Engineering Review Comments
Project Type: 6 Lots Short Plat Review Date: 12/31/2008 Reviewer Name: Mazen Haidar, P.E.
Project Name : Hitone Short Plat Review No.: 2nd Email : mazen.haidar@kingcounty.gov
Project Number : L04S0065 Phone : (206) 296 -7133
Activity Number L07SR019 Fax: (206) 296 -6613 Project Manager: Pete Dye, P.E.
Sub
Item Item
Sheet 1 1
2
3
4
5
6
Code Review Comments
Reference
In the approval block on the Cover Sheet as well as
other plan sheets. please change the Development
Engineer name to show Molly A. Johnson, P.E. (see
redline markuns)
Please remover your stamp expiration date
Please provide actual signature on your stamp,
signature copies will not be accepted, and your stamp
must reflect your registration number very clearly
'currentlv hard to read)
As previousely requested, please provide the United
States Postal Services (USPS) approval stamp and
signature on plans for mailboxes location and show
box standard detail on olans
As previousely requested please show all of the short
plat conditions of approval, this is not shown on sheet
1 O as vou mentioned in vour resoonses
The sheets index makes a reference to sheets 2 & 3
that are missing from the plans set, please provide
~rn@rnowrn@
JUN 3 02009
KC. D.D.E.S.
Page 1 of 8
Consultant Response Date:
Name:
This has been changed to Mark X. Plog. PE. PLS
This has been revised to have the hand written
exoiration date as reouired
This has been corrected
Detail has been added and plans have been
submitted to postmaster for approval. Approval will
be provided with next submittal.
The conditions of approval have been added to the
plan set and are found on sheet C 1
The plan set has been completely revised and the
index has been updated to reflect the new plan set
sheets.
Complete
IY/Nl
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: N/NI
New Sheet 1 As previousely requested, please provide Horizontal The Horizontal Control Plan has been incorprated into
Control Plan sheet, on this sheet show the proposed the new plan set as requested.
short plat layouts with proposed access road, show lot
lines, tract lines, easement lines, access road
centerline, with complete survey information (bearing,
distance, and curve information). This plans sheet
needs to be consistent the preliminary short plat map.
Also, on this sheet show section and quarters
monumnet and section ties information
Sheet4 1 Please show interceptor swales and sediment trap The interceptor swales and sediment traps have been
with section details to control surface flows druing indicated and a construction sequence has been
construction acitivites. On this sheet please show the provided.
construction senuence notes
2 As previously requested please show the correct This has been corrected
plans approval block on the plans sheets (see redline
markun\
3 As previously requested, please make sure all texts This has been corrected
sizes are adequate and clearly read, also please
check your plans to eliminate all text overlaping.
4 Please show existing utility poles to be relocated per The utility pole relocation has been indicated
the 1993 King County Road Standards (KCRS)
Sheet 5 1 Please show the on-site access centerline station and This has been provided
ROW station in nrofile view
2 Show 120th road name and road classification in bold This has been provided
font
Page 2 of 8
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: fY/NI
3 As previously requested please add the following note This note has been added.
on the plans sheet: Per KCRS Section 4.01F, a 1
inch full width overlay shall be required.
Appropriate repairs to the existing subgrade,
base material, surfacing and pre-level may be
required prior to placing the overlay. The overlay
may be waived only upon written request and
after an evaluation of pavement conditions and/or
channelization requirements has been completed
and approved by the County Road Engineer or
Development Engineer.
4 As previously requested, please show turning radii This has been provided
edge of pavement for the on-site access approach at
16-feet from 120th ROW centerline (see redline
markuos)
5 There at least 100-feet of the required paved walkway The walkway has been widened where adjacent to the
not being separated by ditch from the travel lane, this existing roadway.
portion of the walkway shall be 5-feet wide, pleas
address this issue properly (see redlines)
6 Please show sidewalk to shoulder transition ramp with This has been provided with a callout.
standard detail !see redlines\
Sheet 6 1 Please show walkay improvement end station in This has been provided.
orofile
2 Please revise plans to show new fence installation This has been indicated on the plans.
within orivate oronertv instead of KC ROW
Sheet 7 1 Please show the proposed storm drain sturctures This has been provided.
such catch basins and manholes information in plan
and profile views. Please show CB number, stations,
stations off-set, rim elevation, pipe invert elevations,
pipe size, pipe direction, and pipe type (please show
this information in the format shown in red on plans)
2 As previously requested, it is improtant that all of your Flow arrows have been provided.
plan sheets clearly show the directional flow arrows
for all storm drain pipes, please clearly show
Page 3 of 8
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: IY/NI
3 Please remove the water and sanitary sewer Left as background only
imorovements from all plan sheets.
4 In profile view , please label all pipes & road design The slopes have been labeled
nrade slooes as S = slope
Sheets 8 & 9 1 Strom system information shown on these plan The storm system has been simplified to eliminate the
sheets are unclear and very confusing. Please show flow splitter and to provide a combined
flow directional arrows for all pipes, unless there is treatment/detention vault as suggested.
specific reason why wetvault and detention vault
cannot be combined, the plans shall be revised to
show one Combined Wet-RD Vault system. Also,
flow splitter is not needed for this project, plans shall
be revised to show one vault system to treat and
control flows consistent with the 1998 King County
Surface Water Design Manual (KCSWDM) guidlines.
2 Please revise the profile design to show one This has been provided.
combined profile, this can be easly accomplished on
the plan sheet. Show complete structure information
as shown in red on clans.
3 Plans must be revised to elinimate all text This has been done.
overlannino this shall be done on Plan sheets
4 As previously requested, the proposed spreader The spreader has been previously approved as part
system will not be accepted because it will allow of the COA.
sheet flow over adjacente property roadways (private
or public), please revise plans to show tight line
instead
Page 4 of 8
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: IY/NI
5 As previously requested, please submit easement This easement has been provided for review.
documentation for proposed strom easement for
review bv Kina Countv
6 Provide section details to show adequate information Pipe crossings have been eliminated on the new plan
at pipe corssings, and make sure that at least 1.0' set.
seoaration is orovided between oines
7 Please revise your plans to eliminate many of the This has been done.
storm by-pass pipes, and keep in mind that all
impervious surfaces including but not limited to on-
site roof tops must all be routed to one on-site
Combined Wet-RID vault system, this can be easly
accomnlished so olease nrovide.
8 Clearly show limits of proposed landscape tract This has been done.
encumbering drainage easement to King County for
the orooosed vault svstem
9 Clearly identify the location of the control structure, This has been done.
show maintenance access to this structure, and show
removable bollard at the access entrance with
standard details
10 Please provide separate profile design for the The bypass has been eliminated
orooosed bv-oass svstem
11 Show S'X 1 O' maintenance access opening for the This has been provided.
second cell of the wetvault
12 Show gravity drain line with valve for the proposed There is not sufficient fall to provide a drain for the
wetvault. see section 6 in the 1998 KCSWDM wetvault.
13 Show footing drains for the vault system(s) and show This has been provided
its downstream discharge location in plan and section
views
TIR 1 All hand written calculations must be legible and very The TIR has been revised and no hand calculations
clear to read, this is critical because the TIR are included.
document will be microfilmed eventually and hand
written information cannot be read if it is not clear in
the original document, please print or legibly write all
calculations
Page 5 of 8
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: IV/NI
2 Please check your area calculations for the The TIR areas and calculations have been completely
developed conditions, hand written calculations revised.
information is not consistent with information provided
for peak flow calculations. Also there should be no
pasture ground cover in the developed conditions
area calculations, please revise accordingly
3 In TIR please place all your area calculations ahead The TIR has been revised to a more traditional
of the RID desian calculations. format.
