HomeMy WebLinkAboutHitone Kuehnienz Short PlattQ King County Department of Development and Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-1219 Engineering Review Comments Project Type: 6 Lots Short Plat Review Date: 12/31/2008 Reviewer Name: Mazen Haidar, P.E. Project Name : Hitone Short Plat Review No.: 2nd Email : mazen.haidar@kingcounty.gov Project Number : L04S0065 Phone : (206) 296 -7133 Activity Number L07SR019 Fax: (206) 296 -6613 Project Manager: Pete Dye, P.E. Sub Item Item Sheet 1 1 2 3 4 5 6 Code Review Comments Reference In the approval block on the Cover Sheet as well as other plan sheets. please change the Development Engineer name to show Molly A. Johnson, P.E. (see redline markuns) Please remover your stamp expiration date Please provide actual signature on your stamp, signature copies will not be accepted, and your stamp must reflect your registration number very clearly 'currentlv hard to read) As previousely requested, please provide the United States Postal Services (USPS) approval stamp and signature on plans for mailboxes location and show box standard detail on olans As previousely requested please show all of the short plat conditions of approval, this is not shown on sheet 1 O as vou mentioned in vour resoonses The sheets index makes a reference to sheets 2 & 3 that are missing from the plans set, please provide ~rn@rnowrn@ JUN 3 02009 KC. D.D.E.S. Page 1 of 8 Consultant Response Date: Name: This has been changed to Mark X. Plog. PE. PLS This has been revised to have the hand written exoiration date as reouired This has been corrected Detail has been added and plans have been submitted to postmaster for approval. Approval will be provided with next submittal. The conditions of approval have been added to the plan set and are found on sheet C 1 The plan set has been completely revised and the index has been updated to reflect the new plan set sheets. Complete IY/Nl Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: N/NI New Sheet 1 As previousely requested, please provide Horizontal The Horizontal Control Plan has been incorprated into Control Plan sheet, on this sheet show the proposed the new plan set as requested. short plat layouts with proposed access road, show lot lines, tract lines, easement lines, access road centerline, with complete survey information (bearing, distance, and curve information). This plans sheet needs to be consistent the preliminary short plat map. Also, on this sheet show section and quarters monumnet and section ties information Sheet4 1 Please show interceptor swales and sediment trap The interceptor swales and sediment traps have been with section details to control surface flows druing indicated and a construction sequence has been construction acitivites. On this sheet please show the provided. construction senuence notes 2 As previously requested please show the correct This has been corrected plans approval block on the plans sheets (see redline markun\ 3 As previously requested, please make sure all texts This has been corrected sizes are adequate and clearly read, also please check your plans to eliminate all text overlaping. 4 Please show existing utility poles to be relocated per The utility pole relocation has been indicated the 1993 King County Road Standards (KCRS) Sheet 5 1 Please show the on-site access centerline station and This has been provided ROW station in nrofile view 2 Show 120th road name and road classification in bold This has been provided font Page 2 of 8 Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: fY/NI 3 As previously requested please add the following note This note has been added. on the plans sheet: Per KCRS Section 4.01F, a 1 inch full width overlay shall be required. Appropriate repairs to the existing subgrade, base material, surfacing and pre-level may be required prior to placing the overlay. The overlay may be waived only upon written request and after an evaluation of pavement conditions and/or channelization requirements has been completed and approved by the County Road Engineer or Development Engineer. 4 As previously requested, please show turning radii This has been provided edge of pavement for the on-site access approach at 16-feet from 120th ROW centerline (see redline markuos) 5 There at least 100-feet of the required paved walkway The walkway has been widened where adjacent to the not being separated by ditch from the travel lane, this existing roadway. portion of the walkway shall be 5-feet wide, pleas address this issue properly (see redlines) 6 Please show sidewalk to shoulder transition ramp with This has been provided with a callout. standard detail !see redlines\ Sheet 6 1 Please show walkay improvement end station in This has been provided. orofile 2 Please revise plans to show new fence installation This has been indicated on the plans. within orivate oronertv instead of KC ROW Sheet 7 1 Please show the proposed storm drain sturctures This has been provided. such catch basins and manholes information in plan and profile views. Please show CB number, stations, stations off-set, rim elevation, pipe invert elevations, pipe size, pipe direction, and pipe type (please show this information in the format shown in red on plans) 2 As previously requested, it is improtant that all of your Flow arrows have been provided. plan sheets clearly show the directional flow arrows for all storm drain pipes, please clearly show Page 3 of 8 Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: IY/NI 3 Please remove the water and sanitary sewer Left as background only imorovements from all plan sheets. 4 In profile view , please label all pipes & road design The slopes have been labeled nrade slooes as S = slope Sheets 8 & 9 1 Strom system information shown on these plan The storm system has been simplified to eliminate the sheets are unclear and very confusing. Please show flow splitter and to provide a combined flow directional arrows for all pipes, unless there is treatment/detention vault as suggested. specific reason why wetvault and detention vault cannot be combined, the plans shall be revised to show one Combined Wet-RD Vault system. Also, flow splitter is not needed for this project, plans shall be revised to show one vault system to treat and control flows consistent with the 1998 King County Surface Water Design Manual (KCSWDM) guidlines. 2 Please revise the profile design to show one This has been provided. combined profile, this can be easly accomplished on the plan sheet. Show complete structure information as shown in red on clans. 3 Plans must be revised to elinimate all text This has been done. overlannino this shall be done on Plan sheets 4 As previously requested, the proposed spreader The spreader has been previously approved as part system will not be accepted because it will allow of the COA. sheet flow over adjacente property roadways (private or public), please revise plans to show tight line instead Page 4 of 8 Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: IY/NI 5 As previously requested, please submit easement This easement has been provided for review. documentation for proposed strom easement for review bv Kina Countv 6 Provide section details to show adequate information Pipe crossings have been eliminated on the new plan at pipe corssings, and make sure that at least 1.0' set. seoaration is orovided between oines 7 Please revise your plans to eliminate many of the This has been done. storm by-pass pipes, and keep in mind that all impervious surfaces including but not limited to on- site roof tops must all be routed to one on-site Combined Wet-RID vault system, this can be easly accomnlished so olease nrovide. 8 Clearly show limits of proposed landscape tract This has been done. encumbering drainage easement to King County for the orooosed vault svstem 9 Clearly identify the location of the control structure, This has been done. show maintenance access to this structure, and show removable bollard at the access entrance with standard details 10 Please provide separate profile design for the The bypass has been eliminated orooosed bv-oass svstem 11 Show S'X 1 O' maintenance access opening for the This has been provided. second cell of the wetvault 12 Show gravity drain line with valve for the proposed There is not sufficient fall to provide a drain for the wetvault. see section 6 in the 1998 KCSWDM wetvault. 13 Show footing drains for the vault system(s) and show This has been provided its downstream discharge location in plan and section views TIR 1 All hand written calculations must be legible and very The TIR has been revised and no hand calculations clear to read, this is critical because the TIR are included. document will be microfilmed eventually and hand written information cannot be read if it is not clear in the original document, please print or legibly write all calculations Page 5 of 8 Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: IV/NI 2 Please check your area calculations for the The TIR areas and calculations have been completely developed conditions, hand written calculations revised. information is not consistent with information provided for peak flow calculations. Also there should be no pasture ground cover in the developed conditions area calculations, please revise accordingly 3 In TIR please place all your area calculations ahead The TIR has been revised to a more traditional of the RID desian calculations. format. 4 Since frontage road improvments are not routed to The design and calculations have been revised to the proposed on-site RID facilities, By-pass eliminate the bypass. calculations shall be included in the vault design calculations. This was considered in the previous submittal and need to be included in the revised TIR, please revise all of the RID system design Mlcula•ions as ne.,ded 5 Also, please re-arrange the program print out sheet The TIR has been revised to a more traditional sequencs, it appears mixed up and very confusing format. 6 Please note that the vault design calculations are The revised vault calculations and design have been based on 130' long X 1 O' wide X 1 O' deep structure updated to coordinate. resulting in 13,000 c.f. of live storage, however the required peak reservior storage volume is 13,138 c.f., please revise your calculations to make sure that live storage volume is equal to or greater than the peak reservior volume, see redlines 7 As previously requested, please show all of the short This has been provided. i plat conditions of annroval in Tl R 8 Please revise the wetvault design calculations to This has been provided. include impervious surface areas for proposed roof toPS in the develoned conditions 9 Include By-pass area calculations and By-pass peak Bypass has been removed flow calculations 10 Provide actual computer print out for the facility This has been provided performance curve instead of nrint screen 11 Please provide sediment trap design calculations in This has been provided TIR Page 6 of 8 Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: IV/NI 12 Please provide standard size for the engineer stamp This has been provided in TIR, show acutal signature (signature copy will be accepted), and remove the exipration date from the stamo 13 Please revise the bond calculations as needed The calculations have been revised. General 1 Please provide written agreement from adjacent The owner will provide this documentation as soon as property owner to the south for work associated with possible. grading and clearing improvements, such as fence relocation 2 Please provide easement documentation for This has been provided proposed downstream drainage system for County review 3 Please provide separate landscape plans with This has been provided under separate cover by the separate application for review, please submit as owner. soon as nossible. 4 Provide wetland report for adjacent wetland to the This wetland is exempt per the COA. east, and show wetland buffer and BSBL lines on all related nlan sheets 5 Provide 3 copies of Structural Plans and calculations Vault structural plans will be provided once the TIR for the proposed storm water vaults calculations have been reviewed and approved by the drainane reviewer. 6 Please show street plans A separate road plan has been added 7 Please provide 4 copies of separate Significant Trees A Tree Retention Plan has been provided as part of th Retention Plans olan set. 8 Please refere to plans and TIR redline markups and This has been done. revise accordinalv 9 Please submit 3 set of revised plans and TIR for This has been done. further review by the County along with all plans and TIR review redline markuos 10 Please provide list of responses to this list of review This has been done. comments, and indicate how, and where (on what sheet\ each item has been addressed 11 Prior to your next submttal please make sure all items Noted. listed are properly, adequately and completely addressed, this will help completing review with approved budget, otherwise additional fees payment may be needed if exceeded budget hours Page 7 of 8 Sub Code Review Comments Consultant Response Date: Complete Item Item Reference Name: IV/NI 12 Please call me if you have any questions and lets Thanks!!! discuss all issues before resubmittal, I will be happy to assist Page 8 of8 ti KingCounty Department of Development and Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-1219 Date: December 31, 2008 .I ennifer L. Argrades, P .E. North Cascades Engineering, P. 0. Box 309 Winthrop, WA 98862 RE: Hitone Short Plat L04S0065,L07SR019 Dear Mrs. Argrades, Our office has completed the Second review of engineering plans for the Hi tone Short Plat. The attached list of review comments dated December 31, 2008 provides summary of design issues which must be addressed in your next submittal. The review comments are based upon the design plans and technical information report received on December 17 and 29, 2008. Once the second review comments have been addressed, please submit 4 sets of revised plans and technical reports. To assist in reviewing the revised plans, the design engineer should prepare a written response for each issue identified in the attached comments .. If you desire an electronic copy ofmy review comments, please send an email to mazen.haidar@kingcounty.gov. If you have questions regarding the design requirements for the project, please contact me at 206-296-7133 for assistance. ~;,g Mazen Haidar, P.E. Review Engineer Enclosure cc: Mr. Anthony Ford, Owner I 1--~---'-.,--i R-6 <i t-----1 "" ..., ..., LL .c: __J:c----1--, n R-6 ! \ \ \ I \ ' I ----\ f ' ' ,, Ji I _ \I ~L _/ _ ' : 1--------\ ' :I----~ ' ' .c: Hitone L07SR019 NTrails l Schools/School Facilities NTownshiplines S-T-R , n ,, • QSLINES ~SECLlNES TWPUNES N"""" SAOS!ream M,1 ~~ N> ,",:u ~ SAOWel!and(199B) ' Watsr Bodies D Road Righ~-Way CJ""" o-r--Forest(< 20 aaes) Greon""' Forest/Designate '""""""' Ag./No Dev. Rights O::nvnercial o.s. o- CJ""" 0 200 400 Feet 1"=417feel t&1 KllleCountJ rt.inkrmalion inc::ludod an a. map 11M -~ by King Co.tty' a1llt'I from • nnflly.,, _ -ia ~ to change .. lhout nobce. King c...nty m&u no -~.,,_...,_.,__...