTED MATERIALS APPROVED BY LOCAL
JURISDICTION. CONTRACTOR SHALL KEEP AREA CLEAN, HAZARD FREE, AND DISPOSE OF ALL DEBRIS.
14. WORK PREVIOUSLY COMPLETED IS REPRESENTED BY LIGHT SHADED LINES AND NOTES. THE SCOPE OF WORK
FOR THIS PROJECT IS REPRESENTED BY DARK SHADED LINES AND NOTES. CONTRACTOR SHALL NOTIFY THE
GENERAL CONTRACTOR OF ANY EXISTING CONDITIONS THAT DEVIATE FROM THE DRAWINGS PRIOR TO
BEGINNING CONSTRUCTION.
15. CONTRACTOR SHALL PROVIDE WRITTEN NOTICE TO THE CONSTRUCTION MANAGER 48 HOURS. PRIOR TO
COMMENCEMENT OF WORK.
16. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS,• LANDSCAPING AND
STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT CONTRACTOR'S EXPENSE TO THE SATISFACTION OF
THE OWNER.
17. THE CONTRACTOR SHALL CONTACT UTILITY LOCATING SERVICES PRIOR TO THE START OF CONSTRUCTION.
18. GENERAL CONTRACTOR SHALL COORDINATE AND MAINTAIN ACCESS FOR ALL TRADES AND CONTRACTORS TO
THE SITE AND/OR BUILDING.
19. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SECURITY OF THE SITE FOR THE DURATION OF
CONSTRUCTION UNTIL JOB COMPLETION.
20. THE GENERAL CONTRACTOR SHALL MAINTAIN IN GOOD CONDITION ONE COMPLETE SET OF PLANS WITH ALL
REVISIONS, ADDENDA, AND CHANGE ORDERS ON THE PREMISES AT ALL TIMES.
21. THE GENERAL CONTRACTOR SHALL PROVIDE PORTABLE FIRE EXTINGUISHERS WITH A RATING OF NOT LESS
THAN 2-A OT 2-A:10-B:C AND SHALL BE WITHIN 25 FEET OF TRAVEL DISTANCE TO ALL PORTIONS OF
WHERE THE WORK IS BEING COMPLETED DURING CONSTRUCTION.
22. ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES SHALL BE PROTECTED AT ALL
TIMES, AND WHERE REQUIRED FOR THE PROPER EXECUTION OF THE WORK, SHALL BE RELOCATED AS
DIRECTED BY THE ENGINEER. EXTREME CAUTION SHOULD BE USED BY THE CONTRACTOR WHEN EXCAVATING
OR DRILLING PIERS AROUND OR NEAR UTILITIES. CONTRACTOR SHALL PROVIDE SAFETY TRAINING FOR THE
WORKING CREW. THIS SHALL INCLUDE BUT NOT BE LIMITED TO A) FALL PROTECTION, B) CONFINED SPACE,
C) ELECTRICAL SAFETY, AND D) TRENCHING & EXCAVATION.
23. ALL EXISTING INACTIVE SEWER, WATER, GAS, ELECTRIC, AND OTHER UTILITIES, WHICH INTERFERE WITH THE
EXECUTION OF THE WORK, SHALL BE REMOVED, CAPPED, PLUGGED OR OTHERWISE DISCONNECTED AT POINTS
WHICH WILL NOT INTERFERE WITH THE EXECUTION OF THE WORK, AS DIRECTED BY THE RESPONSIBLE
ENGINEER, AND SUBJECT TO THE APPROVAL OF THE OWNER AND/OR LOCAL UTILITIES.
24. THE AREAS OF THE OWNER'S PROPERTY DISTURBED BY THE WORK AND NOT COVERED BY THE TOWER,
EQUIPMENT OR DRIVEWAY, SHALL BE GRADED TO A UNIFORM SLOPE, AND STABILIZED TO PREVENT EROSION.
25. CONTRACTOR SHALL MINIMIZE DISTURBANCE TO THE EXISTING SITE DURING CONSTRUCTION. EROSION
CONTROL MEASURES, IF REQUIRED DURING CONSTRUCTION, SHALL BE IN CONFORMANCE WITH THE FEDERAL
AND LOCAL JURISDICTION FOR EROSION AND SEDIMENT CONTROL.
26. NO FILL OR EMBANKMENT MATERIAL SHALL BE PLACED ON FROZEN GROUNDING. FROZEN MATERIALS, SNOW
OR ICE SHALL NOT BE PLACED IN ANY FILL OR EMBANKMENT.
27. THE SUBGRADE SHALL BE BROUGHT TO A SMOOTH UNIFORM GRADE AND COMPACTED TO 95 PERCENT
STANDARD PROCTOR DENSITY UNDER PAVEMENT AND STRUCTURES AND 80 PERCENT STANDARD PROCTOR
DENSITY IN OPEN SPACE. ALL TRENCHES IN PUBLIC RIGHT OF WAY SHALL BE BACKFILLED WITH FLOWABLE
FILL OR OTHER MATERIAL PRE-APPROVED BY THE LOCAL JURISDICTION.
28. ALL NECESSARY RUBBISH, STUMPS, DEBRIS, STICKS, STONES, AND OTHER REFUSE SHALL BE REMOVED FROM
THE SITE AND DISPOSED OF IN A LAWFUL MANNER.