4 Since frontage road improvments are not routed to The design and calculations have been revised to
the proposed on-site RID facilities, By-pass eliminate the bypass.
calculations shall be included in the vault design
calculations. This was considered in the previous
submittal and need to be included in the revised TIR,
please revise all of the RID system design
Mlcula•ions as ne.,ded
5 Also, please re-arrange the program print out sheet The TIR has been revised to a more traditional
sequencs, it appears mixed up and very confusing format.
6 Please note that the vault design calculations are The revised vault calculations and design have been
based on 130' long X 1 O' wide X 1 O' deep structure updated to coordinate.
resulting in 13,000 c.f. of live storage, however the
required peak reservior storage volume is 13,138 c.f.,
please revise your calculations to make sure that live
storage volume is equal to or greater than the peak
reservior volume, see redlines
7 As previously requested, please show all of the short This has been provided.
i plat conditions of annroval in Tl R
8 Please revise the wetvault design calculations to This has been provided.
include impervious surface areas for proposed roof
toPS in the develoned conditions
9 Include By-pass area calculations and By-pass peak Bypass has been removed
flow calculations
10 Provide actual computer print out for the facility This has been provided
performance curve instead of nrint screen
11 Please provide sediment trap design calculations in This has been provided
TIR
Page 6 of 8
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: IV/NI
12 Please provide standard size for the engineer stamp This has been provided
in TIR, show acutal signature (signature copy will be
accepted), and remove the exipration date from the
stamo
13 Please revise the bond calculations as needed The calculations have been revised.
General 1 Please provide written agreement from adjacent The owner will provide this documentation as soon as
property owner to the south for work associated with possible.
grading and clearing improvements, such as fence
relocation
2 Please provide easement documentation for This has been provided
proposed downstream drainage system for County
review
3 Please provide separate landscape plans with This has been provided under separate cover by the
separate application for review, please submit as owner.
soon as nossible.
4 Provide wetland report for adjacent wetland to the This wetland is exempt per the COA.
east, and show wetland buffer and BSBL lines on all
related nlan sheets
5 Provide 3 copies of Structural Plans and calculations Vault structural plans will be provided once the TIR
for the proposed storm water vaults calculations have been reviewed and approved by the
drainane reviewer.
6 Please show street plans A separate road plan has been added
7 Please provide 4 copies of separate Significant Trees A Tree Retention Plan has been provided as part of th
Retention Plans olan set.
8 Please refere to plans and TIR redline markups and This has been done.
revise accordinalv
9 Please submit 3 set of revised plans and TIR for This has been done.
further review by the County along with all plans and
TIR review redline markuos
10 Please provide list of responses to this list of review This has been done.
comments, and indicate how, and where (on what
sheet\ each item has been addressed
11 Prior to your next submttal please make sure all items Noted.
listed are properly, adequately and completely
addressed, this will help completing review with
approved budget, otherwise additional fees payment
may be needed if exceeded budget hours
Page 7 of 8
Sub Code Review Comments Consultant Response Date: Complete
Item Item Reference Name: IV/NI
12 Please call me if you have any questions and lets Thanks!!!
discuss all issues before resubmittal, I will be happy
to assist
Page 8 of8
ti
KingCounty
Department of Development
and Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-1219
Date: December 31, 2008
.I ennifer L. Argrades, P .E.
North Cascades Engineering,
P. 0. Box 309
Winthrop, WA 98862
RE: Hitone Short Plat
L04S0065,L07SR019
Dear Mrs. Argrades,
Our office has completed the Second review of engineering plans for the Hi tone Short Plat. The
attached list of review comments dated December 31, 2008 provides summary of design issues
which must be addressed in your next submittal. The review comments are based upon the
design plans and technical information report received on December 17 and 29, 2008.
Once the second review comments have been addressed, please submit 4 sets of revised plans
and technical reports. To assist in reviewing the revised plans, the design engineer should
prepare a written response for each issue identified in the attached comments .. If you desire an
electronic copy ofmy review comments, please send an email to mazen.haidar@kingcounty.gov.
If you have questions regarding the design requirements for the project, please contact me at
206-296-7133 for assistance.
~;,g
Mazen Haidar, P.E.
Review Engineer
Enclosure
cc: Mr. Anthony Ford, Owner
I 1--~---'-.,--i
R-6
<i t-----1
"" ..., ...,
LL
.c:
__J:c----1--,
n
R-6
! \
\
\
I
\ ' I ----\ f
' ' ,,
Ji I _ \I
~L _/ _
' : 1--------\
' :I----~
' '
.c:
Hitone
L07SR019
NTrails l Schools/School Facilities
NTownshiplines
S-T-R
, n ,, • QSLINES
~SECLlNES
TWPUNES
N""""
SAOS!ream M,1 ~~ N>
,",:u
~ SAOWel!and(199B)
' Watsr Bodies
D Road Righ~-Way
CJ""" o-r--Forest(< 20 aaes)
Greon""'
Forest/Designate
'""""""' Ag./No Dev. Rights
O::nvnercial o.s.
o-
CJ"""
0 200 400 Feet
1"=417feel
t&1 KllleCountJ
rt.inkrmalion inc::ludod an a. map 11M -~ by
King Co.tty' a1llt'I from • nnflly.,, _ -ia ~ to
change .. lhout nobce. King c...nty m&u no
-~.,,_...,_.,__...-rnplied,atolh!I
...,,.....,,_.......,..___ ~.ornglbtoll"e.-of
tu<:h inl,;rmatian. King Coi.ny .,.... not be bble !of .-.y
--'· opecial, indired. lncldenlal. ot~
--ircl.dng, tulnatlirMo<I to. losl-ct losl
profits ru~ting from Iha UM or m, .... of the information
~ on lt'Q map. My .... of 11,ia map ct infcnnaticn
an Iha map ia f:fd-...:1 ucep1 t,y ...,u., pennioaicn of
'""" Plot elate: Aug 4, 2009; l'dcie$001\idl1'viS\4Y_dev\projeds\base2..ai:,r
V
ti
King County
Department of Development
and Environmental Services
900 Oakesdale Avenue Southwest
Renton, WA 98057-5212 ·
206•296-6600 -lTY 206-296-721-7
www.metrokc.gov
November 20, 2008.
Steven Wade Terrell
Terrell Design Group
923 NW SO'h Street
Seattle, WA 98107
RE: Recreation Plan, KC File L08MI051
Hitone (a.k.a Yee) Short Subdivision
KC Files L04S0065
Dear Mr. Terrell:
I have reviewed the recreation and landscaping plan dated July 24, 2008 and have the
following comments:
1. Please show the dimensions and area calculation for the combined drainage and
recreation tract. Please note that at a minimum, 2,340 square feet shall be
allocated for recreation. The grass-paved driveway to access the drainage vault
cannot be included within the required area. The area allocated for recreation
could include landscaping buffers. No dimension of the recreation tract can be
less than 30 feet.
2. At a minimum a 400-square-foot tot lot area must be provided. The proposed
215-foot toddler area (sand box) is inadequate and does not meet the code. In
addition to the tot lot area, one additional recreation facility must be provided
per KCC 21A.14.180.E2. A pull bar as the only recreation structure does not
meet the code requirement. A basketball court or a picnic area with tables and a
large grassy area for throwing a baseball or Frisbee may be acceptable for a
recreation facility.