-rnplied,atolh!I ...,,.....,,_.......,..___ ~.ornglbtoll"e.-of tu<:h inl,;rmatian. King Coi.ny .,.... not be bble !of .-.y --'· opecial, indired. lncldenlal. ot~ --ircl.dng, tulnatlirMo<I to. losl-ct losl profits ru~ting from Iha UM or m, .... of the information ~ on lt'Q map. My .... of 11,ia map ct infcnnaticn an Iha map ia f:fd-...:1 ucep1 t,y ...,u., pennioaicn of '""" Plot elate: Aug 4, 2009; l'dcie$001\idl1'viS\4Y_dev\projeds\base2..ai:,r V ti King County Department of Development and Environmental Services 900 Oakesdale Avenue Southwest Renton, WA 98057-5212 · 206•296-6600 -lTY 206-296-721-7 www.metrokc.gov November 20, 2008. Steven Wade Terrell Terrell Design Group 923 NW SO'h Street Seattle, WA 98107 RE: Recreation Plan, KC File L08MI051 Hitone (a.k.a Yee) Short Subdivision KC Files L04S0065 Dear Mr. Terrell: I have reviewed the recreation and landscaping plan dated July 24, 2008 and have the following comments: 1. Please show the dimensions and area calculation for the combined drainage and recreation tract. Please note that at a minimum, 2,340 square feet shall be allocated for recreation. The grass-paved driveway to access the drainage vault cannot be included within the required area. The area allocated for recreation could include landscaping buffers. No dimension of the recreation tract can be less than 30 feet. 2. At a minimum a 400-square-foot tot lot area must be provided. The proposed 215-foot toddler area (sand box) is inadequate and does not meet the code. In addition to the tot lot area, one additional recreation facility must be provided per KCC 21A.14.180.E2. A pull bar as the only recreation structure does not meet the code requirement. A basketball court or a picnic area with tables and a large grassy area for throwing a baseball or Frisbee may be acceptable for a recreation facility. 3. Please show fencing around the entire perimeter of the tract except the street side. The fencing along the boundary of the tract and Lot 6 may be 4-feet high and see-through. 4. Landscaping notes must include the type and method of irrigation. 5. The proposed improvements must not conflict with the engineering requirements for the drainage facility or its maintenance. Normal maintenance includes I . • •• driving heavy equipment up to the access point, opening vault access points and lowering equipment into the vault to remove sediments. Please show the vault access points for maintenance and any other drainage related structures that will be part of the recreation tract. Please submit the following by December 22, 2008: L 2. 3. 4. 5 copies ofa revised final-recreation plan, addressing the-items referred-above 5 copies of a revised Bound Quantity Worksheet for the landscaping and other improvements 5 copies of play equipment and recreation tract furnishings specifications A copy of this memo If you have any questions regarding this letter, please contact me at (206) 296-7173. Sincerely, '-:)-~l?~ Fereshteh Dehkordi, Project Manager Current Planning Section Cc: Antony Ford, Applicant Lanny Henoch, Project Manager III Angelica Velasquez, PPM II Mazan Haidar, Engineer, Engineering Review Section L07SR019 File ti King County Department of Development and Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-1219 Engineering Review Comments Project Type: 6 lots Short Plat RevieviDate: 12/31/2008 Reviewer Name: Maien Haidar; P.E. ,. < ., ,_ • • • • '. '" • Project Name : Hitone Short Plat R11~ie,y.' No.: 2nd Email : mazen.haidar@kingcounty.gov Project Number : L04S0065 Phone : (206) 296 -7133 Activity Number: L07SR019 . · F.ax: (206)296 -6613 Project Manager: Pete Qye; P.E. ' . .~ -------· •. ____ ,•=.:_ ., .. ,._., ..•.• Sub Code ·. Review .. Comments ConsultanfResponse Date: · Item Item Reference Name: Sheet 1 1 In the approval block on the Cover Sheet as well as other plan sheets, please change the Development Engineer name to show Molly A. Johnson, P.E. (see redline markuos) 2 Please remover vour stamp exoiration date 3 Please provide actual signature on your stamp, signature copies will not be accepted, and your stamp must reflect your registration number very clearly 'currentlv hard to read\ 4 As previousely requested, please provide the United States Postal Services (USPS) approval stamp and signature on plans for mailboxes location and show box standard detail on "lans 5 As previousely requested please show all of the short plat conditions of approval, this is not shown on sheet 1 O as vou mentioned in vour resconses 6 The sheets index makes a reference to sheets .2 & 3 that are missing from the plans set, please provide Page 1 of 8 Complete IV/NI .. Si.lb Code Review Comments ... ~~~"~!,t~nt,Response Date: .. •·· .· :: ',~/,!\:· Completet Item Item Reference .. ame:· ·-, -, :r.i1N{)i New Sheet 1 As previousely requested, please provide Horizontal Control Plan sheet, on this sheet show the proposed short plat layouts with proposed access road, show lot lines, tract lines, easement lines, access road centerline, with complete survey information (bearing, distance, and curve information). This plans sheet needs to be consistent the preliminary short plat map. Also, on this sheet show section and quarters monumnet and section ties information Sheet 4 1 Please show interceptor swales and sediment trap with section details to control surface flows druing construction acitivites. On this sheet please show the construction seauence notes 2 As previously requested please show the correct plans approval block on the plans sheets (see redline markuc) 3 As previously requested, please make sure all texts sizes are adequate and clearly read, also please check your plans to eliminate all text overlaping. 4 Please show existing utility poles to be relocated per the 1993 King County Road Standards (KCRS) Sheet 5 1 Please show the on-site access centerline station and ROW station in profile view 2 Show 120th road name and road classification in bold font Page 2 of 8 Sub Code ' ·:· · .. ' ,._ Review Comments CorisultantResponse·Date: . . _'(' . :> Complete· Item Item Reference ' . : .: ._ ._;,.,' Name: .. IY/NI' e. "'· •• 3 As previously requested please add the following note on the plans sheet: Per KCRS Section 4.01F, a 1 inch full width overlay shall be required. Appropriate repairs to the existing subgrade, base material, surfacing and pre-level may be required prior to placing the overlay. The overlay may be waived only upon written request and after an evaluation of pavement conditions and/or channelization requirements has been completed and approved by the County Road Engineer or Development Engineer. 4 As previously requested, please show turning radii edge of pavement for the on-site access approach at 16-feet from 120th ROW centerline (see redline markuos) 5 There at least 100-feet of the required paved walkway not being separated by ditch from the travel lane, this portion of the walkway shall be 5-feet wide, pleas address this issue properly (see redlines) 6 Please show sidewalk to shoulder transition ramp with standard detail (see redlines\ Sheet 6 1 Please show walkay improvement end station in nrofile 2 Please revise plans to show new fence installation within orivate orooertv instead of KC ROW Sheet 7 1 Please show the proposed storm drain sturctures such catch basins and manholes information in plan and profile views. Please show CB number, stations, stations off-set, rim elevation, pipe invert elevations, pipe size, pipe direction, and pipe type (please show this information in the format shown in red on plans) 2 As previously requested, it is improtant that all of your plan sheets clearly show the directional flow arrows for all storm drain pipes, please clearly show Page 3 of 8 Sub Code Review ComlTleilts ConsultaritRespo11se Date: ... ::··j'>;'' ' Complete· . . . . ' . Item Item Reference Name: ·· · · IV/NI .. · 3 Please remove the water and sanitary sewer imorovements from all olan sheets. 4 In profile view , please label all pipes & road design nrade slooes as S = slooe Sheets 8 & 9 1 Strom system information shown on these plan sheets are unclear and very confusing. Please show flow directional arrows for all pipes, unless there is specific reason why wetvault and detention vault cannot be combined, the plans shall be revised to show one Combined Wet-RD Vault system. Also, flow splitter is not needed for this project, plans shall be revised to show one vault system to treat and control flows consistent with the 1998 King County Surface Water Design Manual (KCSWDM) guidlines. 2 Please revise the profile design to show one combined profile, this can be easly accomplished on the plan sheet. Show complete structure information as shown in red on nlans. 3 Plans must be revised to elinimate all text overlanninn this shall be done on olan sheets 4 As previously requested, the proposed spreader system will not be accepted because it will allow sheet flow over adjai:ente property roadways (private or public), please revise plans to show tight line instead Page4 of 8 Sub · Code Review Comments Cons.liltant Response Date: .. Complete Item Item Reference Name: IY/Nl 5 As previously requested, please submit easement documentation for proposed strom easement for review bv Kinn Countv 6 Provide section details to show adequate information at pipe corssings, and make sure that at least 1.0' seoaration is orovided between oioes 7 Please revise your plans to eliminate many of the storm by-pass pipes, and keep in mind that all impervious surfaces including but not limited to on- site roof tops must all be routed to one on-site Combined Wet-RID vault system, this can be easly accomnlished so olease orovide. 8 Clearly show limits of proposed landscape tract encumbering drainage easement to King County for the orooosed vault svstem 9 Clearly identify the location of the control structure, show maintenance access to this structure, and show removable bollard at the access entrance with standard details 10 Please provide separate profile design for the nronosed bv-nass svstem 11 Show 5'X10' maintenance access opening for the second cell of the wetvault 12 Show gravity drain line with valve for the proposed wetvault, see section 6 in the 1998 KCSWDM 13 Show footing drains for the vault system(s) and show its downstream discharge location in plan and section views TIR 1 All hand written calculations must be legible and very clear to read, this is critical because the TIR document will be microfilmed eventually and hand written information cannot be read if it is not clear in the original document, please print or legibly write all calculations Page 5 of 8 Sub' Code I .. Review. Comments Consultant,ResponseDate: ' --< • --.~-: Complete Item Item Reference -' Name: .. ;·. ·.·} IY/N\ 2 Please check your area calculations for the developed conditions, hand written calculations information is not consistent with information provided for peak flow calculations. Also there should be no pasture ground cover in the developed conditions area calculations, please revise accordingly 3 In TIR please place all your area calculations ahead of the RID desion calculations. 4 Since frontage road improvments are not routed to the proposed on-site RID facilities, By-pass calculations shall be included in the vault design calculations. This was considered in the previous submittal and need to be included in the revised TIR, please revise all of the RID system design calculations as needed 5 Also, please re-arrange the program print out sheet sequencs, it appears mixed up and very confusing 6 Please note that the vault design calculations are based on 130' long X 1 O' wide X 1 O' deep structure resulting in 13,000 c.f. of live storage, however the required peak reservior storage volume is 13,138 c.f., please revise your calculations to make sure that live storage volume is equal to or greater than the peak reservior volume, see red lines 7 As previously requested, please show all of the short olat conditions of annroval in TIR 8 Please revise the wetvault design calculations to include impervious surface areas for proposed roof toos in the develooed conditions 9 Include By-pass area calculations and By-pass peak flow calculations 10 Provide actual computer print out for the facility nerformance curve instead of orint screen 11 Please provide sediment trap design calculations in TIR Page 6 of 8 Sub Code · Review Comments . ,' .. , ·~'. ·: .. " Co['sultant.Response Datil:"\«··· . ' ,Complete Item -Item Reference . Name: . . . . · ·:: IV/NI 12 Please provide standard size for the engineer stamp in TIR, show acutal signature (signature copy will be accepted), and remove the exipration date from the stamn 13 Please revise the bond calculations as needed General 1 Please provide written agreement from adjacent property owner to the south for work associated with grading and clearing improvements, such as fence relocation 2 Please provide easement documentation for proposed downstream drainage system for County ' review 3 Please provide separate landscape plans with separate application for review, please s_ubmit as soon as nossible. 4 Provide wetland report for adjacent wetland to the east, and show wetland buffer and BSBL lines on all related nlan sheets 5 Provide 3 copies of Structural Plans and calculations for the nrooosed storm water vaults 6 Please show street plans 7 Please provide 4 copies of separate Significant Trees Retention Plans 8 Please refere to plans and TIR redline markups and revise accordinalv 9 Please submit 3 set of revised plans and TIR for further review by the County along with all plans and TIR review redline markuns 10 Please provide list of responses to this list of review comments, and indicate how, and where (on what sheet\ each item has been addressed 11 Prior to your next submttal please make sure all items listed are properly, adequately and completely addressed, this will help completing review with approved budget, otherwise additional fees payment may be needed if exceeded budget hours Page 7 of8 Sub Code ·. ·.