29. ALL BROCHURES, OPERATING AND MAINTENANCE MANUALS, CATALOGS, SHOP DRAWINGS, AND OTHER
DOCUMENTS SHALL BE TURNED OVER TO THE GENERAL CONTRACTOR AT COMPLETION OF CONSTRUCTION AND
PRIOR TO PAYMENT.
30. CONTRACTOR SHALL SUBMIT A COMPLETE SET OF AS-BUILT REDLINES TO THE GENERAL CONTRACTOR UPON
COMPLETION OF PROJECT AND PRIOR TO FINAL PAYMENT.
31. CONTRACTOR SHALL LEAVE PREMISES IN A CLEAN CONDITION.
32. THE PROPOSED FACILITY WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR SEWER SERVICE,
AND IS NOT FOR HUMAN HABITAT (NO HANDICAP ACCESS REQUIRED).
33. OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION, APPROXIMATELY 2 TIMES PER MONTH,
BY AT&T TECHNICIANS.
34. NO OUTDOOR STORAGE OR SOLID WASTE CONTAINERS ARE PROPOSED.
35. ALL MATERIAL SHALL BE FURNISHED AND WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST
REVISION AT&T MOBILITY GROUNDING STANDARD "TECHNICAL SPECIFICATION FOR CONSTRUCTION OF
GSM/GPRS WIRELESS SITES" AND "TECHNICAL SPECIFICATION FOR FACILITY GROUNDING". IN CASE OF A
CONFLICT BETWEEN THE CONSTRUCTION SPECIFICATION AND THE DRAWINGS, THE DRAWINGS SHALL GOVERN.
36. CONTRACTORS SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS AND INSPECTIONS REQUIRED FOR
CONSTRUCTION. IF CONTRACTOR CANNOT OBTAIN A PERMIT, THEY MUST NOTIFY THE GENERAL CONTRACTOR
IMMEDIATELY.
37. CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE SITE ON A DAILY BASIS.
38. INFORMATION SHOWN ON THESE DRAWINGS WAS OBTAINED FROM SITE VISITS AND/OR DRAWINGS PROVIDED
BY THE SITE OWNER. CONTRACTORS SHALL NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO
ORDERING MATERIAL OR PROCEEDING WITH CONSTRUCTION.
39. NO WHITE STROBE LIGHTS ARE PERMITTED. LIGHTING IF REQUIRED, WILL MEET FM STANDARDS AND
REQUIREMENTS.
40. ALL COAXIAL CABLE INSTALLATIONS TO FOLLOW MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
ANTENNA MOUNTING
41. DESIGN AND CONSTRUCTION OF ANTENNA SUPPORTS SHALL CONFORM TO CURRENT ANSI/TIA-222 OR
APPLICABLE LOCAL CODES.
42. ALL STEEL MATERIALS SHALL BE GALVANIZED AFTER FABRICATION IN ACCORDANCE WITH ASTM A123 "ZINC
(HOT-DIP GALVANIZED) COATINGS ON IRON AND STEEL PRODUCTS", UNLESS NOTED OTHERWISE.
43. ALL BOLTS, ANCHORS AND MISCELLANEOUS HARDWARE SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM
A153 "ZINC-COATING (HOT-DIP) ON IRON AND STEEL HARDWARE", UNLESS NOTED OTHERWISE.
44. DAMAGED GALVANIZED SURFACES SHALL BE REPAIRED BY COLD GALVANIZING IN ACCORDANCE WITH ASTM
A780.
45. ALL ANTENNA MOUNTS SHALL BE INSTALLED WITH LOCK NUTS, DOUBLE NUTS AND SHALL BE TORQUED TO
MANUFACTURER'S RECOMMENDATIONS.
46. CONTRACTOR SHALL INSTALL ANTENNA PER MANUFACTURER'S RECOMMENDATION FOR INSTALLATION AND
GROUNDING.
47. ALL UNUSED PORTS ON ANY ANTENNAS SHALL BE TERMINATED WITH A 50-0HM LOAD TO ENSURE
ANTENNAS PERFORM AS DESIGNED.
48. PRIOR TO SETTING ANTENNA AZIMUTHS AND DOWNTILTS, ANTENNA CONTRACTOR SHALL CHECK THE ANTENNA
MOUNT FOR TIGHTNESS AND ENSURE THAT THEY ARE PLUMB. ANTENNA AZIMUTHS SHALL BE SET FROM
TRUE NORTH AND BE ORIENTED WITHIN +/-5% AS DEFINED BY THE RFDS. ANTENNA DOWNTILTS SHALL BE
WITHIN +/-0.5% AS DEFINED BY THE RFDS. REFER TO ND-00246.
49. JUMPERS FROM THE TMA'S MUST TERMINATE TO OPPOSITE POLARIZATION'S IN EACH SECTOR.
50. CONTRACTOR SHALL RECORD THE SERIAL #, SECTOR, AND POSITION OF EACH ACTUATOR INSTALLED AT THE
ANTENNAS AND PROVIDE THE INFORMATION TO AT&T.