3. Please show fencing around the entire perimeter of the tract except the street
side. The fencing along the boundary of the tract and Lot 6 may be 4-feet high
and see-through.
4. Landscaping notes must include the type and method of irrigation.
5. The proposed improvements must not conflict with the engineering requirements
for the drainage facility or its maintenance. Normal maintenance includes
I . • ••
driving heavy equipment up to the access point, opening vault access points and
lowering equipment into the vault to remove sediments. Please show the vault
access points for maintenance and any other drainage related structures that will
be part of the recreation tract.
Please submit the following by December 22, 2008:
L
2.
3.
4.
5 copies ofa revised final-recreation plan, addressing the-items referred-above
5 copies of a revised Bound Quantity Worksheet for the landscaping and
other improvements
5 copies of play equipment and recreation tract furnishings specifications
A copy of this memo
If you have any questions regarding this letter, please contact me at (206) 296-7173.
Sincerely,
'-:)-~l?~
Fereshteh Dehkordi, Project Manager
Current Planning Section
Cc: Antony Ford, Applicant
Lanny Henoch, Project Manager III
Angelica Velasquez, PPM II
Mazan Haidar, Engineer, Engineering Review Section
L07SR019 File
ti King County
Department of Development
and Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-1219
Engineering Review Comments
Project Type: 6 lots Short Plat RevieviDate: 12/31/2008 Reviewer Name: Maien Haidar; P.E.
,. < ., ,_ • • • • '. '" •
Project Name : Hitone Short Plat R11~ie,y.' No.: 2nd Email : mazen.haidar@kingcounty.gov
Project Number : L04S0065 Phone : (206) 296 -7133
Activity Number: L07SR019 . · F.ax: (206)296 -6613 Project Manager: Pete Qye; P.E.
' . .~ -------· •. ____ ,•=.:_ ., .. ,._., ..•.•
Sub Code ·. Review .. Comments ConsultanfResponse Date: ·
Item Item Reference Name:
Sheet 1 1 In the approval block on the Cover Sheet as well as
other plan sheets, please change the Development
Engineer name to show Molly A. Johnson, P.E. (see
redline markuos)
2 Please remover vour stamp exoiration date
3 Please provide actual signature on your stamp,
signature copies will not be accepted, and your stamp
must reflect your registration number very clearly
'currentlv hard to read\
4 As previousely requested, please provide the United
States Postal Services (USPS) approval stamp and
signature on plans for mailboxes location and show
box standard detail on "lans
5 As previousely requested please show all of the short
plat conditions of approval, this is not shown on sheet
1 O as vou mentioned in vour resconses
6 The sheets index makes a reference to sheets .2 & 3
that are missing from the plans set, please provide
Page 1 of 8
Complete
IV/NI ..
Si.lb Code Review Comments ... ~~~"~!,t~nt,Response Date: .. •·· .· :: ',~/,!\:· Completet
Item Item Reference .. ame:· ·-, -, :r.i1N{)i
New Sheet 1 As previousely requested, please provide Horizontal
Control Plan sheet, on this sheet show the proposed
short plat layouts with proposed access road, show lot
lines, tract lines, easement lines, access road
centerline, with complete survey information (bearing,
distance, and curve information). This plans sheet
needs to be consistent the preliminary short plat map.
Also, on this sheet show section and quarters
monumnet and section ties information
Sheet 4 1 Please show interceptor swales and sediment trap
with section details to control surface flows druing
construction acitivites. On this sheet please show the
construction seauence notes
2 As previously requested please show the correct
plans approval block on the plans sheets (see redline
markuc)
3 As previously requested, please make sure all texts
sizes are adequate and clearly read, also please
check your plans to eliminate all text overlaping.
4 Please show existing utility poles to be relocated per
the 1993 King County Road Standards (KCRS)
Sheet 5 1 Please show the on-site access centerline station and
ROW station in profile view
2 Show 120th road name and road classification in bold
font
Page 2 of 8
Sub Code ' ·:· · .. ' ,._ Review Comments CorisultantResponse·Date: . . _'(' . :> Complete·
Item Item Reference ' . : .: ._ ._;,.,' Name: .. IY/NI' e. "'· ••
3 As previously requested please add the following note
on the plans sheet: Per KCRS Section 4.01F, a 1
inch full width overlay shall be required.
Appropriate repairs to the existing subgrade,
base material, surfacing and pre-level may be
required prior to placing the overlay. The overlay
may be waived only upon written request and
after an evaluation of pavement conditions and/or
channelization requirements has been completed
and approved by the County Road Engineer or
Development Engineer.
4 As previously requested, please show turning radii
edge of pavement for the on-site access approach at
16-feet from 120th ROW centerline (see redline
markuos)
5 There at least 100-feet of the required paved walkway
not being separated by ditch from the travel lane, this
portion of the walkway shall be 5-feet wide, pleas
address this issue properly (see redlines)
6 Please show sidewalk to shoulder transition ramp with
standard detail (see redlines\
Sheet 6 1 Please show walkay improvement end station in
nrofile
2 Please revise plans to show new fence installation
within orivate orooertv instead of KC ROW
Sheet 7 1 Please show the proposed storm drain sturctures
such catch basins and manholes information in plan
and profile views. Please show CB number, stations,
stations off-set, rim elevation, pipe invert elevations,
pipe size, pipe direction, and pipe type (please show
this information in the format shown in red on plans)
2 As previously requested, it is improtant that all of your
plan sheets clearly show the directional flow arrows
for all storm drain pipes, please clearly show
Page 3 of 8
Sub Code Review ComlTleilts ConsultaritRespo11se Date: ... ::··j'>;'' ' Complete· . . . . ' .
Item Item Reference Name: ·· · · IV/NI .. ·
3 Please remove the water and sanitary sewer
imorovements from all olan sheets.
4 In profile view , please label all pipes & road design
nrade slooes as S = slooe
Sheets 8 & 9 1 Strom system information shown on these plan
sheets are unclear and very confusing. Please show
flow directional arrows for all pipes, unless there is
specific reason why wetvault and detention vault
cannot be combined, the plans shall be revised to
show one Combined Wet-RD Vault system. Also,
flow splitter is not needed for this project, plans shall
be revised to show one vault system to treat and
control flows consistent with the 1998 King County
Surface Water Design Manual (KCSWDM) guidlines.
2 Please revise the profile design to show one
combined profile, this can be easly accomplished on
the plan sheet. Show complete structure information
as shown in red on nlans.
3 Plans must be revised to elinimate all text
overlanninn this shall be done on olan sheets
4 As previously requested, the proposed spreader
system will not be accepted because it will allow sheet
flow over adjai:ente property roadways (private or
public), please revise plans to show tight line instead
Page4 of 8
Sub · Code Review Comments Cons.liltant Response Date: .. Complete
Item Item Reference Name: IY/Nl
5 As previously requested, please submit easement
documentation for proposed strom easement for
review bv Kinn Countv
6 Provide section details to show adequate information
at pipe corssings, and make sure that at least 1.0'
seoaration is orovided between oioes
7 Please revise your plans to eliminate many of the
storm by-pass pipes, and keep in mind that all
impervious surfaces including but not limited to on-
site roof tops must all be routed to one on-site
Combined Wet-RID vault system, this can be easly
accomnlished so olease orovide.