~ Review Comments ~onsultant Response Date: .•S-· ! complete Item Item Reference . ,. . Name: . tv/Nl 12 Please call me if you have any questions and lets discuss all issues before resubmittal, I will be happy to assist Page 8 of 8 ' .. •. ' ... Dye, Pete From: North Cascades Engineering, PLLC [sukoargr@methow.com] Sent: Monday, May 07, 2007 2:11 PM To: Dye, Pete Cc: Tony Subject: [Spam) Hitone Short Plat -Engineering Activity# L07SR019 Hello Peter, Page 1 of2 Thank you for your time today to discuss the Hitone Short Plat letter dated April 27, 2007. The following outlines some of our correspondence with the County including timeline, used as the basis of our design. This is an attempt to respond to your statements included in the Hitone Short Plat letter dated April 27, 2007. Items 7, 8 and 9: Plan Revision for change in stonn drainage, stonn drainage easements on lots, and downstream drainage: The original Short Plat showed a detention tank and underground treatment facility. In late November of ,2007, we found the downstream conveyance system would not be completed at the time of our engineering review. So, for the Owner to proceed with his project an above ground system was designed per King County's 1998 standards. We contacted the County to see if we could place the detention_and water quality in a SD easement over a residential lot. It is our understanding from the 1998 King County Manual the detention pond must be in a dedicated Tract ifit is to be maintainedby the County. Thus, if this is a privately maintained facility it would not have to be in a Tract. We spoke with Kate Roads (206-296-8046) on 12-12-06 and discussed several options for storm drainage system. She stated the County prefers all SD to be in one tract but SD easements on lots are allowable. She also stated the system we design must function as a complete system now. The owner, at a future date when the downstream conveyance system is available, will potentially put the detention and WQ below ground, thus reclaiming the lot area the SD easement currently occupies. So, the system we designed is a stand alone system. Short Plat Condition 4, part D, states we would have to submit a revision to the application with a new conceptual drainage plan. We contacted the County again to see how to proceed. We did not know if the revision was a formal Revision or exactly what we were required to do. We first contacted Freeshteh Dehkordi in late November she referred us to Curt Foster. Curt was unsure and was going to check with someone else in his office. He said a formal Revision is normally needed when the number of lots change. ~ e still had 6 lots _with Lot 5 partially impacted and Lot 6 completely impacted by the storm drainage.) He called back and referred us on to Kim Clauson (206-296-7167). We spoke with Kim Clauson on 12-06-06. She said to submit extra copies of our plans to engineering and they would let us know if additional information was necessary. She did not think a formal Revision would be required. Item 10: No road access to SD oudet: This will be included when the plans are re-submitted. Item 11: Cul-de-sac design does not meet Kf3'Sliii1dards: We coordinated with Chris Langly (206-296-7155 or 206h63-61'0~oh several occasions (10-30-06, 10-31-06 and 12-12-06) to determine the road and cul-de~sac desigh elrments. I\-re island the only design standard we are not meeting? An island is not required for this r~ad classification. We pilt it in as a WQ element. The required changes will be included when the plans are re-sub1niit!~di ) . • '\ l, ·, l \ . ._J. Thank you for working through this process with us. Plet?r:?rll me-at 509-996;;2252 1f you have any questtons, 05/07/2007 . ( ) • need additional information, or when you determine how we need to proceed. Sincerely Jennifer Jennifer Argraves, PE Principal/ Civil Engineer North Cascades Engineering, PLLC PO Box 309 Winthrop, WA 98862 509-996-2252 206-669.-5792 cell 05/07/2007 i ' . ' _,J Page 2 of2 • ® King County Department of Development and Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-1219 April 27, 2007 Heidi Kuehnienz 413 South 4 7'11 Street Renton, WA 98055 RE: Permit Fee Estimate Project: I-litone Short Plat Engineering Activity: L07SROI 9 Dear Applicant: .,. Thank you for submitting the engineering plans for site development of the I-Ii tone short plat. To implement the engineering review process, our office will use a new procedure for managing the permit application to provide applicants with an enhanced level of customer service. A project manager will be assigned to your project to provide a fee estimate for the anticipated scope of review and will also monitor and manage the permit application throughout the review process. Your application for engineering review was received by our office on March 30, 2007 and will be processed using the Project Manager Program. The enclosed information provides a summary of the fee estimate for the anticipated work disciplines and also discusses the submittal process and disclaimers which may affect the final permit fees. The fee estimate includes the scope of work for engineering plan review only and does not evaluate other final plat requirements such as construction inspection and review of plat recording documents. During our initial screening process of the engineering plans, it was determined that the short plat has been significantly changed since preliminary approval and the designs are not acceptable for engineering review. The original short plat proposed a detention vault located beneath the roadway and recreation tract; however, the current design shows a storm pond and bioswales located within the lot areas which does not meet County design requirements. In addition, several other design requirements for roads and drainage do not meet County standards. The design items identified during the screening process which do not comply with County standards are listed as disclaimers on the attached fee estimate form. Due to the missing information, the fee summary is a rough estimate and is subject to modification based upon the disclaimers noted in the fee estimate form. Heidi Kuehnienz April 27, 2007 Page 2 Before continued review of the engineering submittal, the site plans must be revised to correspond with the original design concept for the preliminary short plat or an application for short plat revision must be submitted to the planning section in our office. The short plat revision is also noted as arequirement in short plat condition 4 regarding the offsite drainage pipe which is not addressed on the current design plans. Please contact the project planner Fereshteh Dehkordi at 206-296-7173 to discuss the requirements for a short plat revision. The short plat revision must be processed before any further review of the engineering designs. In addition to engineering design documents, our Department must also review and approve the recreation space plan as required by short plat condition 13. Please be aware that the recreation plan must be submitted to our planning section as a separate permit application with fee payment. The requirements for submitting recreation plans may also be discussed with Fereshteh Dehkordi at 206-296-7173. Our current records for the short plat do not list your name as the original applicant. If the property has changed ownership, the enclosed Transfer of Applicant Status Form (CASF) must be provided in your next submittal. Once the attached fee estimate form is signed and submitted to our Department along with the estimated fee payment, applicant status form, and revised engineering plans, your project will be assigned for further review. All fee payments shall be made to the cashier in the DOES permit center using activity number L07SROl 9 and other forms or plan documents shall be submitted to my attention in the Land Use Services Division. If you have any questions regarding the permit fees or other aspects of the engineering review process, please contact the project manager, Pete Dye via email pete.dye@metrokc.gov or by telephone at 206-296-7185. sffJ Peter D-t:.E. Senior Engineer Enclosure cc: Jennifer Argraves (® King County Land Use Services Division Permit Fee Estimate Pre-app Estimate Number: L07SR019 Date: 04/27/07 Permit Title: Hitone Short Plat Permit Type: SITEREVS -Engineering Plan · Based on permit information submitted by the applicant, the Department of Development and Environmental Services (ODES) has determined the amount of review fees for the subject application.· The fees shown below do not include ancillary permit fees, recording fees, project-related mitigation fees, or other fees that are passed through to the.applicant from other agencies or as part of the project's environmental review. Fixed Fees: Counter Service Fee for Application Intake Tree Retention Review Structural Review (Fees determined before plan approval) Other Fixed Fees Estimate for Hourly Fees: (] 53 Hours x $144.90) Fee Deposit Paid Total Fixed Fees: Total Permit Fee Estimate: $205.28 1,086.75 $ $1,292.03 $22,169.70 -$784.88 $22,676.85 Note: The estimate for hourly fees stated above is based on the total estimated number of hours not to exceed 153 hours for the disciplines listed below, and is calculated using the department's hourly rate in effect at the time the work is performed. Based upon the financial disclosures found on page 2, the number of hours required may be modified. The total estimated hours reflect work performed by the following disciplines: Engineering Review, Survey Coordination, Project Management, Constructabi!ity, Traffic Review, Planning, and Geotechnical Review. After receiving the fee estimate from ODES, the applicant has ninety (90) days to complete the application submittal. Please call 206-296-6797 to set up an appointment with the Permit Center to complete your application and payment. If the application is not received within ninety (90) days, the applicant may be required to obtain a new fee estimate or this activity may be cancelled. For further questions on this fee estimate or for other requirements about this permit application, please contact Pete Dye via email pete.dye@metrokc.gov or by telephone at 206-296-7185. Peter Dye, P. E. Senior Engineer Land Use Services Division Project Manager.dot 1/26/04 Page I .. . . ' @ King County Land Use Services Division Permit Fee Estimate Engineering Activity No.: L07SR019 Date: 4/27/07 Permit Title: Hitone Short Plat Permit Type: SITEREVS -Engineering Plan Estimated Maximum Hours:153 Applicant: Heidi Kuehnienz Total Fee: $22,676.85 The following d1scla11ners are attached and are part of the fee estimate for this permit. The appltcant is required to submit a signed copy of this form with the application and fee payment acknowledging that. the applicant has read the disclaimers stated below. · Disclaimer Applicants are responsible for all fixed fees, reported hours performed in reviewing submittal materials and processing, up to the fee estimate. Changes in the scope of the project review will result in a revised review fee estimate. Fee estimates are based on information submitted to DOES by the applicant prior to finalization of the permit application. In addition, estimates are determined by utilizing historical data gathered from projects of similar type, size, and scope. The fee estimate will be the maximum fee charged unless the scope of the project changes. Should fewer hours be required to complete the review, then the applicant may receive a refund for those hours. If items are identified that are not originally disclosed or identified later in the process, a new estimate may be required. Applicants will be responsible for any additional hours identified in a new estimate because of: I) Changes in the project and unknown or undisclosed site issues. 2) Incomplete information or errors in applicant submittal. 3) County code fee changes. 4) Fees for Forest Practices Permit if determined necessary. 5) Fees for variance applications and/or structural permit review. 6) More than one major and one minor set ofredline corrections. 7) Short Plat Condition 4 -Downstream drainage issues not resolved. 8) Drainage facilities must be removed from lot areas. 9) Short Plat Revision required to address modified drainage designs. l 0) Road access not provided to drainage outlet structure. 11) Cul-de-sac design does not meet design standards in KCRS 2.08. Keeping review fees at or below the fee estimate will depend on the applicant's commitment to complete the process review. This commitment should include submitting materials which address · all County codes, policies, previously approved conditions, and responding to the County's request for corrections or additional information in a timely manner, not to exceed 90 days. Acknowledged: Applicant/Owner Name (print) Date: ___ Applicant/Owner Name (signature) Project Manager.dot 1/26/04 Page 2 -· ~ tQ KingCounty Department of Development And Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-5212 206-296-6600 TIY 206-296-7217 www.kingcounty.gov ' ~rn@rn~wrn@ OFr. 't. Y 7008 K.C. D.D.E.S. Engineering Plans Review Comments Project Type : Pr6ject N~me : . 6 Lots Shoi:tPlat · Review .. Oatei: · 12-27-2007 Reviev.ier-'Name : ;Maze~ l:laida( R:E:, ; ·.· . Hitone SP Y. · Revi~:;_. No. l / . 1 s Emailfr·'} •·.. · · ,'•.maien:h~ictar@rrietrokc.gov . . Pr6j!icfNiJmber : Xtfi;ify'Nuinber: L04S0Q65/i > '' ' Ph&ne.: : . . (206f296; 7J;3_3;\\ . L07S80l9 '. . . ~~,e;} ·i'.). (206) 206'}..f:l6l3i;,; :.: ' .,-'-:~ .:.:,-:<!:::·· I; ',, ' ', ' .. ·' ; \>. \),, '. , ... I· Sub o: < . R~flil''!nce · . Review c&nimerits . · Consultant Response• ,·. · Back Item Check Item· · · · _·":/}:~f.-r:.-.:-:?::_f,~-;~_--• .;_... . ~ .. .. '-. . ·-:: . ; .. ~-: . ' ' ;, .•.. <·-_'.· " Sheet-1 1 Please show the short plat conditions of approval ~vvEv To s\-1-£1:.:r lo, 2 Provide parcels information on plan ~\:>VE-D 'y~~C.E. \.. N \) t,/'\ 01:-i. ~ . 3 Show soils map for th~ subject site ':)01\..~ N'\~7 1>s.roso. 4 Show the United States Postal Services Approval stamp and signature for mailboxes location, show mailboxes on f\uu.