51. TMA'S SHALL BE MOUNTED ON PIPE DIRECTLY BEHIND ANTENNAS AS CLOSE TO ANTENNA AS FEASIBLE IN A
VERTICAL POSITION.
52. ANTENNAS SHALL HAVE A 4' -0" MIN CENTER TO CENTER HORIZONTAL SEPARATION.
TORQUE REQUIREMENTS
53. ALL RF CONNECTIONS SHALL BE TIGHTENED BY A TORQUE WRENCH.
54. ALL RF CONNECTIONS, GROUNDING HARDWARE AND ANTENNA HARDWARE SHALL HAVE A TORQUE MARK
INSTALLED IN A CONTINUOUS STRAIGHT LINE FROM BOTH SIDES OF THE CONNECTION.
A. RF CONNECTION BOTH SIDES OF THE CONNECTOR.
B. GROUNDING AND ANTENNA HARDWARE ON THE NUT SIDE STARTING FROM THE THREADS TO THE SOLID
SURFACE. EXAMPLE OF SOLID SURFACE: GROUND BAR, ANTENNA BRACKET METAL.
55. ALL 8M ANTENNA HARDWARE SHALL BE TIGHTENED TO 9 LB-FT (12 NM).
56. ALL 12M ANTENNA HARDWARE SHALL BE TIGHTENED TO 43 LB-FT (58 NM).
57. ALL GROUNDING HARDWARE SHALL BE TIGHTENED UNTIL THE LOCK WASHER COLLAPSES AND THE GROUNDING
HARDWARE IS NO LONGER LOOSE.
58. ALL DIN TYPE CONNECTIONS SHALL BE TIGHTENED TO 18-22 LB-FT (24.4 -29.8 NM).
59. ALL N TYPE CONNECTIONS SHALL BE TIGHTENED TO 15-20 LB-IN (1.7 -2.3 NM).
FIBER & POWER CABLE MOUNTING
60. THE FIBER OPTIC TRUNK CABLES SHALL BE INSTALLED INTO CONDUITS, CHANNEL CABLE TRAYS, OR CABLE
TRAY. WHEN INSTALLING FIBER OPTIC TRUNK CABLES INTO A CABLE TRAY SYSTEM, THEY SHALL BE
INSTALLED INTO AN INTER DUCT AND A PARTITION BARRIER SHALL BE INSTALLED BETWEEN THE 600 VOLT
CABLES AND THE INTER DUCT IN ORDER TO SEGREGATE CABLE TYPES. OPTIC FIBER TRUNK CABLES SHALL
HAVE APPROVED CABLE RESTRAINTS EVERY (60) SIXTY FEET AND SECURELY FASTENED TO THE CABLE TRAY
SYSTEM. NFPA 70 (NEC) ARTICLE 770 RULES SHALL APPLY.
61. THE TYPE TC-ER CABLES SHALL BE INSTALLED INTO CONDUITS, CHANNEL CABLE TRAYS, OR CABLE TRAY
AND SHALL BE SECURED AT INTERVALS NOT EXCEEDING (6) SIX FEET. AN EXCEPTION; WHERE TYPE TC-ER
CABLES ARE NOT SUBJECT TO PHYSICAL DAMAGE, CABLES SHALL BE PERMITTED TO MAKE A TRANSITION
BETWEEN CONDUITS, CHANNEL CABLE TRAYS, OR CABLE TRAY WHICH ARE SERVING UTILIZATION EQUIPMENT
OR DEVICES, A DISTANCE (6) SIX FEET SHALL NOT BE EXCEEDED WITHOUT CONTINUOUS SUPPORTING. NFPA
70 (NEC) ARTICLES 336 AND 392 RULES SHALL APPLY.
62. WHEN INSTALLING OPTIC FIBER TRUNK CABLES OR TYPE TC-ER CABLES INTO CONDUITS, NFPA 70 (NEC)
ARTICLE 300 RULES SHALL APPLY.
GENERAL CONSTRUCTION NOTES
COAXIAL CABLE NOTES
63. TYPES AND SIZES OF THE ANTENNA CABLE ARE BASED ON ESTIMATED LENGTHS. PRIOR TO ORDERING
CABLE, CONTRACTOR SHALL VERIFY ACTUAL LENGTH BASED ON CONSTRUCTION LAYOUT AND NOTIFY THE
PROJECT MANAGER IF ACTUAL LENGTHS EXCEED ESTIMATED LENGTHS.
62. CONTRACTOR SHALL VERIFY THE DOWN-TILT OF EACH ANTENNA WITH A DIGITAL LEVEL.
63. CONTRACTOR SHALL CONFIRM COAX COLOR CODING PRIOR TO CONSTRUCTION. REFER TO "ANTENNA SYSTEM
LABELING STANDARD" ND-00027 LATEST VERSION.
64. ALL JUMPERS TO THE ANTENNAS FROM THE MAIN TRANSMISSION LINE SHALL BE· 1/2" DIA. LDF AND SHALL
NOT EXCEED 6'-0".
65. ALL COAXIAL CABLE SHALL BE SECURED TO THE DESIGNED SUPPORT STRUCTURE, IN AN APPROVED
MANNER, AT DISTANCES NOT TO EXCEED 4' -0" OC.