8 Clearly show limits of proposed landscape tract
encumbering drainage easement to King County for
the orooosed vault svstem
9 Clearly identify the location of the control structure,
show maintenance access to this structure, and show
removable bollard at the access entrance with
standard details
10 Please provide separate profile design for the
nronosed bv-nass svstem
11 Show 5'X10' maintenance access opening for the
second cell of the wetvault
12 Show gravity drain line with valve for the proposed
wetvault, see section 6 in the 1998 KCSWDM
13 Show footing drains for the vault system(s) and show
its downstream discharge location in plan and section
views
TIR 1 All hand written calculations must be legible and very
clear to read, this is critical because the TIR
document will be microfilmed eventually and hand
written information cannot be read if it is not clear in
the original document, please print or legibly write all
calculations
Page 5 of 8
Sub' Code I .. Review. Comments Consultant,ResponseDate: ' --< • --.~-: Complete
Item Item Reference -' Name: .. ;·. ·.·}
IY/N\
2 Please check your area calculations for the developed
conditions, hand written calculations information is not
consistent with information provided for peak flow
calculations. Also there should be no pasture ground
cover in the developed conditions area calculations,
please revise accordingly
3 In TIR please place all your area calculations ahead
of the RID desion calculations.
4 Since frontage road improvments are not routed to
the proposed on-site RID facilities, By-pass
calculations shall be included in the vault design
calculations. This was considered in the previous
submittal and need to be included in the revised TIR,
please revise all of the RID system design
calculations as needed
5 Also, please re-arrange the program print out sheet
sequencs, it appears mixed up and very confusing
6 Please note that the vault design calculations are
based on 130' long X 1 O' wide X 1 O' deep structure
resulting in 13,000 c.f. of live storage, however the
required peak reservior storage volume is 13,138 c.f.,
please revise your calculations to make sure that live
storage volume is equal to or greater than the peak
reservior volume, see red lines
7 As previously requested, please show all of the short
olat conditions of annroval in TIR
8 Please revise the wetvault design calculations to
include impervious surface areas for proposed roof
toos in the develooed conditions
9 Include By-pass area calculations and By-pass peak
flow calculations
10 Provide actual computer print out for the facility
nerformance curve instead of orint screen
11 Please provide sediment trap design calculations in
TIR
Page 6 of 8
Sub Code · Review Comments . ,' .. , ·~'. ·: .. " Co['sultant.Response Datil:"\«··· . ' ,Complete
Item -Item Reference . Name: . . . . · ·:: IV/NI
12 Please provide standard size for the engineer stamp
in TIR, show acutal signature (signature copy will be
accepted), and remove the exipration date from the
stamn
13 Please revise the bond calculations as needed
General 1 Please provide written agreement from adjacent
property owner to the south for work associated with
grading and clearing improvements, such as fence
relocation
2 Please provide easement documentation for
proposed downstream drainage system for County '
review
3 Please provide separate landscape plans with
separate application for review, please s_ubmit as
soon as nossible.
4 Provide wetland report for adjacent wetland to the
east, and show wetland buffer and BSBL lines on all
related nlan sheets
5 Provide 3 copies of Structural Plans and calculations
for the nrooosed storm water vaults
6 Please show street plans
7 Please provide 4 copies of separate Significant Trees
Retention Plans
8 Please refere to plans and TIR redline markups and
revise accordinalv
9 Please submit 3 set of revised plans and TIR for
further review by the County along with all plans and
TIR review redline markuns
10 Please provide list of responses to this list of review
comments, and indicate how, and where (on what
sheet\ each item has been addressed
11 Prior to your next submttal please make sure all items
listed are properly, adequately and completely
addressed, this will help completing review with
approved budget, otherwise additional fees payment
may be needed if exceeded budget hours
Page 7 of8
Sub Code ·. ·.~ Review Comments ~onsultant Response Date: .•S-· ! complete
Item Item Reference . ,. . Name: . tv/Nl
12 Please call me if you have any questions and lets
discuss all issues before resubmittal, I will be happy
to assist
Page 8 of 8
' .. •. ' ...
Dye, Pete
From: North Cascades Engineering, PLLC [sukoargr@methow.com]
Sent: Monday, May 07, 2007 2:11 PM
To: Dye, Pete
Cc: Tony
Subject: [Spam) Hitone Short Plat -Engineering Activity# L07SR019
Hello Peter,
Page 1 of2
Thank you for your time today to discuss the Hitone Short Plat letter dated April 27, 2007. The following outlines
some of our correspondence with the County including timeline, used as the basis of our design. This is an attempt
to respond to your statements included in the Hitone Short Plat letter dated April 27, 2007.
Items 7, 8 and 9: Plan Revision for change in stonn drainage, stonn drainage easements on lots, and
downstream drainage:
The original Short Plat showed a detention tank and underground treatment facility. In late November of ,2007, we
found the downstream conveyance system would not be completed at the time of our engineering review. So, for
the Owner to proceed with his project an above ground system was designed per King County's 1998 standards.
We contacted the County to see if we could place the detention_and water quality in a SD easement over a
residential lot. It is our understanding from the 1998 King County Manual the detention pond must be in a
dedicated Tract ifit is to be maintainedby the County. Thus, if this is a privately maintained facility it would not have
to be in a Tract.
We spoke with Kate Roads (206-296-8046) on 12-12-06 and discussed several options for storm drainage system.
She stated the County prefers all SD to be in one tract but SD easements on lots are allowable. She also stated
the system we design must function as a complete system now. The owner, at a future date when the downstream
conveyance system is available, will potentially put the detention and WQ below ground, thus reclaiming the lot area
the SD easement currently occupies. So, the system we designed is a stand alone system.
Short Plat Condition 4, part D, states we would have to submit a revision to the application with a new conceptual drainage
plan. We contacted the County again to see how to proceed. We did not know if the revision was a formal Revision
or exactly what we were required to do. We first contacted Freeshteh Dehkordi in late November she referred us to
Curt Foster. Curt was unsure and was going to check with someone else in his office. He said a formal Revision is
normally needed when the number of lots change. ~ e still had 6 lots _with Lot 5 partially impacted and Lot 6
completely impacted by the storm drainage.) He called back and referred us on to Kim Clauson (206-296-7167).
We spoke with Kim Clauson on 12-06-06. She said to submit extra copies of our plans to engineering and they
would let us know if additional information was necessary. She did not think a formal Revision would be required.
Item 10: No road access to SD oudet:
This will be included when the plans are re-submitted.
Item 11: Cul-de-sac design does not meet Kf3'Sliii1dards:
We coordinated with Chris Langly (206-296-7155 or 206h63-61'0~oh several occasions (10-30-06, 10-31-06
and 12-12-06) to determine the road and cul-de~sac desigh elrments. I\-re island the only design standard we are
not meeting? An island is not required for this r~ad classification. We pilt it in as a WQ element. The required
changes will be included when the plans are re-sub1niit!~di ) . • '\
l, ·, l
\ . ._J.
Thank you for working through this process with us. Plet?r:?rll me-at 509-996;;2252 1f you have any questtons,
05/07/2007 .
( )
•
need additional information, or when you determine how we need to proceed.
Sincerely
Jennifer
Jennifer Argraves, PE
Principal/ Civil Engineer
North Cascades Engineering, PLLC
PO Box 309
Winthrop, WA 98862
509-996-2252
206-669.-5792 cell
05/07/2007
i
' . ' _,J
Page 2 of2
• ®
King County
Department of Development
and Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-1219
April 27, 2007
Heidi Kuehnienz
413 South 4 7'11 Street
Renton, WA 98055
RE: Permit Fee Estimate
Project: I-litone Short Plat
Engineering Activity: L07SROI 9
Dear Applicant:
.,.