=0, '::, C. t=-S 1-t E:. E.:, 8 P,.,.-M O I \ plans with standard detail 5 Label sheet as cover sheet \'\E-1'.lf'\),('-.,e-v sr1sET. Sheet-2 1 Please show north arrow and scale =:> £ £ 'h iz..v I <-,,1.-Q 5 L,) il.. \/ I:. '( 3 Show and label utility easement /I I I If 4 Please make sure all text fonts are large enough to read I( I( I I 5 This sheet should reflect existing site conditions, shouid I I show existing site features and parcel boundaries, and I{ 1/ section / ouarters monument ties, etc. ~. Sheet 1 of 6 ....... ~ ' ' ' King County Department of Development And Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-5212 206-296-6600 TIY 206-296-7217 www.kingcounty,gov ' Sub Reference Item · Item ' Sheet-3 1 2 3 4 5 6 7 8 9 10 Sheet. 4 1 2 ' ; ,t ' ·. Revi~w Comments Please make sure the engineer stamp is clearly readable on all plan sheets Please show the County plans approval block on all plan sheets except the cover sheet, see redline markup Show and identify all off-site easements, show easement type and width Use four digits for centerline stationing Le. 15+00 instead of 15 Please avoid text all overlapping on all plan sheets Show and label drainage facilities within public drainage easement, the drainage easement should be located in a Recreation Tract ' Clearly label and identify new grade lines (contour lines) Combine the road, drainage and grading improvements on one plan sheet Show complete Cul-De-Sac centerline information, see redline markups Show north arrow and scale on plan · Please re.move proposed improvements from this plan sheet, show TESC measures, Re-label construction dispersion trench as Interceptor Trench and show its location on plan Sheet 2 of 6 S f Yt<~ 1 (t:: ' .... ,. f. •· ... · Back . ,,._,:: . · Consultant Response Check ' ,' ~Sc R i'a." I';;, •'i-0 "b u.,.:,J '=-'i ( S,-5, ~ J"A(Y,' x \\ \ \ \ , ' I \ I ,, ' \ I \ ' I i\ ,, ,, ' I I I', I I \( \ I I \ ' H I I, I I '. I I l I ' \ . " I I I ! \ \ I \ t I ' ' I I l IV\ ?Ro" E.N\ c 1-\ '1 S V, c iAov s 'v :[ N 1E:.,,i,(.,,2.-r,o R., 1i\,o,,'\(,,I,\-SU N,.I ),\~~, ',t. ;::,__ -~-. . :t{' ~'; King County Department of Development And Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-5212 206-296-6600 nv 206-296-1211 www.kingcounty.gov Sub Reference Item Item 2 3 Sheet -5 1 2 3 4 5 Sheet-6 1 2 > Review Comments Please provide written agreement from adjacent property owner to the south for work associated with grading and clearing improvements, such as fence relocation It is unclear what type of off-site drainage improvements are you proposing, on sheet you show dispersal trench but on another you show tight line connection, this is- very confusing, please make sure all sheets show consistent improvement and provide complete information with standard details for our review Please show all existing driveways on the south side of 120'" and show how the new walkway improvement imnact each existino drivewav Show proposed finished grade lines for improvements in 120th .. Please revise the walkway cross section to show 2% cross slope The profile grid shown on this sheet is blank; please provide complete information as needed. Please revise proposed shoulder improvements in 120'" to 5' shoulder width Please extend and wrap the walkway improvement at 120111 intersection as shown in red on plans, provide section for the shoulder improvement at this location and show pavement radii setback at 16-feet from ROW centerline Please show the drainage improvements in plan and profile designs and show complete design information, and show flow direction arrows in olan views Sheet 3 of 6 . Back Consultant Response Check p,. Gi iLi2.<2-M.a.\\. ,~ \ N C..\..v0~D IN " ,, s iZ..y'J'n"l.f'n'z.. 7~\<.i\b~ U'R.l.~ C-i¥:.e-r/l ~'\~- '('L.?,1'1.'6 'R,,l.\/1 s,1.-P , o 'S,(+,,....; f, {;) wr L 11-lfz. C.o>l"' e..c..,10,-( -.o Di'r'( U Gtf'f' -r'o ,::. Lo 'v-( p ,s 1'"""~'°'--1 ..,.IZ-,'!..,'1.0,I . S ;;.,z. yt_..i\rN. "-.l+,~ff JI: l'-.'-\D \ I • \)Id ,sµ.o..,.,,.., w( Sr"-.-~Ui-1/ • °Pl'fT>I ( ,i..-,..\Ti'{\\..,~lG. ~~N1 PP·t~lt?o' lz.L-i 'J, ~ (l. J I'? r,_,{.:) f,'f..~ '-I· ~A->n-1 "i" ~ c.. \-\(I,,!, 1.. ,..,, ~ 1. ,1 e "'c.. o~ I0·5o-ob ~ ZDb-z_c,1 "71S'S 1Z-~v' \ '::> n..o ~i1..-116•~ I . \ ;,,,;::__ B.3ifil ~ KingCounty Department of Development And Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-5212 206-296-6600 TTY 206-296-7217 www.kingcounty.gov Sub Reference Item Item 3 Sheet-7 1 2 3 4 5 Sheet-8 1 ) 2 3 Sheet-9 1 Back RevieviComments Consultant Response ' Check Please provide complete information in the road profile design to make sure landing crtteria is fully met per I '>-I Pen"\..~ A-'n "1'i_ ~~,W . KCRS Provide more information for the by-pass trench such as I '-1 'P""-""-,YTI ut-\ ~ ~'~~ length width and show in drainage easement Please show the drainage improvements in plan and }.-.S .::> ~ profile designs and show complete design information, and show flow direction arrows in olan views Pleas provide complete information for proposed drainage improvements off-site, use either direct tight line connection or spreader system, and provide documentation for off-site drainaae easement p,.-D u ;;,,(.) Please replace grade breaks in the road profile with \<._v-J1"'.:,1~ vertical curves and show complete design information Show individual storm stub-outs with complete ?>,.-\)7'>~ information for each lot Show profile design for the vault and provide complete "'~,J I~ \1.-P design information in the vault detail as show in red Show the vaults in public drainage easements within recreation tract, show limits of tract and easement <Sae. -. i2 J'r,:.,T "? I.. r'l"'t\ -':> ~?, ':, ii.'1';. Show maintenance access to control structure '::>~~, Revise the proposed road sections to include ~izV•'='~ ?•~ c..,-..\v~l'L<:.P.1"1,r-1. w,Tt+ information shown in red on olans . ,. M Pl~i;.." >ri. 1>-,?~i\. ... l'"'I '-I. 1<i-o"b, Sheet 4 of 6 :--.. R~f11 ~ King County Department of Development And Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-5212 206-296-6600 TTY 206-296-7217 www.kingcounty.gov Sub Reference Item Item T.I.R. 1 < 2 3 4 General 1 2 3 ·• . Review Comments -. Please revise the peak flow calculations and the RID design calculations based on 50% of existing pervious surface consideration + pasture or forested for the remainder of the site area in the pre-developed conditions. - Revise the RID calculations based on actual stage O elevation as shown on plans Provi_de compete and detailed downstream analysis in TIR and include basin maps as needed Provide bond quantities calculations work sheet in Tl R The Landscape plans requires separate application for review, please submit;as soon as possible. Provide wetland report for adjacent wetland to the east Provide Structural Plans and calculations for the proposed storm water vaults Sheet 5 of 6 '-Back Consultant Response '.· Check - F,. l',.,,J I '? i l-v-> ~ i',,,,-,.J ,'::,, ... ..{) ~ .~ •'?(1..D P...·D {)~.-c:> Sv?,M~, L (:,., ?vA,-1.<:, ~3{'-?~ ~ S'tl" ~ (,.,ii ,S.;z.c_it-.\ b -'R ~ .. i'A,,.J, ),>l'.:) .. L ""''-'-V ~ ,i,.;-, ,.,._ ~ "':. ~·Ul.. l)TI\.' V r, .. .1 c"\ lo • ~ . . . King County Department of Development And Environmental Services 900 Oakesdale Avenue SW Renton, WA 98055-5212 206-296-6600 TIY 206-296-7217 www.kingcounty.gov Sub Reference Item Item 4 5 Review Comments '·' ' Add the following note.on the plans: Per KCRS Section 4. 01 F, a 1 inch full width overlay shall be required. Appropriate repairs to the existing subgrade, base material, surfacing and pre-level may be required prior to placing the overlay. The overlay may be waived only upon written request and after an evaluation of pavement conditions and/or channelization requirements has been completed and approved by the County Road Engineer or Development Enaineer. Please submit 3 set of revised plans and TIR for further review by the County along with all plans and TIR review redline markuos .. Sheet6 of 6 ' C_onsultant Response Back ~heck I I I I )'\,:,, f'; i:)u r,; P -? ,'l,o ~ iU)I'"" ' YO~<, N.OT M "v, 'f-'-\ a t . I z o "i1"I-, K (',. w ~ i>,-"!"-~ )~ ~~· 'P1\.c tM,.. ~~ 1' ;z e,.> .J' "l:> ,7,_.0 •---· Web date: 10/10/2005 ® King County Department of Development and Environmental Services Land Use Services Division ENGINEERING REVIEW CHECKLIST 1998 Surface Water Design Manual 1993 King County Road Standards 900 Oakesdale Avenue Southwest Renton, WA 98055-1219 206-296-6600 TIY 206-296-7217 For alternate formats, call 206-296-6600. PROJECT INFORMATION Pmject Nam, 1~ \'\\kE~N,,lf fXZ Act1v1ty Number ~~ Project Number Development Number ODES Review Engineer Date Notes OK D Hearing Examiner's Report ........ Date Revised Report ...... Date ------- 0 Plat Ordinance Number Date D Preliminary Plat Map .......... Date Approved by Hearing Examiner D Revised Preliminary Plat Map ....... Date Approved by ODES D 5-year Expiration ....... Date ------~---(Show on engineering cover sheet) ROUTING'TO OTHER KING COUNTY SECTIONS OK D Wetland Report/ Plans ,. Route Date Response Date D Geotechnical Report/ Plans Route Date Response Date D Grading Report / Plans Route Date Response Date D Structural Designs I Calculations/ Civil Plans/ Soils Report (Vaults, Retaining Walls, Bridges) Route Date Response Date ___________ _ D Landscape / Recreation I Street Tree I Plan Route Date ------------Response Date ------------ EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 1 of 16 Activity Number: ------------- (Continued) D Traffic Improvement Plan / Report Route Date ___________ _ Response Date ____________ _ D Tree Retention I Forestry I Plan Route Date ___________ _ Response Date ------------- D Other Report I Plan Route Date ___________ _ Response date ------------- D All required routing stations shown and updated on PRMS Notes GENERAL SUBDIVISION REQUIREMENTS D Site plan layout matches preliminary plat approved by Hearing Examiner (Check for same lot count, tract configuration, road alignments, etc.) D Compliance with conditions of preliminary approval D Compliance with Mitigated Determination of Non-Significance D Tract Table if three or more tracts. Identify name, size and purpose. D Show and label all SAO tracts, buffers, and 15' BSBL. D Review maximum height of 6-feet for rockeries and retaining walls per KCC 21A.12.030, 110-170, 220) Also show standard note per policy on Web site. D Use updated cover sheet showing designation for highly critical sites per Appendix, D44. D Determine if HPA fisheries permit required -contact CAO staff. D Tree Retention Plans -Show standard plan note (see section policies). SURFACE WATER DESIGN MANUAL (1998) CORE AND SPECIAL REQUIREMENTS OK SWDM D 1.2.1 D 1.2.2 D 1.2.3 D 1.2.6 D 1.2.8 D 1.3.1 D 1.3.2 Core #1 -Evaluate diversion of drainage within subbasins and/or tightline requirements for landslide hazard drainage areas. Core #2 -Off-site analysis. Evaluate adequacy and conclusions. Core #3 -Flow control. Determine design standard based upon mapping and/or off-site analysis. Evaluate exemptions from flow control if applicable. Core #6 -All drainage facilities and road access shall be located in public tracts, right-of-way and/or drainage easements dedicated to King County. For private facilities, specify the required Declaration of Covenant and drainage easements for final recording. Core #8 -Water Quality. Determine design standard based upon mapping and/or off-site analysis. Evaluate exemptions if applicable and untreated areas per page 1-57. Special #1 -Area specific requirements. Perform P-suffix search on computer, evaluate grading code restrictions, and review for shared facility drainage plan. Special #2 -Floodplain boundaries shown on plans. EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 2 of 16 ~/ Activity Number: ------------- DRAINAGE VARIANCES OK SWDM D 1.4 Activity No. _________ Approval Date Design lssue.;,.s _____________________________ ---. TECHNICAL INFORMATION REPORT OK SWDM D 2.3.1.1 D D D D D D D D D D D D D D D D D D 0 D D D 0 D D D D D Section 1 -Project Overview Figure 1: TIR Worksheet Figure 2: Site Location Figure 3: Drainage Basins a. Acreage of subbasins b. Identify all site characteristics c. Show existing discharge points to and from the site d. Show routes of existing, construction, and future flows at all discharge points and downstream hydraulic structures. e. Use a minimum USGS 1 :2400 topographic map as a base f. Show and cite the length of travel from the farthest upstream end of a proposed storm system in the development to any proposed flow control facility. Figure 4: Soils a. Show the project site b. The area draining to the site c. The drainage system downstream for the distance of the downstream analysis Section 2 -Preliminary Conditions Summary with responses Section 3 -Off-Site Analysis Section 4 -Flow Control and Water Quality Facility Analysis and Design Existing Site Hydrology (Part A) Developed Site Hydrology (Part B) Performance Standards (Part C) Flow Control System (Part D) Water Quality System (Part E) Section 5 -Conveyance System Design and Analysis Section 6 -Special Reports and Studies -Geo, Wetlands, Floodplain analysis (4.4.2) Section 7 -Other Permits (HPA, Special Use, WSDOT, etc.) Section 8 -Erosion / Sedimentation Control Design Section 9 -Bond Quantities Worksheet and RID Facility Summary Section 10 -Maintenance and Operations Manual (Section 10 for privately maintained or special non-standard features EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 3 of 16 './ Activity Number: ------------- SITE IMPROVEMENT PLANS OK SWDM D 2.3.1.2 D Vertical Datum NAVO 1988 -show benchmark D Horizontal Control NAO 1983/91 D 2.3.1.2 General Plan Format (1) Sheet size 24" x 36"; quality reproducibles (2) King Co. Standard Map Symbols; existing / proposed (Reference 7 A) (3) Project Information I Cover Sheet a. Title: Project name and DOES file number b. Table of Contents if more than 3 plan sheets c. Vicinity Map D D D D D D D d. Name & Phone of Utility field contacts and One Call Number: 1-800-424-5555 (water, sewer, D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D gas, power) e. Preconstruction / Inspection notification requirements f. Name & Phone of erosion control supervisor g. Name & Phone of Surveyor h. Name & Phone of Owner/ Agent i. Name & Phone of Applicant j. Legal description k. Plan approval block for ODES I. Name & Phone of engineering firm preparing