66. CONTRACTOR SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS REGARDING BOTH THE INSTALLATION
AND GROUNDING OF ALL COAXIAL CABLES, CONNECTORS, ANTENNAS, AND ALL OTHER EQUIPMENT.
67. CONTRACTOR SHALL WEATHERPROOF ALL ANTENNA CONNECTORS WITH SELF AMALGAMATING TAPE.
WEATHERPROOFING SHALL BE COMPLETED IN STRICT ACCORDANCE WITH AT&T STANDARDS.
GENERAL CABLE AND EQUIPMENT NOTES
68. CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY ANTENNA, TMAS, DIPLEXERS, AND COAX CONFIGURATION,
MAKE AND MODELS PRIOR TO INSTALLATION.
69. ALL CONNECTIONS FOR HANGERS, SUPPORTS, BRACING, ETC. SHALL BE INSTALLED PER TOWER
MANUFACTURER'S RECOMMENDATIONS.
70. CONTRACTOR SHALL REFERENCE THE TOWER STRUCTURAL ANALYSIS/DESIGN DRAWINGS FOR DIRECTIONS ON
CABLE DISTRIBUTION/ROUTING.
71. ALL OUTDOOR RF CONNECTORS/CONNECTIONS SHALL BE WEATHERPROOFED, EXCEPT THE RET CONNECTORS,
USING BUTYL TAPE AFTER INSTALLATION AND FINAL CONNECTIONS ARE MADE. BUTYL TAPE SHALL HAVE A
MINIMUM OF ONE-HALF TAPE WIDTH OVERLAP ON EACH TURN AND EACH LAYER SHALL BE WRAPPED
THREE TIMES. WEATHERPROOFING SHALL BE SMOOTH WITHOUT BUCKLING. BUTYL BLEEDING IS NOT
ALLOWED.
72. IF REQUIRED TO PAINT ANTENNAS AND/OR COAX:
A. TEMPERATURE SHALL BE ABOVE so· F.
B. PAINT COLOR MUST BE APPROVED BY BUILDING OWNER/LANDLORD.
C. FOR REGULATED TOWERS, FM/FCC APPROVED PAINT IS REQUIRED.
D. DO NOT PAINT OVER COLOR CODING OR ON EQUIPMENT MODEL NUMBERS.
73. ALL CABLES SHALL BE GROUNDED WITH COAXIAL CABLE GROUND KITS. FOLLOW THE
MANUFACTURER'S RECOMMENDATIONS.
A. GROUNDING AT THE ANTENNA LEVEL.
B. GROUNDING AT MID LEVEL, TOWERS WHICH ARE OVER 200'-0", ADDITIONAL CABLE GROUNDING
REQUIRED.
C. GROUNDING AT BASE OF TOWER PRIOR TO TURNING HPR.IZONTAL.
D. GROUNDING OUTSIDE THE EQUIPMENT SHELTER AT ENTRY PORT.
E. GROUNDING INSIDE THE EQUIPMENT SHELTER AT THE ENTRY P,ORT.
74. ALL PROPOSED GROUND BAR DOWNLEADS ARE TQ ,BE TERMINATED _TO THE EXISTING ADJACENT GROUND
BAR DOWNLEADS A MINIMUM DISTANCE OF 4'-0" BELOW GROUND BAR. TERMINATIONS MAY BE EXOTHERMIC
OR COMPRESSION. ,
75. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE ANTENNA AND THE COAX CONFIGURATION IS
THE CORRECT MAKE AND MODELS, PRIOR TO INSTALLATION.
76. ALL CONNECTIONS FOR HANGERS, SUPPORTS, BRACING, ETC. SHALL BE INSTALLED PER TOWER
MANUFACTURER'S SPECIFICATION & RECOMMENDATIONS.
77. ANTENNA CONTRACTOR SHALL FURNISH AND INSTALL A 12'-0" T-BOOM SECTOR ANTENNA MOUNT, IF
APPLICABLE, INCLUDING ALL HARDWARE.
SAFETY ENFORCEMENT
SAFETY IS OF PARAMOUNT CONCERN TO BOTH SITE WORKERS AND THE PUBLIC.
1. CONSTRUCTION WORK PRESENTS UNIQUE THREATS TO HEALTH AND SAFETY. THE CONTRACTOR IS
RESPONSIBLE TO EDUCATE THEIR WORK FORCE OF THESE DANGERS AND LIMIT THEIR EXPOSURE TO
HAZARDS. THIS EDUCATION SHALL INCLUDE BUT NOT BE LIMITED TO APPLICABLE TRAINING COURSES AND
CERTIFICATIONS, PROPER PERSONAL PROTECTIVE EQUIPMENT USAGE, DAILY TAILGATE MEETINGS AND ANY
OTHER PREVENTATIVE MEASURES WHICH MAY BE REASONABLY EXPECTED. THE CONTRACTOR AND ALL
SUB-CONTRACTORS SHALL BE RESPONSIBLE FOR THE SAFETY OF THE WORK AREA, ADJACENT AREAS AND
ANY PROPERTY OCCUPANTS WHO MAY BE AFFECTED BY THE WORK UNDER CONTRACT. THE CONTRACTOR
SHALL REVIEW ALL LANDOWNER, PRIME CONTRACTOR, CARRIER, OSHA, AND LOCAL SAFETY GUIDELINES AND
AT ALL TIMES SHALL CONFORM TO THE MOST RESTRICTIVE OF THESE STANDARDS TO ENSURE A SAFE
WORKPLACE.