Thank you for submitting the engineering plans for site development of the I-Ii tone short
plat. To implement the engineering review process, our office will use a new procedure
for managing the permit application to provide applicants with an enhanced level of
customer service. A project manager will be assigned to your project to provide a fee
estimate for the anticipated scope of review and will also monitor and manage the permit
application throughout the review process.
Your application for engineering review was received by our office on March 30, 2007
and will be processed using the Project Manager Program. The enclosed information
provides a summary of the fee estimate for the anticipated work disciplines and also
discusses the submittal process and disclaimers which may affect the final permit fees.
The fee estimate includes the scope of work for engineering plan review only and does
not evaluate other final plat requirements such as construction inspection and review of
plat recording documents.
During our initial screening process of the engineering plans, it was determined that the
short plat has been significantly changed since preliminary approval and the designs are
not acceptable for engineering review. The original short plat proposed a detention vault
located beneath the roadway and recreation tract; however, the current design shows a
storm pond and bioswales located within the lot areas which does not meet County design
requirements. In addition, several other design requirements for roads and drainage do
not meet County standards. The design items identified during the screening
process which do not comply with County standards are listed as disclaimers on the
attached fee estimate form. Due to the missing information, the fee summary is a rough
estimate and is subject to modification based upon the disclaimers noted in the fee
estimate form.
Heidi Kuehnienz
April 27, 2007
Page 2
Before continued review of the engineering submittal, the site plans must be revised to
correspond with the original design concept for the preliminary short plat or an
application for short plat revision must be submitted to the planning section in our office.
The short plat revision is also noted as arequirement in short plat condition 4 regarding
the offsite drainage pipe which is not addressed on the current design plans. Please
contact the project planner Fereshteh Dehkordi at 206-296-7173 to discuss the
requirements for a short plat revision. The short plat revision must be processed before
any further review of the engineering designs.
In addition to engineering design documents, our Department must also review and
approve the recreation space plan as required by short plat condition 13. Please be
aware that the recreation plan must be submitted to our planning section as a
separate permit application with fee payment. The requirements for submitting recreation
plans may also be discussed with Fereshteh Dehkordi at 206-296-7173.
Our current records for the short plat do not list your name as the original applicant. If
the property has changed ownership, the enclosed Transfer of Applicant Status Form
(CASF) must be provided in your next submittal. Once the attached fee estimate form is
signed and submitted to our Department along with the estimated fee payment, applicant
status form, and revised engineering plans, your project will be assigned for further
review. All fee payments shall be made to the cashier in the DOES permit center using
activity number L07SROl 9 and other forms or plan documents shall be submitted to my
attention in the Land Use Services Division.
If you have any questions regarding the permit fees or other aspects of the engineering
review process, please contact the project manager, Pete Dye via email
pete.dye@metrokc.gov or by telephone at 206-296-7185.
sffJ
Peter D-t:.E.
Senior Engineer
Enclosure
cc: Jennifer Argraves
(® King County
Land Use Services Division Permit Fee Estimate
Pre-app Estimate Number: L07SR019 Date: 04/27/07
Permit Title: Hitone Short Plat
Permit Type: SITEREVS -Engineering Plan
· Based on permit information submitted by the applicant, the Department of Development and
Environmental Services (ODES) has determined the amount of review fees for the subject application.·
The fees shown below do not include ancillary permit fees, recording fees, project-related mitigation
fees, or other fees that are passed through to the.applicant from other agencies or as part of the project's
environmental review.
Fixed Fees:
Counter Service Fee for Application Intake
Tree Retention Review
Structural Review (Fees determined before plan approval)
Other Fixed Fees
Estimate for Hourly Fees: (] 53 Hours x $144.90)
Fee Deposit Paid
Total Fixed Fees:
Total Permit Fee Estimate:
$205.28
1,086.75
$
$1,292.03
$22,169.70
-$784.88
$22,676.85
Note: The estimate for hourly fees stated above is based on the total estimated number of hours not to
exceed 153 hours for the disciplines listed below, and is calculated using the department's hourly rate in
effect at the time the work is performed. Based upon the financial disclosures found on page 2, the
number of hours required may be modified. The total estimated hours reflect work performed by the
following disciplines: Engineering Review, Survey Coordination, Project Management,
Constructabi!ity, Traffic Review, Planning, and Geotechnical Review.
After receiving the fee estimate from ODES, the applicant has ninety (90) days to complete the
application submittal. Please call 206-296-6797 to set up an appointment with the Permit Center to
complete your application and payment. If the application is not received within ninety (90) days, the
applicant may be required to obtain a new fee estimate or this activity may be cancelled.
For further questions on this fee estimate or for other requirements about this permit application, please
contact Pete Dye via email pete.dye@metrokc.gov or by telephone at 206-296-7185.
Peter Dye, P. E.
Senior Engineer
Land Use Services Division
Project Manager.dot 1/26/04 Page I
.. . . '
@ King County
Land Use Services Division Permit Fee Estimate
Engineering Activity No.: L07SR019 Date: 4/27/07
Permit Title: Hitone Short Plat
Permit Type: SITEREVS -Engineering Plan Estimated Maximum Hours:153
Applicant: Heidi Kuehnienz Total Fee: $22,676.85
The following d1scla11ners are attached and are part of the fee estimate for this permit. The appltcant is
required to submit a signed copy of this form with the application and fee payment acknowledging that.
the applicant has read the disclaimers stated below.
· Disclaimer
Applicants are responsible for all fixed fees, reported hours performed in reviewing submittal materials
and processing, up to the fee estimate. Changes in the scope of the project review will result in a revised
review fee estimate. Fee estimates are based on information submitted to DOES by the applicant prior
to finalization of the permit application. In addition, estimates are determined by utilizing historical
data gathered from projects of similar type, size, and scope. The fee estimate will be the maximum fee
charged unless the scope of the project changes. Should fewer hours be required to complete the
review, then the applicant may receive a refund for those hours. If items are identified that are not
originally disclosed or identified later in the process, a new estimate may be required. Applicants will
be responsible for any additional hours identified in a new estimate because of:
I) Changes in the project and unknown or undisclosed site issues.
2) Incomplete information or errors in applicant submittal.
3) County code fee changes.
4) Fees for Forest Practices Permit if determined necessary.
5) Fees for variance applications and/or structural permit review.
6) More than one major and one minor set ofredline corrections.
7) Short Plat Condition 4 -Downstream drainage issues not resolved.
8) Drainage facilities must be removed from lot areas.
9) Short Plat Revision required to address modified drainage designs.
l 0) Road access not provided to drainage outlet structure.
11) Cul-de-sac design does not meet design standards in KCRS 2.08.
Keeping review fees at or below the fee estimate will depend on the applicant's commitment to
complete the process review. This commitment should include submitting materials which address
· all County codes, policies, previously approved conditions, and responding to the County's request
for corrections or additional information in a timely manner, not to exceed 90 days.
Acknowledged: Applicant/Owner Name (print)
Date: ___ Applicant/Owner Name (signature)
Project Manager.dot 1/26/04 Page 2
-·
~
tQ
KingCounty
Department of Development
And Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-5212
206-296-6600 TIY 206-296-7217
www.kingcounty.gov
' ~rn@rn~wrn@
OFr. 't. Y 7008
K.C. D.D.E.S.
Engineering Plans Review Comments
Project Type :
Pr6ject N~me :
. 6 Lots Shoi:tPlat · Review .. Oatei: · 12-27-2007 Reviev.ier-'Name : ;Maze~ l:laida( R:E:, ; ·.·
. Hitone SP Y. · Revi~:;_. No. l / . 1 s Emailfr·'} •·.. · · ,'•.maien:h~ictar@rrietrokc.gov .