plans m. Fire Marshal's approval stamp (if required) n. Mailbox location approval by U.S. Postal Service o. List of conditions of preliminary approval on all site improvements (4) An overall site plan if more than three plan sheets are used a. The complete property area development b. Right-of-way information c. Street names and road classification d. All project phasing and proposed division boundaries e. All natural and proposed drainage collection and conveyance systems with catch basin numbers shown (5) Each sheet and TIR is stamped, signed, and dated by a Professional Engineer licensed in Washington State (6) Detail Sheets Provided (7) Title block on each sheet a. Development title b. Name, address and phone number of engineering firm c. Revision block d. Page numbering e. Sheet title (e.g., road and drainage, grading, etc.) (8) King County approval block on each plan sheet (9) The location and label for each section or other detail shall be provided (10) Critical Area Setbacks per K.C.C. 21A.24 (11) All match lines correspond to the sheet reference (12) Division phase lines with limits of construction (13) Standard Plan Notes -General, Drainage & Structural notes (Reference 78) (14) Survey control plan sheet stamped by licensed PLS in Washington State EngineeringReviewCheck.listFORM.doc le-ckl-ercheck. pdf 10/10/2005 4 of 16 Activity Number: ------------- SITE IMPROVEMENT PLANS tcontlnuedl OK SWDM D 2.3.1.2 Plan View: Site Plan and Roadway Elements (1) Property Lines, R/VV lines, roadway widths shown D D (2) Existing/ Proposed road features; CL, edge pavement, edge shoulder, ditches, curb, sidewalk & D D D D D D access pis (3) Existing/ Proposed topographic contours@ 2', 5'>15% slope, 10-'>40% slope (4) All affected utilities are shown; utility poles marked (5) All roads and adjoining subdivisions identified (6) Existing / Proposed R/VV dimensioned and shown (7) Existing / Proposed surfacing shown (8) Scale generally 1"':50' (1"=100' for lots >1 Acre) D 2.3.1.2 Plan View: Drainage Conveyance D D D D D D Sequentially number all catch basins and curb inlets Show length, diameter, and material for all pipes, culverts, and stubouts Label catch basin size and type Show stubout locations for roof drains Label all drainage easements, access easements, tracts, and building setbacks Provide flow arrows for drainage direction D 2.3.1.2 Plan View: Other Show all buildings, property lines, streets, alleys, and easements Verify condition of public right-of-way Show structures on abutting properties within 50 feet Identify fencing for drainage facilities Provide section details of all retaining walls and rockeries D D D D D D Show all wells on-site and within 100-feet of site. For well abandonment, include notes referencing DOE procedures. D 2.3.1.2 Profiles: Roadway and Drainage D D D D D D D D D D D Existing / proposed roadway centerline (CL) at 50' stations increasing, reading from left to right. Show stationing of points of smooth vertical curve, with elevations Show vertical curve data including stopping sight distance Show all pipes and detention tanks with slope, length, size and type Show all pipe inverts and elevations of catch basins or lids Minimum cover dimensions if less than 2.0' Indicate roadway stationing and offset for all catchbasins Show vertical and horizontal scales (vertical 1 "=5') Label all profiles with street names and reference numbers to plan sheet Show all property boundaries and match line locations Provide profiles for conveyance systems of 12" and larger pipes or channels other than roadway ditches Catch basin lids are flush with ground line EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 5 of 16 Activity Number: -------------SITE IMPROVEMENT PLANS fconUnuedl OK SWDM D 2.3.1.2 Plan Details D D D D D D D D D D D D Provide scale drawing of each pond, vault, or water quality facility. Include all pipe details for size, type, slope, length, etc. Show existing and final grade contours at 2-foot intervals. Show maximum design water elevation. Dimension all berm widths Provide two cross sections through pond, including one section through restrictor Specify soils and compaction requirements Show location and detail of emergency overflows, spillways, and bypasses Specify rock protection I energy dissipation details Provide inverts for all pipes, grates, etc., and spot elevations on pond bottom Show location of access roads to control manholes and pond / forebay bottoms Provide plan and section views of all energy dissipaters. Specify size and thickness of rock. Show bollard locations (Typically at entrance to drainage facility and walking trails) Restrictor and control structures must have section and plan view drawn to scale D 2.3.1.2 Structural Plan Details D Verify that designer is a licensed structural P.E. for vaults or bridges Notes: EROSION AND SEDIMENT CONTROL (SWDM Appendix Dl OK D D D D D D D D D D D D D D D D SWDM 2.3.1.3 0.4.1 General Specifications Separate plan sheet showing entire site w/features Show critical areas and buffers in separate tracts Show existing contours and final grades if scope or work includes grading Pertinent information from soils report is added to plans Drainage features identified (streams, wetlands, bogs, springs, seeps, swales, ditches, pipes & depressions) Utility corridors other than roads shown Show drainage divides and flow directions Specify best management practices Show cut and fill slopes with catch lines indicated Sufficient conceptual details to convey design intent Standard ESC plan notes shown on plans (Page D-69) For grading and structural fill within lot areas -show standard notes for geo hazards (see section policies for geo notes) Clearing Limits (1) Delineate clearing limits -colored survey tape may be used. Critical areas require plastic/ metal safety fence or stake and wire fences. (2) Provide detail of fencing EngineeringReviewChecklistFORM.doc le-ck.1-ercheck.pdf 10/10/2005 6 of 16 Activity Number: ------------- 2.3.1.3 EROSION AND SEDIMENT CONTROL ISWDM Appendix Dl !continued) OK SWDM 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D.4.2 D.4.3 D.4.4 D.4.5 D.4.6 Cover Measures (1) Specify the type and location of temporary and permanent cover measures. (Mulch, erosion control nets, blankets, plastic, seeding and sodding) (2) Specify the seed mixes, fertilizers and soil amendments to be used and application rates (3) Areas receiving special treatment are specified Qute netting, rock lining or sod) (4) Soil cover practices and locations of disturbed areas Perimeter Protection (1) Specify the location and type of perimeter protection to be used -silt fence, brush barriers, and/or vegetated strips (2) Provide details and specify type of fabric for silt fence Traffic Area Stabilization (1) Show construction entrance with detail (Figure D.4.G) (2) Show proposed construction roads and parking areas. Specify details for stabilization. Sediment Retention (1) Show location of sediment pond or sediment trap. Very small areas can be treated with only perimeter protection (see D.4.3). (2) Sediment Trap -Can be used for drainage areas of 3 acres or less. Calculate surface area using 2-year design storm. Show detail per Figure D.4.H. (3) Sediment Pond -Determine pond geometry and show details on plan for required storage, depth, length and width (4) Show sediment pond cross section and detail (Figures D.4.J and K) (5) Provide details of cell dividers and stabilization techniques for inlet/ outlet (6) Specify mulch or recommended cover of berms & slopes (7) Specify the 1-foot marker for sediment removal (8) Indicate catch basins for protection and show design details (Figures D.4.L and M) Surface Water Control (1) Show conveyance of all surface water to a sediment pond or trap (2) Discharge location shall be downslope from disturbed areas (3) Show details for conveyance with interceptor dike, swales (Figures D.4.0, P). (4) For ditches, determine capacity for 10-year storm with 0.5 feet freeboard. Show details for check dams (Figure D.4.R). Determine check dam spacing and as needed, show inverts and minimum slopes of open channels. Also show direction of open channel ftow. (5) For pipe slope drains, determine capacity for 10-year storm. Show details per Figure D.4.Q. (6) Determine level of protection for outlet (rock pad, outfall design, or level spreader). See requirements in D-38 through D-40. (7) Evaluate off-site flows entering the site and assure bypass of disturbed areas EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 7 of 16 Activity Number: ------------- 2.3.1.3 EROSION AND SEDIMENT CONTROL (SWDM Appendix DI (contlnuedl OK SWDM D D D D D D D D D D D D D D D D D D D D D D D D D D.5.1 D.5.2 D.5.3 D.5.4 D.5.7 D.5.8 ESC Report (1) Show detailed construction sequence (page D-70) (2) All required calculations and soils reports contained in TIR Wet Season Requirements (1) Provide a list of all applicable wet season requirements (details on page D-42) Critical Area Restrictions (1) Consider phased construction during the dry season. See special recommendations on page D- 43. Maintenance (1) Plans shall list the name, address and phone number of the ESC Supervisor. A sign shall also be posted on the construction site with information for contacting the ESC supervisor. (2) Determine if site is Highly Critical (Soil Types C or D, 5 acres of disturbance, large areas with slopes >10%, proximity to streams, wetlands, or lakes) (3) On cover sheet of engineering plans, designate if highly critical site NPDES Requirements (1) Determine if project will disturb more than 5 acres (2) If disturbed area is greater the 5 acres, show the following note on the plans: "No construction or site disturbance for this project may begin before the applicant first obtains a General Permit to Discharge Stormwater Associated with Construction Activity permit from the Washington State Department of Ecology (DOE). For more information or application form, please visit DOE's website at http://www.ecy.wa.gov/bibliolecy02085.html" Forest Practices Permit (1) Determine if project needs FPA permit. Contact DDES grading section. (2) Provide a reference note on the cover sheet indicating whether or not an FPA permit has been obtained. Early Start Plan Review (1) Standard cover sheet included with Title for Phased Early Start (2) List the scope of work for early start (scope of work will vary for each project -evaluate clearing, grading for roads, lot grading, utility installation, vault construction, off-site work) (3) Update the sheet index to identify all plans with updated page numbers (4) Include standard ESC plan prepared in accordance with all requirements listed above for erosion and sediment control (5) Include detailed construction sequence and identify ESC supervisor (6) Show standard erosion control notes (7) Show early start activity number on all plain sheets EngineeringReviewChecklistFORM.doc 10/10/2005 6 of 16 Activity Number: ------------- DESIGN REQUIREMENTS OK SWDM D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D 3.2 3.27 3.3.6 3.3.7 4.0 4.5 4.7 4.9 4.9 4. 10 4.27 4.35 4.51 4.69 4.53 5.0 5.3 5.9 5. 11 Runoff Computation Rational Method required for on-site conveyance (See Table 3.2) KCRTS used for flow control design Evaluate correct data: Rainfall region, scale factor, time step, record type, acreages, soil cover groups, and percent impervious For urban areas, unprotected forest modeled as pasture or grass For rural areas, unprotected forest assumes 50% grass, 50% pasture All pre-developed grassland modeled as pasture All post developed grassland modeled as grass Impervious coverage calculated based upon specific project -clearly summarize types and amounts of impervious For urban development, impervious for each lot, >= 4,000 sq ft or maximum allowed in zoning code For rural development, impervious for each lot, >= 8,000 sq ft or maximum allowed in zoning code Evaluate requirements for modeling with effective impervious area Point of compliance -evaluate for on-site bypass and off-site closed depression On-site closed depressions and ponding areas Conveyance System Analysis and Design Conveyance systems are in easements with BSBLs Off-site easements must be recorded using standard forms (Reference 8H) Determine which easements are public and private, label and dimension Pipes are parallel to and alongside property lines Minimum pipe size 12-inch, for private systems may allow 8 inch Easements for pipes outside of right of way For connecting pipes at structures, match crowns, 80% diameter, or inverts Minimum velocity at full flow 3.0 feet per second Minimum cover for pipes 2 feet Debris barrier for pipes 18-36 inch Outfall design criteria Surcharges (backwater analysis may be required) Maximum headwater allowed for culverts Bridge design Floodplain analysis Open channels Flow Control Design Mandatory requirements for roof downspouts in order of preference. Must evaluate feasibility of each. o Infiltration o Dispersion o Perforated stubouts Dispersion system criteria including vegetated flow path Perforated stub out, if used show detail per Fig. 5. 