2. ALL SAFETY EQUIPMENT SHALL BE INSPECTED ACCORDING TO ALL OSHA AND INDUSTRY SCHEDULED
INTERVALS AND ALL INSPECTIONS SHALL BE DOCUMENTED PER APPLICABLE CODES AND STANDARDS.
3. TOWER WORK PRESENTS ADDITIONAL THREATS TO HEALTH AND SAFETY. ALL TOWER WORKERS WORKING ON
A TOWER MUST BE ADEQUATELY TRAINED AND MONITORED TO ENSURE THAT SAFE WORK PRACTICES ARE
LEARNED AND FOLLOWED. AS REQUIRED BY OSHA, WHEN WORKING ON EXISTING COMMUNICATION TOWERS
EMPLOYEES MUST BE PROVIDED WITH APPROPRIATE FALL PROTECTION, TRAINED TO USE THIS FALL '
PROTECTION PROPERLY, AND THE USE OF FALL PROTECTION MUST BE CONSISTENTLY SUPERVISED AND
ENFORCED BY THE CONTRACTOR.
4. ELECTRICAL WORK PRESENTS SPECIFIC THREATS TO THE HEALTH AND SAFETY OF WORKERS ON SITE.
SPECIFICALLY ELECTROCUTIONS ARE THE FOURTH LEADING CAUSE OF DEATH ON CONSTRUCTION SITES. ALL
ELECTRICAL WORKERS SHALL HAVE CURRENT CERTIFICATIONS WHICH SATISFY ALL TRAINING REQUIREMENTS
FOR THE ELECTRICAL WORK THEY ARE PERFORMING PER OSHA STANDARDS. ALL ELECTRICAL WORKERS
SHALL ADHERE TO ALL SAFETY RULES AND REGULATIONS FOR WORKER AND PUBLIC SAFETY. ALL WORK
SHALL BE PERFORMED BY QUALIFIED ELECTRICIANS TRAINED FOR THE TYPE OF WORK AND THE VOLTAGES
PRESENT FOR EACH TASK. THE CONTRACTOR SHALL REVIEW ALL LANDOWNER, PRIME CONTRACTOR,
CARRIER, OSHA, NFPA 70, AND LOCAL SAFETY GUIDELINES AND AT ALL TIMES SHALL CONFORM TO THE
MOST RESTRICTIVE OF THESE STANDARDS TO ENSURE A SAFE WORKPLACE.
1
at&t
mobility
·=·Ma sTe c
Network Solutions
IA:
GPDGROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
PROJECT NO: 2016723.04.11566.01
DRAWN BY: CJM
CHECKED BY: JG
8 09/13/16 REVISED PER CLIENT COMMENTS
A 07/29/16 ISSUED FOR REVIEW
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
LTE -STEALTH POLE
SHEET TITLE
GENERAL NOTES
SHEET NUMBER
GN-2
N
22"x34" SCALE: 1 /16" = 1 '-0"
11"x17" SCALE: 1 /32" = 1 '-o·
PROPOSED AT&T CONCEALMENT
POLE (SEE SHEET C-3 FOR
EXISTING PROPERTY
LINE (TYP.)
~ EXISTING PARKING LOT\
~ PARCEL #, 172305914-0 \
DETAILED ELEVATION PLAN) ____ _:,,"s:::""__::~;;:------JL-~~f
,,u,.,.
15· 12· a~ o" 16'
~ ~ ~~A
>i~
~
EXISTING AT&T EQUIPMENT
LOCATION (SEE SHEET
C-2 FOR DETAILED PLAN)
.t:
" I
" .t: ', I
" .t: '/.
.t:
~ ~ ~
~A
>i~
A"l
~
~PARCEL/, 1723059147\
~ EXISTING BUILDING\
~ '6.,_~
~A
>i~
~ ~ ~
~h
>i~
~ ~ ~ '(
~
EXISTING AT&T CABLES IN ~A
CABLE TRAY TO BE REMOVED y
FROM ROOFTOP (REUSE
EXISTING AS APPLICABLE) ~
}
I
t
I t
• -I
~
VICINITY MAP
t ~ !Ji..-lJ----';----'t-EXISTING AT&T ANTENNA
SECTORS & MOUNTS TO BE
REMOVED FROM ROOFTOP
(REUSE EXISTING EQUIPMENT
AS APPLICABLE)
PARCEL 1723059140 LEGAL DESCRIPTION
POR GL 8-BEG AT INTSN OF E LN WITH SLY MGN OF MAPLE
VALLEY HWY TH NWLY ALG HWY 167.48 FT TO TPOB TH S
01-14-13 W 117.96 FT TH N 56-43-47 W 201.14 FT TH N
33-16-13 E TO SLY MGN OF HWY TH TO TPOB LESS SR 169
OVERALL SITE PLAN 1
at&t
mobility
·=·r'I a sTe c
Network Solutions
~:
GPDGROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
PROJECT NO: 2016723.04.11566.01
DRAWN BY: CJM
CHECKED BY: JG
B 09/13/16 REVISED PER CLIENT COMMENTS
A 07/29/16 ISSUED FOR REVIEW
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
LTE -STEALTH POLE
SHEET TITLE
OVERALL SITE PLAN
SHEET NUMBER
C-1
NOV O 9 2016
"'---EXISTING PARKING LOT \
PROPOSED POLE LIGHT
CONDUITS TO BE ROUTED FROM EXISTING POWER
EQUIPMENT AREA TO NEW POLE FOR DISTRIBUTION BOX---.,.,,_
'\_ EXISTING RESTAURANT ,
PATIO AREA \
(4) PROPOSED AT&T
RRHs, STACKED AND
MOUNTED TO NEW
UNISTRUT ATTACHED TO
CHAIN LINK FENCE
PULL BOX LINK FENCE (lYP.)