. Pr6j!icfNiJmber :
Xtfi;ify'Nuinber:
L04S0Q65/i > '' ' Ph&ne.: : . . (206f296; 7J;3_3;\\ .
L07S80l9 '. . . ~~,e;} ·i'.). (206) 206'}..f:l6l3i;,; :.:
' .,-'-:~ .:.:,-:<!:::·· I; ',, ' ', ' .. ·' ; \>. \),, '. , ... I· Sub o: < .
R~flil''!nce · . Review c&nimerits . · Consultant Response• ,·. · Back Item Check Item· · · · _·":/}:~f.-r:.-.:-:?::_f,~-;~_--• .;_... . ~ .. .. '-.
. ·-:: . ; .. ~-: . ' ' ;, .•.. <·-_'.· "
Sheet-1 1 Please show the short plat conditions of approval ~vvEv To s\-1-£1:.:r lo,
2 Provide parcels information on plan ~\:>VE-D 'y~~C.E. \.. N \) t,/'\ 01:-i. ~ .
3 Show soils map for th~ subject site ':)01\..~ N'\~7 1>s.roso.
4 Show the United States Postal Services Approval stamp
and signature for mailboxes location, show mailboxes on f\uu.=0, '::, C. t=-S 1-t E:. E.:, 8 P,.,.-M O I \ plans with standard detail
5 Label sheet as cover sheet \'\E-1'.lf'\),('-.,e-v sr1sET.
Sheet-2 1 Please show north arrow and scale =:> £ £ 'h iz..v I <-,,1.-Q 5 L,) il.. \/ I:. '(
3 Show and label utility easement /I I I If
4 Please make sure all text fonts are large enough to read I( I( I I
5 This sheet should reflect existing site conditions, shouid
I I show existing site features and parcel boundaries, and I{ 1/
section / ouarters monument ties, etc.
~.
Sheet 1 of 6
.......
~ '
' '
King County
Department of Development
And Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-5212
206-296-6600 TIY 206-296-7217
www.kingcounty,gov
'
Sub
Reference Item
· Item
'
Sheet-3 1
2
3
4
5
6
7
8
9
10
Sheet. 4 1
2
' ; ,t '
·. Revi~w Comments
Please make sure the engineer stamp is clearly
readable on all plan sheets
Please show the County plans approval block on all plan
sheets except the cover sheet, see redline markup
Show and identify all off-site easements, show
easement type and width
Use four digits for centerline stationing Le. 15+00
instead of 15
Please avoid text all overlapping on all plan sheets
Show and label drainage facilities within public drainage
easement, the drainage easement should be located in
a Recreation Tract '
Clearly label and identify new grade lines (contour lines)
Combine the road, drainage and grading improvements
on one plan sheet
Show complete Cul-De-Sac centerline information, see
redline markups
Show north arrow and scale on plan ·
Please re.move proposed improvements from this plan
sheet, show TESC measures,
Re-label construction dispersion trench as Interceptor
Trench and show its location on plan
Sheet 2 of 6
S f Yt<~ 1 (t::
' .... ,. f. •· ... ·
Back . ,,._,:: .
· Consultant Response Check
' ,'
~Sc R i'a." I';;, •'i-0 "b u.,.:,J '=-'i ( S,-5, ~ J"A(Y,' x
\\ \ \ \ ,
' I
\ I ,, ' \ I \
' I i\
,, ,,
' I I I', I I
\( \ I I \ '
H I I, I I '.
I I l I ' \ . "
I I I ! \ \
I \ t I ' ' I I
l IV\ ?Ro" E.N\ c 1-\ '1 S V, c iAov s 'v
:[ N 1E:.,,i,(.,,2.-r,o R., 1i\,o,,'\(,,I,\-SU N,.I ),\~~,
',t.
;::,__
-~-. .
:t{' ~';
King County
Department of Development
And Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-5212
206-296-6600 nv 206-296-1211
www.kingcounty.gov
Sub
Reference Item
Item
2
3
Sheet -5 1
2
3
4
5
Sheet-6 1
2
>
Review Comments
Please provide written agreement from adjacent
property owner to the south for work associated with
grading and clearing improvements, such as fence
relocation
It is unclear what type of off-site drainage improvements
are you proposing, on sheet you show dispersal trench
but on another you show tight line connection, this is-
very confusing, please make sure all sheets show
consistent improvement and provide complete
information with standard details for our review
Please show all existing driveways on the south side of
120'" and show how the new walkway improvement
imnact each existino drivewav
Show proposed finished grade lines for improvements in
120th ..
Please revise the walkway cross section to show 2%
cross slope
The profile grid shown on this sheet is blank; please
provide complete information as needed.
Please revise proposed shoulder improvements in 120'"
to 5' shoulder width
Please extend and wrap the walkway improvement at
120111 intersection as shown in red on plans, provide
section for the shoulder improvement at this location and
show pavement radii setback at 16-feet from ROW
centerline
Please show the drainage improvements in plan and
profile designs and show complete design information,
and show flow direction arrows in olan views
Sheet 3 of 6
. Back Consultant Response Check
p,. Gi iLi2.<2-M.a.\\. ,~ \ N C..\..v0~D IN
" ,,
s iZ..y'J'n"l.f'n'z.. 7~\<.i\b~ U'R.l.~ C-i¥:.e-r/l ~'\~-
'('L.?,1'1.'6 'R,,l.\/1 s,1.-P , o 'S,(+,,....;
f, {;) wr L 11-lfz. C.o>l"' e..c..,10,-( -.o Di'r'( U Gtf'f'
-r'o ,::. Lo 'v-( p ,s 1'"""~'°'--1 ..,.IZ-,'!..,'1.0,I . S ;;.,z.
yt_..i\rN. "-.l+,~ff JI: l'-.'-\D \ I •
\)Id ,sµ.o..,.,,.., w( Sr"-.-~Ui-1/ •
°Pl'fT>I ( ,i..-,..\Ti'{\\..,~lG. ~~N1 PP·t~lt?o' lz.L-i 'J,
~ (l. J I'? r,_,{.:)
f,'f..~
'-I· ~A->n-1 "i" ~ c.. \-\(I,,!, 1.. ,..,, ~ 1. ,1 e "'c.. o~
I0·5o-ob ~ ZDb-z_c,1 "71S'S
1Z-~v' \ '::> n..o
~i1..-116•~
I
. \
;,,,;::__
B.3ifil
~
KingCounty
Department of Development
And Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-5212
206-296-6600 TTY 206-296-7217
www.kingcounty.gov
Sub
Reference Item
Item
3
Sheet-7 1
2
3
4
5
Sheet-8 1
)
2
3
Sheet-9 1
Back RevieviComments Consultant Response ' Check
Please provide complete information in the road profile
design to make sure landing crtteria is fully met per I '>-I Pen"\..~ A-'n "1'i_ ~~,W .
KCRS
Provide more information for the by-pass trench such as I '-1 'P""-""-,YTI ut-\ ~ ~'~~ length width and show in drainage easement
Please show the drainage improvements in plan and
}.-.S .::> ~ profile designs and show complete design information,
and show flow direction arrows in olan views
Pleas provide complete information for proposed
drainage improvements off-site, use either direct tight
line connection or spreader system, and provide
documentation for off-site drainaae easement
p,.-D u ;;,,(.)