1.3.A EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 9 of 16 Activity Number: ------------- DESIGN REQUIREMENTS (continued) OK SWDM D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D 5.14 5.15 5.17 5.3 5.3.1 5.3.2 Forested open space flow control BMPs o Show tracts or easements for FOS o Show required notes on plan for plat recording Roadway dispersion BMPs, check design criteria BMPs for reducing facility size. Note: Facility sizing credit allowed for dispersion only if flowpath from roofs ultimately drain to RID facility. Detention Facilities Emergency overflow -Evaluate flow path for safe and adequate conveyance Setbacks Flow-through system Detention Ponds Dam Safety Compliance Two cross-sections through pond (one x-section to include control structure) Review pond details in Figures 5.3.1.A and B Designed as flow-through system Side slopes interior 3H:1V or fenced Vertical interior retaining walls Stamped by licensed structural civil engineer For pond walls, min. 25% of perimeter vegetated and no steeper than 3:1 Berms greater than 4 feet require key excavation Minimum berm width of 6 feet Primary overflow (control structure with riser). Secondary Inlet to the control structure Emergency Overflow Spillway, 100 year developed peak flow Soil and compaction requirements described (95% modified proctor) Access road min. turning radius, maximum grade, min. width, fences or gates Pond sign (Figure 5.3.1.D) Fencing and planting requirements Setbacks -5 feet from tow of exterior slope or 5 feet from water surface for cut slope Detention Tanks Flow-through system required 6" of dead storage in tank bottom Minimum pipe diameter of 36" Materials and structural stability Control structure per Section 5.3.4 Buoyancy Access risers and CBs are spaced properly with max. depth from finished grade to tank invert shall be 20 feet and accessible by maintenance vehicles EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 10 of 16 Activity Number: ------------- DESIGN REQUIREMENTS fcontlnuedl OK SWDM D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D 5.3.3 5.3.4 5.4 6.0 6.1 6.2 6.2.2A 6.2.3 6.2.4 6.2.5 6.3 6.3.1 6.3.1.1 6.3.1 6.3.4 Detention Vaults Structural package submitted for approval Flow-through system required Review design details per Fig. 5.3.3.A. Note: Grate over sump with 2' x 2' hinged access door Access positioned a maximum of 50 feet from any location. (if over 3 foot cover use cone riser) Access required to inlet pipe and outlet Removable 5x1 O panel if vault greater than 1250 sq. ft. floor area Maximum depth from finished grade to vault invert to be 20 feet Minimum internal height shall be 7 feet, min. width shall be 4 feet min Ventilation pipes provided in all four corners Control Structures Section and plan view shown to scale Orifice size and elevation on plans match calculations. Minimum orifice 0.5". (Note: Information Plate details are no longer required -see policy on Web site.) Infiltration Facilities Appropriate soils logs and testing procedures in TIR Pond bottom at least 3 feet above seasonal high water Permeable soil extends minimum 3 feet below bottom of pond Geotechnical report states suitability and determines design infiltration rate Overflow route identified with 100-yr overflow conveyance Spill Control device upstream of facility Presettling Review setback requirements, page 5-60. Design water surface setback of 20 feet from external tract, easement or property lines Show the standard note regarding public rule for in operation facility (see section policies) Water Quality Design Water Quality Menus Water Quality facilities Water Quality Sequencing Setbacks, slopes and embankments Facility Liners Flow Splitter Designs Blofittration Facility Biofiltration swales and soil amendments Methods of Analysis Swale geometry, plantings, flow conveyance, high flows, velocity Road access requirements, page 6-43 Filter strip geometry (slopes) EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 11 of 16 Activity Number: ------------- DESIGN REQUIREMENTS (continued) OK SWDM D D D D D D D D D D D D D D D D D D D D D D D D D D D D D Notes· 6.4 6.4.1.2 6.4.1.1 6.4.2 6.4.1.1 6.4.1.1 6.4.2.2 6.4.3 6.4.3.1 6.4.3.2 6.4.4 6.4.4.1 6.4.4.2 6.4.4.2 6.5 6.5.1 6.5.2 6.5.2.1 6.5.2.2 6.5.3 6.5.3.2 6.5.3.2 Wetpool Facility Designs Wetpool geometry, 2 cells, minimum depth of first cell 4 feet Flowpath length to width ratio 3:1. Note: If flow path achieved with berms or walls, top of berm must be at 2-year water surface elevation. Berms, Baffles, Slopes Inlet/Outlet Design Access, setbacks, and plantings Wetvaults Sizing basic or large Berms, Baffles, Slopes Two cells separated by wall or removable baffle Vault bottom forms a broad "V" with 5% sideslopes Inlet is submerged and outlet pipe designed for 100-year overflow Gravity drain provided if grade allows Minimum 50 square feet of grate over second cell Stormwater Wetlands Methods of Analysis Design Criteria -Wetland geometry, liners, access, plantings Combination Detention and Wetpool facilities Methods of Analysis Design Criteria -Detention and wetpool geometry, berms, baffles, slopes Access and plantings Media FIitration Facility Designs Presettling/pretreatment Sandfilters -Basic and Large Methods of analysis Design Criteria -Geometry, overflow/bypass, underdrain, and access Sandfilter Vaults Design Criteria -geometry, pretreatment, flow-spreading, energy dissipation Overflow/bypass, underdrain and access EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 12of16 Activity Number: ------------- KING COUNTY ROAD STANDARDS (1993) GENERAL REQUIREMENTS KCRS 1.03A, B 1.03 D Off-site and frontage improvements determined by reviewing agency Note: For grading permits, the required extent of road improvements must be determined during engineering review. For subdivisions, the requirements are determined during preliminary review. Subdivisions must have recorded public access except for private roads DESIGN REQUIREMENTS 1.08 Road Variances Activity No. Approval Date ---------- Design Issues ROAD CLASSIFICATION TABLE Name of Roadway KCRS Classification OK KCRS D 2.03C Maximum Superelevation (2.05) D 2.03D Horizontal curvature (2.05) D 2.03E Maximum grade (2.11) D 2.03F Stopping Sight Distance (2.05, 2.12) D 2.03G Entering Sight Distance (2.05, 2.13) EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 13of16 Activity Number: ------------- KING COUNTY ROAD STANDARDS (1993) DESIGN REQUIREMENTS (conllnuedl OK KCRS D 2.03H D 2.031 D 2.03J D 2.03J D 2.03K D 2.03L D 2.06 D 2.0667 D 2.07 D 2.08A D 2.086 D 2.08E D 2.08F D 2.09 D 2.096 D 2.10A D 2.10A D 2.10A D 2.106 D 2.10C D 2.10E D 2.11A D 2.11 B D 2.12D D 2.16 D 2.18 D 2.20 D 3.01 D 3.01 D 3.02A D 3.026 D 3.05 Minimum pavement width (Note: Footnote 9 -Neighborhood collectors require 36-feet at approach to intersections with arterials) Minimum roadway width Minimum R/W width Min. R/W width (Footnote 12 and 2.19B -include 1 foot extra ROW behind curb or sidewalk) Curb or shoulder type road (2.01) Minimum Half-Street width Private Street Design Standards Verify maximum potential of 16 lots Half Streets Minimum Cul-de-Sac diameters Maximum Cul-de-Sac length Maximum Cross Slope 6% Bulb island shall be offset 2-feet Alleys Private Access Tracts (Note: Must meet all standards for minor access street, except curb cut driveway design is allowed with property line radii dedication) Angle of intersection between 85 and 95 degrees Intersection curb radius Intersection right-of-way radius Intersection spacing Intersection landing Low Speed Curves Maximum Grade -Use AC for grades >12%, Use PCC for grades >20% Grade Brakes -maximum 1 % at intersections Intersection stopping sight distance (125' SSD allowed for local access streets) Bus zones -For arterials and neigh. collectors, the designer shall contact metro Intersections with State Highways Single access serving more than 100 lots Driveways Joint Use Driveways Sidewalks (both sides for subcollectors and higher classification) Location and width Handicapped access ramp (Use updated detail from KC Road Engineer, 3/26/04) EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 1011012005 14 of 16 Activity Number: ------------- KING COUNTY ROAD STANDARDS (1993) · DESIGN REQUIREMENTS (continuedl OK D D D D D D D D D D D D D D D D D D D D D D D D D D D D D D KCRS 3.09 3.10 3.11 4.01 4.01F 4.01F 4.02 4.02 4.03 4.05 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.11 6.00 7.02A-D 7.03A 7.03L 7.04A 7.04E 7.05A 7.058 7.05E 8.02 8.038 School Access -asphalt walkway, sidewalk, or delineated shoulder Bikeways Equestrian Facilities Road Section and Surfacing (drawings 1-001 -1-006) Note: Neighborhood collectors require 3-inch asphalt concrete. Perform saw cut of pavement at fog line Pavement overlay for widening and channelization (show special note as approved by Development Engineer -see section policies) Residential street design Poor subgrade evaluation Arterial pavement design Pavement markings, channelization, and tapers (Requires DOT review) Rock facings (Dwg. Nos. 5-004 --5-007) Side slopes, generally 2H:1V Street trees and landscaping Mail boxes (Dwg. Nos. 5-010 -5-012) Street illumination Survey Monuments to be disturbed are shown Roadway Barricades Bollards for walkways or maintenance roads Roadside obstacles (Note: If variance required for utility pole, the utility company must apply for the variance.) Bridges (minimum width 28-feet) Grass-lined, pipe or rock lined, special designed ditch Minimum pipe size 12-inch diameter Beveled ends for culverts in ROW Maximum spacing between catch basins CBs taller than 5' (grate to invert) are Type II, Max. depth 12-feet per Dwg. 2-005 Vaned grates Through curb inlet frames for sag curves and intersections> 4%. Notes: a) Through curb inlet not used on rolled curb b) See section policies for policy on three flanking inlets All covers and grates shall be locking Utility pole locations and other obstacles Open cuts on existing roadways, patch requirements EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10110/2005 15 of 16 Activity Number: ------------- KING COUNTY ROAD STANDARDS (1993) DESIGN REQUIREMENTS fcontlnuodl Notes: Check out the DOES Web site at www.metrokc.gov/ddes EngineeringReviewChecklistFORM.doc 10/10/2005 16 of 16 , ® King County DeJ)artment of Development and Environmental Services 900 Oakesdale A venue Southwest Renton, WA 98055-1219 March 31, 2006 Fanny and Philip Yee 11431 233th Street Woodway, WA 98020 RE: Preliminary Approval for Short Subdivision No. L04S0065. Dear Mr. and Mrs. Yee: The Land Use Services Division (LUSD) has completed review of the short subdivision application captioned above. The LUSD finds that the proposed short subdivision complies with the King County Land Segregation Code (Title 19A), Zoning Code (Title 2 IA), and other applicable codes as specified in King County Code (KCC) I 9A.08.060. The short subdivision is granted preliminary approval subject to the Conditions of Preliminary Approval attached hereto and incorporated herein by reference. Any aggrieved party may appeal this decision by the appeal deadline, which is April 24, 2006. The appeal procedure is enclosed for your information. The preliminary approval is valid for a period of 60 months from the date of this Jetter, unless an appeal is filed. In the event that an appeal is filed, the preliminary approval is valid for a period of 60 months from the date of the appeal decision. Enclosed are the following: o Notice of Decision o Conditions of Preliminary Approval o Appeal Procedure If you have any questions regarding this Jetter, please contact Fereshteh Dehkorcli, Program Manager, at (206) 296-7173 and Curt Foster, Engineer, at (206) 296-7106. Sanders, Development Engineer Engineering Review Section, LUSD Enclosures cc: De En Lang, Consulting Engineer Applicant File Letter frm/CoverLtr2000 SP.doc 3/9/00 iSM\)~~ Lisa Dinsmore, Supervisor Current Planning Section, LUSD A ® KING COUNTY DEPARTMENT OF DEVELOPMENT AND ENVIRONMENTAL SERVICES LAND USE SERVICES DIVISION 900 Oakesdale Avenue Southwest Re_nton, WA 98055-1219 REPORT AND DECISION SHORT SUBDIVISION File No. L04S0065 DESCRIPTION OF THE PROPOSED SHORT SUBDIVISION: This is a short subdivision of .96-acre site (two tax parcels) into six (6) lots for detached single-family dwellings in the R-6 zone. The proposed density is 6 dwelling units per acre. The proposed lot sizes range from approximately 3000 square feet to 5,300 square feet. Refer to Attachment 1 for a copy of the short plat map. B. GENERAL INFORMATION: Owner/Applicant: Consulting Engineer: STR: Location: Zoning: Acreage: Number of Lots: Density: Lot Size: Proposed Use: Sewage Disposal: Water Supply: Fire District: School District: Date Submitted: Fanny and Philip Yee 11431 2381h Street · Woodway WA 98020 Lang Associates, Inc. 10658 Riviera Place NE Seattle, WA 98125 SW Y. 33-23-05 12052 SE 129th Place R-6 .96 acre 6 6 du/acre Ranges from 3000 to 5,300 square feet Residential Soos Creek Water and Sewer District Soos Creek Water and Sewer District Fire District 40 Renton School District Complete Application Date: December 27, 2004 January 17, 2005 C. HISTORY and BACKGROUND The Subdivision Technical Committee (STC) of King County has conducted an on-site examination of the subject property. The STC has discussed the proposed development with the applicant to clarify technical details of the application and to determine the compatibility of this project with applicable King County plans, codes, and other official documents regulating this development. As a result of preliminary discussions, the applicant presented the Technical Com.mittee with a revised site plan on January 9, 2006. The revision to address some of the technical issues was minor. No change to the road or lot layout was made. Report and Decision -I -L04S0065 D. NATURAL ENVIRONMENT 1. Topography: The site slopes down gently from west to east. The maximum slope is3%. 2. Soils: One soil type is found on this site per King County Soil Survey, 1973. The entire site is classified AgB. The following are characteristics of AgB soils: AgB -Alderwood gravely, sandy loam; 0-6% slopes. Runoff is slow and the erosion hazard is slight. This soil type has moderate limitations for low building foundations due to a seasonally high water table, and severe limitations for septic tank filter fields due to very slow permeability in the substratum. 3. Wetlands: A wetland and report was prepared by Altmann Oliver Associates dated December 22, 2004. The report identified a small (175 sq.ft.) isolated shallow wetland partly on site. This wetland is exempt from regulation. The site lies within the Soos Creek drainage basin. 4. Vegetation: This site is primarily covered in grasses. Scattered evergreen and deciduous trees and sherubs occur in limited numbers. 5. Wildlife: Small birds and animals may inhabit this site; however, their population and species are limited due to nearby development. No threatened or endangered species are known to exist on or near the property. 