• 'i'
N
/
(2) PROPOSED 6" UNDERGROUND
NEW EQUIPMENT CABLES -~
X
r EXISTING FIBER rEXISTING CHAIN
~ X X I X I X X --X---'-------.------------1----------1
~~ d ~ rr==,===i--l_ ____ _Jr=~~~~--==--9--,,--\---------, ,,,-,,,.,,.----PROPOSED AT&T
_,, ,,,--PURCELL CABINET x
--..---~r, / STACKED ON TOP
i--------------~---r----------------------+--~X X X
/
/
PROPOSED 59'-10 (30"0)
CONCEALMENT LIGHT POLE
• .,
I
°N
"'---EXISTING GRASSY AREA\
-
P/L P/L p• . . .
EXISTING RETAINING
WALL (lYP.)
22"x34" SCALE: 1 /2" = 1 '-o"
11 "x 1 7" SCALE: 1 / 4" = 1 '-o·
I
2·
P/L P/L p·
1' O" 2'
EXISTING
CONCRETE BOX
W/ ENTRY
EXISTING WOOD
TIE (TYP.)
. ' P" .
',
' ', ', ,, -----
X
X
X
-
X
-
\
X
t.------_--EXISTING STAIRS
EXISTING
GSM
CABINET
EXISTING
TE40
BATTERY
CABINET
L.
I
I
I
X X
u
EXISTING
TE43
LTE
EXISTING POWER
DISTRIBUTION
EXISTING CUTOFF
SWITCH
X VX\
\
X
EXISTING
FLX16
LTE
EXISTING
TE41
BATTERY
CABINET
l.1
EXISTING
UMTS
CABINET
X
'
X X
OF EXISTING LTE
CABINET
X
X
X
X
t
EXISTING AT&T CABLES IN
CABLE TRAY TO BE REMOVED
FROM ROOFTOP (REUSE
EXISTING AS APPLICABLE)
I
I
I
I
I
I
/ I
I I
-
X
I,---""----,-. EXISTING TELCO
PULL BOX
X ·1
--~----EXISTING TMAs r,.. 1 (lYP.)
I /
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
I I
-I I
X I I ~ '$,I/ I/
--------------------....! I /
-I X . I
r----l 1
~ ........_ ___ EXISTING
HOFFMAN BOX
X---X---X x---x--
P/L--P/L--P/L---P/L---P/L---P/L--\-rP/L---P/L--\,\_/l---P/L
P/L---P/L
\ 1
1\/l---P/L---P/L--P/L--P/L---P/L---P/L---P/L---P/L---I
H-FRAME \ EXISTING
'---------EXISTING GENERATOR
INTERFACE
"'---EXISTING PARKING LOT\
EXISTING PULL
BOX
P/L--'----P/L---P/L---1
.
EQUIPMENT LAYOUT 1
at&t
mobility
·=·MasTec
Network Solutions
~.
GPDGROUP
P1'0fessional Corporation
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330,572.2102
PROJECT NO: 2016723.04.11566.01
DRAWN BY: CJM
CHECKED BY: JG
8 09/13/16 REVISED PER CLIENT COMMENTS
A 07 /29/16 ISSUED FOR REVIEW
.... -&,, --
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
LTE -STEALTH POLE
SHEET TITLE
EQUIPMENT LAYOUT
SHEET NUMBER
NOTE:
PROPOSED CONCEALMENT POLE
TO BE PAINTED A MUTED COLOR
IN A NON-GLARE FINISH.
w
...J
0
D..
' ...J OW ~w
I f-. (/)
~LL
0
D..