Please replace grade breaks in the road profile with \<._v-J1"'.:,1~ vertical curves and show complete design information
Show individual storm stub-outs with complete
?>,.-\)7'>~ information for each lot
Show profile design for the vault and provide complete "'~,J I~ \1.-P design information in the vault detail as show in red
Show the vaults in public drainage easements within
recreation tract, show limits of tract and easement <Sae. -. i2 J'r,:.,T "? I.. r'l"'t\ -':> ~?, ':, ii.'1';.
Show maintenance access to control structure '::>~~,
Revise the proposed road sections to include ~izV•'='~ ?•~ c..,-..\v~l'L<:.P.1"1,r-1. w,Tt+ information shown in red on olans . ,. M Pl~i;.." >ri. 1>-,?~i\. ... l'"'I '-I. 1<i-o"b,
Sheet 4 of 6
:--..
R~f11
~
King County
Department of Development
And Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-5212
206-296-6600 TTY 206-296-7217
www.kingcounty.gov
Sub
Reference Item
Item
T.I.R. 1 <
2
3
4
General 1
2
3
·• .
Review Comments
-.
Please revise the peak flow calculations and the RID
design calculations based on 50% of existing pervious
surface consideration + pasture or forested for the
remainder of the site area in the pre-developed
conditions. -
Revise the RID calculations based on actual stage O
elevation as shown on plans
Provi_de compete and detailed downstream analysis in
TIR and include basin maps as needed
Provide bond quantities calculations work sheet in Tl R
The Landscape plans requires separate application for
review, please submit;as soon as possible.
Provide wetland report for adjacent wetland to the east
Provide Structural Plans and calculations for the
proposed storm water vaults
Sheet 5 of 6
'-Back Consultant Response '.·
Check
-
F,. l',.,,J I '? i l-v->
~ i',,,,-,.J ,'::,, ... ..{)
~ .~ •'?(1..D
P...·D {)~.-c:>
Sv?,M~, L (:,., ?vA,-1.<:, ~3{'-?~ ~ S'tl"
~ (,.,ii ,S.;z.c_it-.\ b -'R ~ .. i'A,,.J, ),>l'.:) ..
L ""''-'-V ~ ,i,.;-, ,.,._ ~ "':. ~·Ul.. l)TI\.'
V r, .. .1 c"\ lo •
~ .
.
.
King County
Department of Development
And Environmental Services
900 Oakesdale Avenue SW
Renton, WA 98055-5212
206-296-6600 TIY 206-296-7217
www.kingcounty.gov
Sub
Reference Item
Item
4
5
Review Comments
'·' '
Add the following note.on the plans:
Per KCRS Section 4. 01 F, a 1 inch full width
overlay shall be required. Appropriate repairs to
the existing subgrade, base material, surfacing
and pre-level may be required prior to placing
the overlay. The overlay may be waived only
upon written request and after an evaluation of
pavement conditions and/or channelization
requirements has been completed and approved
by the County Road Engineer or Development
Enaineer.
Please submit 3 set of revised plans and TIR for further
review by the County along with all plans and TIR review
redline markuos
..
Sheet6 of 6
'
C_onsultant Response Back
~heck
I
I
I
I
)'\,:,, f'; i:)u r,; P -? ,'l,o ~ iU)I'"" '
YO~<, N.OT M "v, 'f-'-\ a t .
I z o "i1"I-, K (',. w ~ i>,-"!"-~
)~ ~~· 'P1\.c tM,.. ~~
1' ;z e,.> .J' "l:> ,7,_.0
•---· Web date: 10/10/2005
®
King County
Department of Development and Environmental Services
Land Use Services Division
ENGINEERING REVIEW
CHECKLIST
1998 Surface Water Design Manual
1993 King County Road Standards
900 Oakesdale Avenue Southwest
Renton, WA 98055-1219
206-296-6600 TIY 206-296-7217 For alternate formats, call 206-296-6600.
PROJECT INFORMATION
Pmject Nam, 1~ \'\\kE~N,,lf fXZ
Act1v1ty Number ~~
Project Number
Development Number
ODES Review Engineer Date
Notes
OK
D Hearing Examiner's Report ........ Date Revised Report ...... Date -------
0 Plat Ordinance Number Date
D Preliminary Plat Map .......... Date Approved by Hearing Examiner
D Revised Preliminary Plat Map ....... Date Approved by ODES
D 5-year Expiration ....... Date ------~---(Show on engineering cover sheet)
ROUTING'TO OTHER KING COUNTY SECTIONS
OK
D Wetland Report/ Plans ,.
Route Date Response Date
D Geotechnical Report/ Plans
Route Date Response Date
D Grading Report / Plans
Route Date Response Date
D Structural Designs I Calculations/ Civil Plans/ Soils Report (Vaults, Retaining Walls, Bridges)
Route Date Response Date ___________ _
D Landscape / Recreation I Street Tree I Plan
Route Date ------------Response Date ------------
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 1 of 16
Activity Number: -------------
(Continued)
D Traffic Improvement Plan / Report
Route Date ___________ _ Response Date ____________ _
D Tree Retention I Forestry I Plan
Route Date ___________ _ Response Date -------------
D Other Report I Plan
Route Date ___________ _ Response date -------------
D All required routing stations shown and updated on PRMS
Notes
GENERAL SUBDIVISION REQUIREMENTS
D Site plan layout matches preliminary plat approved by Hearing Examiner
(Check for same lot count, tract configuration, road alignments, etc.)
D Compliance with conditions of preliminary approval
D Compliance with Mitigated Determination of Non-Significance
D Tract Table if three or more tracts. Identify name, size and purpose.
D Show and label all SAO tracts, buffers, and 15' BSBL.
D Review maximum height of 6-feet for rockeries and retaining walls per KCC 21A.12.030, 110-170, 220) Also show
standard note per policy on Web site.
D Use updated cover sheet showing designation for highly critical sites per Appendix, D44.
D Determine if HPA fisheries permit required -contact CAO staff.
D Tree Retention Plans -Show standard plan note (see section policies).
SURFACE WATER DESIGN MANUAL (1998)
CORE AND SPECIAL REQUIREMENTS
OK SWDM
D 1.2.1
D 1.2.2
D 1.2.3
D 1.2.6
D 1.2.8
D 1.3.1
D 1.3.2
Core #1 -Evaluate diversion of drainage within subbasins and/or tightline requirements for landslide
hazard drainage areas.
Core #2 -Off-site analysis. Evaluate adequacy and conclusions.
Core #3 -Flow control. Determine design standard based upon mapping and/or off-site analysis.
Evaluate exemptions from flow control if applicable.
Core #6 -All drainage facilities and road access shall be located in public tracts, right-of-way and/or
drainage easements dedicated to King County. For private facilities, specify the required Declaration
of Covenant and drainage easements for final recording.
Core #8 -Water Quality. Determine design standard based upon mapping and/or off-site analysis.
Evaluate exemptions if applicable and untreated areas per page 1-57.
Special #1 -Area specific requirements. Perform P-suffix search on computer, evaluate grading code
restrictions, and review for shared facility drainage plan.
Special #2 -Floodplain boundaries shown on plans.
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 2 of 16
~/
Activity Number: -------------
DRAINAGE VARIANCES
OK SWDM
D 1.4 Activity No. _________ Approval Date
Design lssue.;,.s _____________________________ ---.
TECHNICAL INFORMATION REPORT
OK SWDM
D 2.3.1.1
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
0
D
D
D
0
D
D
D
D
D
Section 1 -Project Overview
Figure 1: TIR Worksheet
Figure 2: Site Location
Figure 3: Drainage Basins
a. Acreage of subbasins
b. Identify all site characteristics
c. Show existing discharge points to and from the site
d. Show routes of existing, construction, and future flows at all discharge points and
downstream hydraulic structures.
e. Use a minimum USGS 1 :2400 topographic map as a base
f. Show and cite the length of travel from the farthest upstream end of a proposed storm
system in the development to any proposed flow control facility.