6. The Sensitive Areas Folio does not identify any mapped sensitive areas as being present on this site. · E. NEIGHBORHOOD CHARACTERISTICS: F. The property lies within a gradually urbanizing area east of the City of Renton. The proposed subdivision of Fleuve Des Voies, KC File L04P0002, with 38 residential lots is on parcels east of the site and is currently under review by DOES. There are larger lots with potential for re-subdivision to the west and north of the site. The properties south of the site are developed with single family residences. The site and the surrounding parcels are zoned Residential (R-6) with six dwelling units per acre. The proposed subdivision site is undeveloped. DESIGN FEATURES 1. Lot Pattern and Density: The proposed density and lot layout meets the density requirements of R-6 and the Short Subdivision Code. 2. Access/Roadway Section: The site obtains access to 1201 h Avenue SE via a 30- foot wide easement extending east from the road to the site. The easement will be improved to an urban minor access road standards consisting of curb, gutter and sidewalks on the north side of the road. 3. Drainage: Currently drainage from the property leaves the site in the form of sheet flow. After development, storm water runoff (from the proposed under ground vault) will be conveyed eastward (same direction) to a proposed development on the neighboring property. The applicant has received a letter of agreement from the property owner directly east of the site to allow a drainage easement across his property for this purpose. The on-site vault will be located in the southeast corner of the property. It will be designed for Level II flow control and basic water quality (1998 Surface Water Design Manual). 3. Other Design Features: The proposal includes a 3,173-square-foot recreation tract located southeast of the site. This tract will be improved with landscaping and a toy structure for the benefit of the subdivision's future residents. Report and Decision -2 • L04S0065 G. G. PUBLIC SERVICES 1. Sewage Disposal: The applicant proposes to serve the subject subdivision by means of a public sewer system managed by the Soos Creek Water and Sewer District. A Certificate of Sewer Availability, dated December 2004 indicates this sewer distrids capability to serve the proposed development. 2. Water Supply: The applicant proposes to serve the subject subdivision with a public water supply and distribution system managed by the Soos Creek Water and sewer District. A Certificate of Water Availability dated December 17, 2004 indicates this water district's capability to serve the proposed development. 3. School facilities: The subject subdivision will be served by Benson Elementary, Nelson Middle, and Lindberg Senior High Schools, all located within the Renton School District. 4. School Access: The District has indicated that the future students from this subdivision· will walk to Benson Elementary and the middle and high school students will be bussed from the intersections of 120th Avenue SE and SE 1881h Street and from the intersection of SE 1881 h and 116th Avenue SE respectively. Currentlr there are no sidewalks along 1201 h Avenue SE to its intersection with SE 188 1 Street. Sidewalk improvements are expected along SE 1881h Street by other subdivision proposals in the area. This improvement together with the required off-site pedestrian improvements (See SEPA condition below) will complete a continuous walkway facility from the site to the school bus pick up areas. 5. Parks and Recreation Space: The nearest public park is Soos Creek Park located along SE 192"d Street a few miles southeast of the site. KCC 21A.14 requires subdivisions in the UR and R zone classifications to either provide on- site recreation space or pay a fee to the Parks Division for establishment and maintenance of neighborhood parks. At this time, the applicant is proposing to provide a 3,100 square-foot recreation tract on the site. The site of the recreation tract is encumbered by the Soos Creek utility easement. The Soos Creek Water and Sewer District has agreed to reduce the easement width to 10-foot wide for the water main. The District has no objection to development of a recreation tract on the easement provided no toy structure is anchored within the easement, see attachment ~- KCC 21 A.14.190 requires subdivisions to provide tot/children play areas within the recreation space on-site. The proposal must include a 270-square-foot play area with the required recreation tract The recreation tract plan must be reviewed and approved by the Soos Creek Utility District. SEPA THRESHOLD DETERMINATION: Pursuant to the State Environmental Policy Act (SEPA), RCW 43.21 C, the responsible official of the LUSD issued a mitigated threshold determination of non-significance (MONS) for the proposed development on March 24, 2006. This determination was based on the review of the environmental checklist and supporting documentation filed with the application, resulting in the conclusion that the proposal would not cause probable significant adverse impacts on the environment provided the following measures are attached to the project as conditions: In accordance with the requirements with RCW 58.17.110 (2), the Applicant shall improve 120th Avenue SE, from the plat entrance in the 19000 block northward to the intersection of SE 188th Street/120th Avenue SE by providing a paved walkway along the easterly side of 120th Avenue SE. The walkway, per Section 3.09 of the KCRS shall be selected and designed by the Applicant's engineer in accordance with any one of the following standards, and upon approval by DOES, constructed: Report and Decision -3 -L04S0065 H. I. A A full width (8 feet) paved shoulder 8. A paved shoulder of no less than four (4) feet in width, separated by vehic)e traffic by either an extruded curb or an unpaved gravel shoulder strip C. A concrete curb and gutter, and sidewalk section FINDINGS/CONCLUSIONS: The subject subdivision will comply with the goals and objectives of the King County Comprehensive Plan and will comply with the requirements of the Subdivision and Zoning Codes and other official land use controls of King County ( e.g. 1993 King County Road Standards, 1998 Surface Water Design Manual, etc.), based upon the conditions for final short plat approval. DECISION: The proposed Short Plat revised and received January 9, 2006 (Attachment 1) is granted preliminary approval subject to the following conditions of final approval: 1. The proposal shall comply with all platting provisions of King County Title 19A. 2. All persons having an ownership interest in the subject property shall sign on the face of the final short subdivision. 3. All utilities within proposed rights-of-way must be included within a franchise approved by the King County Council prior to final short plat recording 4. 1998 King County Surface Water Design Mariual /SWDM) /KCC 9)-The proposed short plat qualifies for full drainage review as outlined in Chapter One of the SWDM. Final short plat approval shall require full compliance with the drainage provisions set forth in King County Code 9.04. A professional civil engineer licensed in the State of Washington shall prepare drainage plans and a technical information report as outlined in Chapter 2 of the drainage manual. · The drainage plan submittal shall demonstrate compliance with all applicable Core and Special Requirements. Compliance may result in reducing the number and/or location of lots as shown on the preliminary approved short plat. Preliminary review has identified the following conditions of approval, which represent portions of the drainage requirements. All other applicable requirements in KCC 9.04 and the Surface Water Design Manual (SWDM) must also be satisfied during engineering and final review. A. Engineering plans and analysis shall comply with the SWDM. Prior to short plat recording, the applicant shall submit engineering plans to address the required short plat improvements. King County approval of drainage and roadway plans is required prior to any construction. Permit fees for review and inspection shall be paid as required by County codes and policies. Bonding for the drainage plans will also be established as determined by ODES prior to plan approval. After receiving drainage plan approval, the applicant shall contact the DOES Land Use Inspection Section to schedule a pre-construction meeting prior to performing work on the site. B. Current standard plan notes and ESC notes, as established by. ODES Engineering Review shall be shown on the engineering plans. C. The following note shall be shown on the final recorded plat: "All building downspouts, footing drains, and drains from all impervious surfaces such as patios and driveways shall be connected to the permanent storm drain outlet as shown on the approved construction drawings# on file with ODES and/or the Department of Transportation. This plan shall be submitted with the appJication of any .;- Report and Decision . 4. L04S0065 building permit. All connections of the drains must be constructed and approved prior to the final building inspection approval. For those lots designated for perforated stubouts, dispersion, or infiltration systems, the designs shall be constructed at the time of the building permit and shall comply with the plans on file." SITE SPECIFIC CONDITIONS: The conceptual drainage plan for this short plat proposes to discharge surface water run-off into a future piping system. The future piped conveyance would be constructed and located on the adjace t property to the east under a proposed subdivision application (LO 02). Prior to engineering plan approval, the applicant shall provi e proof that assures the offsite conveyance will be constructed and located in easements where appropriate. D. Should the proposed offsite conveyance not be available at engineering review, and prior to plan approval the applicant shall submit a revision to this application with a new conceptual drainage plan. Since this will require a substantial change this project may be re-vest to the current SWDM (20.20.080 KKC). 5. 1993 King County Road Standards /KCRS) /KCC 14)-Final short plat approval shall require full compliance with the provisions set forth in the King County Road Standards (KCRS), including engineering plans for all road and site improvements. The engineering plans shall be prepared by a professional civil engineer licensed in the state of Washington. DOES strongly recommends that the engineering plans be submitted at least two years prior to the expiration date of the project. All construction and upgrading of public and private roads within this short plat shall comply with the following requirements unless otherwise approved by ODES (KCRS Section1 .03). A. The proposed road and cul-de sac serving the property shall be constructed to urban minor access street standard per KCRS, Section 2.03. It shall extend from 1201h Avenue SE and continue into the site terminating into a cul-de-sac bulb as shown on the site plan per KCRS Section 2.08. · B. The off-site portion of the road improvements may remain in the existing easement. A note conveying an equally undivided responsibility (to each future lot owner) for the offsite maintenance cost (for roadway and facilities within the easement) shall be placed on the final recorded map page or recorded separately. Additionally, the note shall include a statement allowing the maintenance responsibility to be modified if agreed to by all beneficiaries of the original easement including right of way dedication to a public agency. C. The on-site improvements shall be placed in a tract. The tract shall be an undivided ownership to the lots it serves, and the lot owners shall be responsible for its maintenance. 0. The proposed road improvements shall address the requirements for road surfacing outlined in KCRS Chapter 4. As noted in section 4.01 F, full width pavement overlay is required where widening existing asphalt. E. Modifications to the above road conditions may be considered by King County pursuant to the variance procedures in KCRS 1.08. F. The following notes shall be shown on the final recorded short subdivision: Report and Decision -5 -L04S0065 (1) All private easements and/or tracts to be maintained, repaired, and/or rebuilt by the owners of the parcels having legal access there from and their.heirs, assigns or successors, unless and until such roads are improved to King County standards and are dedicated and accepted by King County for maintenance. (2) All restrictions, easements, tracts, and their purpose shall be shown on the final recorded short subdivision. 6. Health (KCC 13)-This project is exempt from further King County Heath Department review. However, if improvements are required from the Sewer and/or the Water District, then verification shall be required from said District(s) that the improvements have been bonded and/or installed, prior to final recording of the short plat. 7. Building and Construction Standards (Title 16)-The applicant shall comply with all applicable provisions of KCC 16.82. including the significant tree retention requirements. 8. Fire Code (KCC 17) -Section 902 of the 1997 Edition of Uniform Fire Code The applicant must obtain the approval of the King County Fire Protection Engineer for the adequacy of the fire hydrant, water main and fire flow standards of Chapter 17 .08 of the King County Code prior to the final short plat approval. 9. Density and Dimensions (KCC 21A.12) -All lots shall meet the density and dimensions requirements of the R-6 zone classification or shall be as shown on the face of the approved preliminary short subdivision, whichever is larger. Minor revisions to the short subdivision, which do not result in substantial changes and/or do not create additional lots may be approved at the discretion of the Department of Development and Environmental Services. 10 Street Trees (KCC 21A.16)-Street trees shall be provided as follows (per KCRS 5.03 and KCC 21 A.16.050): A. Trees shall be planted at a rate of one tree for every 40 feet of frontage along all roads. Spacing may be modified to accommodate sight distance requirements for driveways and intersections. B. Trees shall be located within the street right-of-way and planted in accordance with Drawing No. 5-009 of the 1993 King County Road Standards, unless King County Department of Transportation determines that trees should not be located in the street right-of-way. C. If King County determines that the required street trees should not be located within the right-of-way, they shall be located no more than 20 feet from the street right-of-way line. D. The trees shall be owned and maintained by the abutting lot owners or the homeowners association or other workable organization unless the County has adopted a maintenance program. Ownership and maintenance shall be noted on the face of the final recorded plat. E. The species of trees shall be approved by ODES if located within the right-of-way, and shall not include poplar, cottonwood, soft maples, gum, any fruit-bearing trees, or any other tree or shrub whose roots are likely to obstruct sanitary or storm sewers, or that is not compatible with overhead utility lines. F. The applicant shall submit a street tree plan and bond quantity sheet for review and approval by DOES prior to engineering plan approval. Report and Decision -.6. L04S0065 G. The street trees must be installed and inspected, or a performance bond posted prior to recording of the plat. If a perfo~m~nce bond is posted, .the street trees must be installed and inspected within one year of recording of the plat. At the time of inspection, if the trees are. found to be installed per the approved plan, a maintenance bond must be submitted or the performance bond replaced with a maintenance bond, and held for one year. After one year, the maintenance bond may be released after ODES has completed a second inspection and determined that the trees have been kept healthy and thriving. 