0
f-
a:: w
f-z w u
0
' ~ st
I ..: inz
Ii) z w
f-z
<{
f-
~ !;;:
22"x34" SCALE: 1 /8" = 1 '-0"
11"x17" SCALE: 1 /16" = 1'-o· 8' 6' 4' 2 1 O"
a:: w
f-z w u
0
' ~ st
I ..: inZ stZ w
f-z
<{
f-
~
!;;:
C:
8'
. --------------PROPOSED AT&T PANEL ANTENNAS •
..-----------(TOTAL OF 4)
J-----------(8) NEW AT&T DIPLEXERS &
(4) RELOCATED FROM EXISTING
ROOFTOP EQUIPMENT
-MOUNTED BEHIND NEW AT&T PANEL
ANTENNAS
----PROPOSED 59'-10" (30"9))
CONCEALMENT LIGHT POLE
(LIGHT OFFSET ON OPPOSITE
SIDE OF POLE)
-----PROPOSED CABLES TO ~ BE ROUTED IN NEW
~ CONCEALMENT POLE
-----PROPOSED POLE LIGHT
~~-PROPOSED CABLES TO BE
ROUTED IN (2) NEW 6"
CONDUITS TO POLE
r--EXISTING EQUIPMENT
AREA
Ir--EXISTING BUILDING
PROPOSED SOUTH ELEVATION 2
IN ACCORDANCE WITH RF DATA SHEET DATED JUNE 6, 2016 VERSION 3.0
RF DATA SHEET NOTE
1. TYPES AND SIZES OF THE ANTENNA CABLE ARE BASED ON ESTIMATED
LENGTHS. PRIOR TO
3
ORDERING CABLE, CONTRACTOR SHALL VERIFY ACTUAL LENGTH BASED ON
CONSTRUCTION
LAYOUT AND NOTIFY THE PROJECT MANAGER IF ACTUAL LENGTHS EXCEED
ESTIMATED LENGTHS.
2. CONTRACTOR SHALL VERIFY THE DOWN-TILT OF EACH ANTENNA WITH A
DIGITAL LEVEL.
3. CONTRACTOR TO CONFIRM COAX COLOR CODING PRIOR TO CONSTRUCTION.
REFER TO "ANTENNA
SYSTEM LABELING STANDARD" ND-00027, REFER TO THE LATEST
VERSION.
4. ALL JUMPERS TO THE ANTENNAS FROM THE MAIN TRANSMISSION LINE
WILL BE 1 /2" DIA. LDF AND
SHALL NOT EXCEED 6' -0".
5. ALL COAXIAL CABLE WILL BE SECURED TO THE DESIGNED SUPPORT
STRUCTURE, IN AN APPROVED MANNER, AT DISTANCES NOT TO EXCEED
4'-o" oc.
6. CONTRACTOR MUST FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS
REGARDING BOTH THE INSTALLATION AND GROUNDING OF ALL COAXIAL
CABLES, CONNECTORS, ANTENNAS, AND ALL OTHER EQUIPMENT.
7. WEATHERPROOF ALL ANTENNA CONNECTORS WITH SELF AMALGAMATING
TAPE. WEATHERPROOFING SHALL BE COMPLETED IN STRICT ACCORDANCE
WITH AT&T STANDARDS.
8. CONTRACTOR SHALL GROUND ALL EQUIPMENT. INCLUDING ANTENNAS, RET
MOTORS, TMA'S, COAX CABLES, AND RET CONTROL CABLES AS A
COMPLETE SYSTEM. GROUNDING SHALL BE EXECUTED BY QUALIFIED
WIREMEN IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION AND
RECOMMENDATION.
9. CONTRACTOR SHALL PROVIDE STRAIN-RELIEF AND CABLE SUPPORTS FOR
ALL CABLE ASSEMBLIES, COAX CABLES, AND RET CONTROL CABLES.
CABLE STRAIN-RELIEFS AND CABLE SUPPORTS SHALL BE APPROVED FOR
THE PURPOSE. INSTALLATION SHALL BE IN ACCORDANCE WITH
MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.
10. CONTRACTOR TO VERIFY THAT EXISTING COAX HANGERS ARE STACKABLE
SNAP IN HANGERS. IF EXISTING'.HANGERS ARE NOT STACKABLE SNAP IN
HANGERS THE CONTRACTOR SH-4,LL REPLACE EXISTING HANGERS WITH NEW
SNAP IN HANGERS IF APPLICABLE.
COAXIAL ANTENNA CABLE NOTES 4
NOT USED 5
at&t
mobility
·=-~asTec
Network Solutions
~:
GPDGROUP
Professional Corporation
520 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 330.572.2102
PROJECT NO: 2016723.04.11566.01
DRAWN BY: CJM
CHECKED BY: JG
B 09/13/16 REVISED PER CLIENT COMMENTS
A 07/29/16 ISSUED FOR REVIEW
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
LTE -STEALTH POLE
SHEET TITLE
SOUTH TOWER ELEVATION
SHEET NUMBER
C-3
,)r·c··c" 1···r . l'\.t°: ...,Cl\, i":~L
NOV O 9 ZOiti
NOTE:
PROPOSEO CONCEALMENT POLE
TO BE PAINTED A MUTED COLOR
IN A NON-GLARE FINISH.
,,--EXISTING BUILDING
,---EXISTING RESTAURANT
PATIO
u.J
....J
0 a..
• ....J
Ou.I ~w
I I-
-Ul
0)
I() u...
0
a..