11. Sensitive Areas (KCC 21A.24)-The small size Class Ill wetland located near the northeast property line is exempt from the Sensitive area requirements. 12. Road Mitigation Payment System -The applicant or subsequent owner shall comply with Road Mitigation Payment System (MPS), King County Code 14.75, by paying the required MPS fee and administration fee as determined by King County Department of Transportation. The applicant has an option to either: A. Pay the MPS fee at final short plat recording. If this option is chosen, the fee paid shall be the fee in effect at the time of short plat application and a note shall be placed on the face of the short plat that reads, "All fees required by King County code 14.75, Mitigation Payment System (MPS) have been paid." Or B. Pay the MPS fee at the time of building permit issuance. If this option is chosen, the fee paid shall be the amount in effect as of the date of the building permit application. 13. Recreation Tract. KCC 21A.14-As shown on the site plan, a recreation tract shall be provided consistent with the requirements of KCC 21A.14.180 and KCC 21A.14.190 (i.e., sport court[s], children's play equipment, picnic table[s], benches, etc.). A detailed recreation space plan (i.e., landscape specs, equipment specs, etc.) consistent with KC 21A.16 shall be submitted for review and approval by DOES and King County Parks prior to submittal of the final plat documents or concurrent with the Engineering Review phase. The recreation plan must show only a 10-foot wide easement within the tract as agreed by the Soos Creek Utility District. No toy structure shall be placed within the 10-foot wide utility easement. The recreation tract shall be fully fenced. A performance bond for recreation space improvements shall be posted prior to recording of the plat. 14. A homeowner's association or other workable organization shall be established to the satisfaction of ODES which provides for the ownership and continued maintenance of the recreation tract. 15. To implement KCC 21A.38.230 which applies to the site, a detailed tree retention plan shall be submitted with the engineering plans for the subject plat. The tree retention plan and the engineering plans shall be consistent with the requirements of KCC 21A.38.230, as well as the conceptual tree retention plan which is part of the hearing record for this project. No clearing of the subject property is permitted until the final tree retention plan is approved by LUSO. Flagging and temporary fencing of trees to be retained shall be provided, consistent with KCC 21A.38.23084. The placement of impervious surfaces, fill material, excavation work, or the storage of construction materials is prohibited . within the fenced areas around preserved trees, except for grading work permitted pursuant to KCC 21A.38.23084d(2). A note shall be placed on the final plat indicating that the trees shown to be retained on the tree retention plan shall be maintained by the future owners of the proposed lots, consistent with KCC 21A.38.23086. Please Note that the tree retention plan shall be included as part of the final engineering plans for the subject plat. Report and Decision -7 -L04S0065 16. The following has been established under SEPA: In accordance with the requirements with RCW 58.17.11 O (2), the Applicant shall . improve 120th Avenue SE, from the plat entrance in the 19000 block northward to the intersection of SE 188th Street/120th Avenue SE by providing a paved walkway along the eastward side of 120th Avenue SE. The walkway, per Section 3.09 of the KCRS, shall be selected and designed by the Applicant's engineer in accordance with any one of the following standards, and upon approval by DOES, constructed. A. A full width (8 feet) paved shoulder B. A paved shoulder of no less than four (4) feet in width, separated by vehicle traffic by either an extruded curb or an unpaved gravel shoulder strip C. A concrete curb and gutter, and sidewalk section Other Considerations A. Preliminary approval of this application does not limit the applicant's responsibility to obtain any required permit or license from the State or other. regulatory body. This may include, but not be limited to, obtaining a forest . practice permit, an HPA permit, building permits, and other types of entitlements as necessitated by circumstances. B. The short subdivision shall conform to KCC 16.82 relating to grading on private property. C. Development of the subject property may require registration with the Washington State Department of Licensing, Real Estate Division Parties and Persons of Interest: BULEN, BRENDA & KEN 19007 120TH AVENUE SE RENTON, WA 98058 BUSH, BEN & GERALDINE 19124 121ST PLACE SE RENTON, WA 98058 LABRIE, ERIC ESM CONSULTING ENGINEERS 720 S 348TH STREET FEDERAL WAY, WA 98003 LANG ASSOCIATES DE EN LANG 10658 RIVIERA PLACE NE SEATILE, WA 98125 YEE, FANNY & PHILIP 11431-238TH STREET WOODWAY, WA 98020 CLAUSSEN. KIM PROGRAM MANAGER Ill DDES/LUSD DEHKORDI, FERESHTEH PROJECT MANAGER II DDES/LUSD FOSTER, CURT SR. ENGINEER DDES/LUSD LISA DINSMORE. SUPERVISOR, CURRENT PLANNING SECTION JIM SANDERS, DEVELOPMENT ENGINEER< ENGINEERING REVIEW SECTION Report and Decision -8 -L04S0065 Appeal Information and Parties of Record RIGHT TO APPEAL This action may be appealed in writing to the King County Hearing Examiner, with a fee of $250 (check payable to King County Office of Finance). As required by KCC 20.20.090 and 20.24.090, the appeal period shall be twenty one (21) calendar days and shall commence on the third day after the notice of decision is mailed. Filing an appeal requires actual delivery to the King County Land Use Services Division prior to the close of business (4:30 p.m.) on April 24, 2006. Prior mailing is not sufficient if actual receipt by the Division does not occur within the applicable time period. The Examiner does not have authority to extend the time period unless the Division is not open on the specified closing date, in which event delivery prior to the close of business on the next business day is sufficient to meet the filing requirement. · If a timely Notice of Appeal has been filed, the appellant shall file a statement of appeal within a 21-day calendar period commencing three days after the notice of decision is mailed. The statement of appeal shall identify the decision being appealed (including file number) and the alleged errors in that decision. The statement of appeal shall state: 1) specific reasons why the decision should be reversed or modified; and 2) the harm suffered or anticipated by the appellant, and the relief sought. The scope of an appeal shall be based on matters or issues raised in the statement of appeal. Failure to timely file a notice of appeal, appeal fee, or statement of appeal deprives the Examiner of jurisdiction to consider the appeal. Appeals must be submitted to the Department of Development and Environmental Services, addressed as follows; LAND USE APPEAL Land Use Services Division Department of Development and Environmental Services . Black River Corporate Park 900 Oakesdale Avenue Southwest Renton, WA 98055-1219 Any party may make a request for a pre-hearing conference. For more information regarding appeal proceedings and pre-hearing conferences, please contact the Office of the Examiner for a Citizens' Guide to the Examiner Hearings and/or read KCC 20.20 and 20.24. Report and Decision . 9 • L04S0065 • SOOS CREER v\TAT~ .~ & SEWER DISTRICT 14616 s.E. 192nd St. • P.O. Box 58039 • Renton, WA 98058-1039 • Phone (253) 630-9900 • Fax (253) 630- September I, 2005 Ms. Fanny Yee RE: Short Plat Dear Fanny: K.C. D.D.E.S. 1L04S0065 / This letter is in response to your request for a letter to reduce a JO-foot construction easement that Soos Creek now holds for the installation of a water line to a IO-foot easement. Soos Creek will require a minimtun ofa 30-foot easement for the installation of the water line; however, we have no problem reducing that to a I 0-foot easement after the line is constructed. The easement we are discussing is from Alaskan House Movers to King County Water District No. 58 (33-23-5-21 ). Sincerely, fW4<~ Ron Speer District Manager RS:lks C:\Linda\LETrERS\FannyYee.doc www.soo.sc rcc k.co n1 ATTACHMENT~Z..~~ ' OF 1 PAGE -""P"A"G"'E=- / " ,..., ... ,--_. MENT OF OEvt'LOPMENT AND EN"1RONMENTAL SER"1CES j ond approved this --day of ---~ 20_~ Examined and approved th,19 __ day of 20 __ " "' "" , land Use Servfce:s Division ~- d and approved thlf:I __ doy of ---~ 20_~ Deputy Aeseaaor Account Number nent Engineer 1 CASED MON .. HO MARr-OFFSETS fOR t.AON. 00) " )> -; ~ i! .. S.E. 188th ST. BM '-0 ;..I I q 0 ,, r w U> w ~ ~ (',j ...- $ ~ m z -; " ~ jj ,s i, i 11111 1ht1 ~IG 6199000041 RS-6-50 <,f--____ _ TRACT 6 3-13.oo· GARDEN TRA< ~ VOL. 47, PAGE 90 J I ,.: 6199000120 .,. RS-6-50 -30" EASEMENT FOR ----INGRESS, EGRESS, ---~, I 0 0 N av~;9•20• W I ru o D l~ l, "' SCALE: 1 • = 50' -~ D .• ·,;_,_ PORTION OF SE 1/4 of SW 1/4, S. 33 T. 23 N., R. 5 E., W.M. EXISTING LOTS I I I~ 6199000050 RS-6-50 ~ N OIP.lii" H 6199000059 RS-6-50 I \' I( FOUND REBAR AND CAP LS 16898 \ I 0.36' N. Of LINE N 89"54'28" W i.BX t: I . / 7 \ . . _ 6199000080 RS-6-50 ,..__ ~~~riA~\ w @l @ \ @,' ~ ~ ~\\&li O ~ /'04 5 6199000125 PlPE I 3' RS-6-50 .P-• f, 8 ///, '~ 0 <II I \ .. LOT 1 ~ "' "' '£ j . 911· -,--, ii "" \ PruVATE STREIT 11 '1 ~...-f~WeUand Aroo 175 Sq. Ft . o LOT6 ~@ 'll_,@ z 6199000210 RS-6-50 RECREATION SPACE I 6199000220 •· RS-6-50 , FOUND 2• IRON PIPE 30' WATER MAIN EASEMENT RtC. NO. 7810020168C,:~ E IN PO\\Ul POLE '· 505.27 !1 ~lo /. I : :c I I I I 6199000142 RS-6-50 I I ~ I ~ I'.·~ Ir ~@ I 6199000140 : RS-6-50 .; I ' I LEGEND a_ 0 N .q [ill PO\\Ul POI.£ BOUARD WATER VALVf. FlRE HYDRANT WATER METER I LEGAL DESCRIPTI'oN TRACT 6, NORTHWESTERN GARDEN TRACTS, DIVISION NO. 5, ACCORDING TO THE PLAT THEREOF, RECORDED IN VOLUME 47 OF PLATS, PAGE 90, IN KING COUNTY, WASHINGTON. EXCEPT THE WEST 343.00 FEET THEREOF. () z 0 b rn (I) . c::, <i> ~ 0 ~ 00 0 0 ~ ~ • Laureen M. Nicolay From: Sent: To: Subject: Laureen M. Nicolay Monday, September 21, 2009 12:45 PM Stacy Tucker; Kayren K. Kittrick; Jennifer T. Henning LUA09-122, YEE (AKA HITONE) SHORT PLAT TRANSFERRED FROM KC WITH PREL APPROVAL -Needs assigned 6-LOT SHORT PLAT PLANNING FILE TRANSFERRED FROM KC ON 9-21-2009 AFTER APPROVAL BUT PRIOR TO RECORDING. UNSURE OF STATUS OF ENGINEERING OR LOCATION OF THOSE PLANS (IF ANY) HAS SMALL UNREGULATED WETLAND ON-SITE ACCORDING TO COUNTY STAFF REPORT Laureen Nicolay, Senior Planner City of Renton Development Planning 1055 S. Grady Way Renton, WA 98057 (425) 430-7294 phone (425) 430-7231 fax lnicolay@rentonwa.gov I Hitone Short Plat -Engineering File Status -Final review comments not yet sent to applicant. /'.>c. Pa~ially prepared redlines are shown on attached plans received June 30, 2009. Strdctural plans for storm vault not yet submitted by applicant. Tree retention review comments also enclosed and not yet sent to applicant. D e, Pete From: Sent: To: Subject: Attachments: Pete: r I ' Engell, Bruce Thursday, August 20, 2009 11 :45 AM Dye, Pete FW: Hitone S.P. # L07SR019 SigTreeSoilsPlatDirectionsCAO.doc; ls-inf-SoilPost-ConStd.pdf; SigTreeExPlantSoilsBond.doc This is the corrected copy that needs to be sent. From: Sent: To: Cc: Subject: Pete: Engell, Bruce Thursday, August 20, 2009 11:38 AM Dye, Pete Dobkins, Doug Hitone S.P. # L07SR019 2nd Comment List Tree / Soils Review I have completed the second review of the above referenced short plat for Significant Tree Retention, Soils Amendments and Bonding and have the following comments: 1. The Significant Tree Retention Plan shall follow the specific directions (attached). This is so all Tree Plans are consistent and clear for documentation, recording, construction and inspections. The wording as shown in the directions have blanks that must be filled in by the applicant. (4 copies are needed). It should be noted that this request was sent previously on January 24, 2008, but not followed on this revised submittal. 2. A Soils Amendment Plan shall be submitted along with the forms that need to be filled out (see attached ... 4 copies are needed). It should be noted that this request was sent previously on January 24, 2008, but not followed on this revised submittal. 3. A Significant Tree Retention Bond Quantity Form shall be completed and submitted (4 copies are needed). Sent previously but not followed on revision. 4. The lot boundary shall be shown on the tree site plan along with existing and proposed utility corridors and easements. Requested previously but not followed on revision. 5. If there are adjacent buildings, trees or shrubs within 10 feet of the plat boundary lines that could be impacted by clearing and grading of this, short plat they shall be shown on the plan with an explanation on how they will be protected both above and below ground level (as in the case of impacting root structures by excavation). The applicant is responsible for all damage to existing/adjacent buildings, trees and shrubs negatively impacted by construction occurring on this short plat. 6. I need a valid charge and billing number in order to charge my review time to this application. Note: Is this in the City of Renton now?? The applicant or consultant needs to read and understand the directions and information attached. If there are questions have them contact me via e-mail at bruce.engell@kingcounty.gov .. I will need 4 copies of all plans and documents requested. Thanks. 1