0 I-
a::
u.J I-z
u.J
0
Cl
<( • a:: "<I"
I <C
ioZ
I() G:i a::
u.J I-I-z z
<( u.J
~ 0
Cl ~ <( ':st a::
I <C ioZ
"<I" z
u.J I-z
<(
I-
.;>I
~
I
.-----PROPOSED AT&T PANEL ANTENNAS. ~ (TOTAL OF 4)
l---~--------(8) NEW AT&T DIPLEXERS & -+ (4) RELOCATED FROM EXISTING
ROOFTOP EQUIPMENT
-MOUNTED BEHIND NEW AT&T PANEL
ANTENNAS
-
-----------PROPOSED 59'-10" (30"¢) CONCEALMENT LIGHT POLE
(LIGHT OFFSET ON OPPOSITE
~
SIDE OF POLE)
----PROPOSED CABLES TO
I ~ BE ROUTED IN NEW
. ~ CONCEALMENT POLE
----PROPOSED POLE LIGHT
I
-----------------__ ----~CL._L--'-'----'-'~~L L--L~~-LL-~-c_ --··----'---'~~•-~-~~-'-+-+-'-'----~-~--~---~--------------·--------··----L~~--'-----------
1
22"x34" SCALE: 1 /8" = 1 '-o·
11 "x1 7" SCALE: 1 /16" = 1'-0"
I"' ..... -LLW 8' 6' 4' 2· O" 8'
~-PROPOSED CABLES TO BE
ROUTED IN (2) NEW 6"
CONDUITS TO POLE
PROPOSED NORTH ELEVATION 2
IN ACCORDANCE WITH RF DATA SHEET DATED JUNE 6, 2016 VERSION . 3.0
RF DATA SHEET NOTE
1. TYPES AND SIZES OF THE ANTENNA CABLE ARE BASED ON ESTIMATED
LENGTHS. PRIOR TO
3
ORDERING CABLE, CONTRACTOR SHALL VERIFY ACTUAL LENGTH BASED ON
CONSTRUCTION
LAYOUT AND NOTIFY THE PROJECT MANAGER IF ACTUAL LENGTHS EXCEED
ESTIMATED LENGTHS.
2. CONTRACTOR SHALL VERIFY THE DOWN-TILT OF EACH ANTENNA WITH A
DIGITAL LEVEL.
3. CONTRACTOR TO CONFIRM COAX COLOR CODING PRIOR TO CONSTRUCTION.
REFER TO "ANTENNA
SYSTEM LABELING STANDARD" ND-00027, REFER TO THE LATEST
VERSION.
4. ALL JUMPERS TO THE ANTENNAS FROM THE MAIN TRANSMISSION LINE
WILL BE 1/2" DIA. LDF AND
SHALL NOT EXCEED 6' -0".
5. ALL COAXIAL CABLE WILL BE SECURED TO THE DESIGNED SUPPORT
STRUCTURE, IN AN APPROVED MANNER, AT DISTANCES NOT TO EXCEED
4'-0" oc.
6. CONTRACTOR MUST FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS
REGARDING BOTH THE INSTALLATION AND GROUNDING OF ALL COAXIAL
CABLES, CONNECTORS, ANTENNAS, AND ALL OTHER EQUIPMENT.
7. WEATHERPROOF ALL ANTENNA CONNECTORS WITH SELF AMALGAMATING
TAPE. WEATHERPROOFING SHALL BE COMPLETED IN STRICT ACCORDANCE
WITH AT&T STANDARDS.
8. CONTRACTOR SHALL GROUND ALL EQUIPMENT. INCLUDING ANTENNAS, RET
MOTORS, TMA'S, COAX CABLES, AND RET CONTROL CABLES AS A
COMPLETE SYSTEM. GROUNDING SHALL BE EXECUTED BY QUALIFIED
WIREMEN IN COMPLIANCE WITH MANUFACTURER 'S SPECIFICATION AND
RECOMMENDATION.
9. CONTRACTOR SHALL PROVIDE STRAIN-RELIEF AND CABLE SUPPORTS FOR
ALL CABLE ASSEMBLIES, COAX CABLES, AND RET CONTROL CABLES .
CABLE STRAIN-RELIEFS AND CABLE SUPPORTS SHALL BE APPROVED FOR
THE PURPOSE. INSTALLATION SHALL BE IN ACCORDANCE WITH
MANUFACTURER'S SPECIFICATIONS AND RECOMMENDATIONS.
1 0. CONTRACTOR TO VERIFY THAT EXISTING COAX HANGERS ARE STACKABLE
SNAP IN HANGERS. IF EXISTING HANGERS ARE NOT STACKABLE SNAP IN
HANGERS THE .CONTRACTOR SHALL REPLACE EXISTING HANGERS WITH NEW
SNAP IN HANGERS IF APPLICABLE.
COAXIAL ANTENNA CABLE NOTES 4
NOT USED 5
at&t
mobility
·=·Ma sTe c
Network Solutions
A ~--..~
GPDGROUP
Professional Coiporation
52 0 South Main Street, Suite 2531
Akron, OH 44311
330.572.2100 Fax: 33 0.572 .2102
PROJECT NO: 2016723 .04.11566 .01
DRAWN BY: CJM
CHECKED BY: JG
B 09/13/16 REVISED PER CLIENT COMMENTS
A 07 /29/16 ISSUED FOR REVIEW
-----
IT IS A VIOLATION Of LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
Of A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
CEDAR RIVER
10030930 ·
2439 SE MAPLE VALLEY HWY
RENTON, WA 98055
L TE -STEAL TH POLE
SHEET TITLE
NORTH TOWER ELEVATION
SHEET NUMBER
f~ECE IV E1
)
C-4 NOV O \l 20\6