Figure 4: Soils
a. Show the project site
b. The area draining to the site
c. The drainage system downstream for the distance of the downstream analysis
Section 2 -Preliminary Conditions Summary with responses
Section 3 -Off-Site Analysis
Section 4 -Flow Control and Water Quality Facility Analysis and Design
Existing Site Hydrology (Part A)
Developed Site Hydrology (Part B)
Performance Standards (Part C)
Flow Control System (Part D)
Water Quality System (Part E)
Section 5 -Conveyance System Design and Analysis
Section 6 -Special Reports and Studies -Geo, Wetlands, Floodplain analysis (4.4.2)
Section 7 -Other Permits (HPA, Special Use, WSDOT, etc.)
Section 8 -Erosion / Sedimentation Control Design
Section 9 -Bond Quantities Worksheet and RID Facility Summary
Section 10 -Maintenance and Operations Manual (Section 10 for privately maintained or special
non-standard features
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 3 of 16
'./
Activity Number: -------------
SITE IMPROVEMENT PLANS
OK SWDM
D 2.3.1.2
D Vertical Datum NAVO 1988 -show benchmark
D Horizontal Control NAO 1983/91
D 2.3.1.2 General Plan Format
(1) Sheet size 24" x 36"; quality reproducibles
(2) King Co. Standard Map Symbols; existing / proposed (Reference 7 A)
(3) Project Information I Cover Sheet
a. Title: Project name and DOES file number
b. Table of Contents if more than 3 plan sheets
c. Vicinity Map
D
D
D
D
D
D
D d. Name & Phone of Utility field contacts and One Call Number: 1-800-424-5555 (water, sewer,
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
gas, power)
e. Preconstruction / Inspection notification requirements
f. Name & Phone of erosion control supervisor
g. Name & Phone of Surveyor
h. Name & Phone of Owner/ Agent
i. Name & Phone of Applicant
j. Legal description
k. Plan approval block for ODES
I. Name & Phone of engineering firm preparing plans
m. Fire Marshal's approval stamp (if required)
n. Mailbox location approval by U.S. Postal Service
o. List of conditions of preliminary approval on all site improvements
(4) An overall site plan if more than three plan sheets are used
a. The complete property area development
b. Right-of-way information
c. Street names and road classification
d. All project phasing and proposed division boundaries
e. All natural and proposed drainage collection and conveyance systems with catch basin
numbers shown
(5) Each sheet and TIR is stamped, signed, and dated by a Professional Engineer licensed in
Washington State
(6) Detail Sheets Provided
(7) Title block on each sheet
a. Development title
b. Name, address and phone number of engineering firm
c. Revision block
d. Page numbering
e. Sheet title (e.g., road and drainage, grading, etc.)
(8) King County approval block on each plan sheet
(9) The location and label for each section or other detail shall be provided
(10) Critical Area Setbacks per K.C.C. 21A.24
(11) All match lines correspond to the sheet reference
(12) Division phase lines with limits of construction
(13) Standard Plan Notes -General, Drainage & Structural notes (Reference 78)
(14) Survey control plan sheet stamped by licensed PLS in Washington State
EngineeringReviewCheck.listFORM.doc le-ckl-ercheck. pdf 10/10/2005 4 of 16
Activity Number: -------------
SITE IMPROVEMENT PLANS tcontlnuedl
OK SWDM
D 2.3.1.2 Plan View: Site Plan and Roadway Elements
(1) Property Lines, R/VV lines, roadway widths shown D
D (2) Existing/ Proposed road features; CL, edge pavement, edge shoulder, ditches, curb, sidewalk &
D
D
D
D
D
D
access pis
(3) Existing/ Proposed topographic contours@ 2', 5'>15% slope, 10-'>40% slope
(4) All affected utilities are shown; utility poles marked
(5) All roads and adjoining subdivisions identified
(6) Existing / Proposed R/VV dimensioned and shown
(7) Existing / Proposed surfacing shown
(8) Scale generally 1"':50' (1"=100' for lots >1 Acre)
D 2.3.1.2 Plan View: Drainage Conveyance
D
D
D
D
D
D
Sequentially number all catch basins and curb inlets
Show length, diameter, and material for all pipes, culverts, and stubouts
Label catch basin size and type
Show stubout locations for roof drains
Label all drainage easements, access easements, tracts, and building setbacks
Provide flow arrows for drainage direction
D 2.3.1.2 Plan View: Other
Show all buildings, property lines, streets, alleys, and easements
Verify condition of public right-of-way
Show structures on abutting properties within 50 feet
Identify fencing for drainage facilities
Provide section details of all retaining walls and rockeries
D
D
D
D
D
D Show all wells on-site and within 100-feet of site. For well abandonment, include notes referencing
DOE procedures.
D 2.3.1.2 Profiles: Roadway and Drainage
D
D
D
D
D
D
D
D
D
D
D
Existing / proposed roadway centerline (CL) at 50' stations increasing, reading from left to right.
Show stationing of points of smooth vertical curve, with elevations
Show vertical curve data including stopping sight distance
Show all pipes and detention tanks with slope, length, size and type
Show all pipe inverts and elevations of catch basins or lids
Minimum cover dimensions if less than 2.0'
Indicate roadway stationing and offset for all catchbasins
Show vertical and horizontal scales (vertical 1 "=5')
Label all profiles with street names and reference numbers to plan sheet
Show all property boundaries and match line locations
Provide profiles for conveyance systems of 12" and larger pipes or channels other than roadway
ditches
Catch basin lids are flush with ground line
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 5 of 16
Activity Number: -------------SITE IMPROVEMENT PLANS fconUnuedl
OK SWDM
D 2.3.1.2 Plan Details
D
D
D
D
D
D
D
D
D
D
D
D
Provide scale drawing of each pond, vault, or water quality facility. Include all pipe details for size,
type, slope, length, etc.
Show existing and final grade contours at 2-foot intervals. Show maximum design water elevation.
Dimension all berm widths
Provide two cross sections through pond, including one section through restrictor
Specify soils and compaction requirements
Show location and detail of emergency overflows, spillways, and bypasses
Specify rock protection I energy dissipation details
Provide inverts for all pipes, grates, etc., and spot elevations on pond bottom
Show location of access roads to control manholes and pond / forebay bottoms
Provide plan and section views of all energy dissipaters. Specify size and thickness of rock.
Show bollard locations (Typically at entrance to drainage facility and walking trails)
Restrictor and control structures must have section and plan view drawn to scale
D 2.3.1.2 Structural Plan Details
D Verify that designer is a licensed structural P.E. for vaults or bridges
Notes:
EROSION AND SEDIMENT CONTROL (SWDM Appendix Dl
OK
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
SWDM
2.3.1.3
0.4.1
General Specifications
Separate plan sheet showing entire site w/features
Show critical areas and buffers in separate tracts
Show existing contours and final grades if scope or work includes grading
Pertinent information from soils report is added to plans
Drainage features identified (streams, wetlands, bogs, springs, seeps, swales, ditches, pipes &
depressions)
Utility corridors other than roads shown
Show drainage divides and flow directions
Specify best management practices
Show cut and fill slopes with catch lines indicated
Sufficient conceptual details to convey design intent
Standard ESC plan notes shown on plans (Page D-69)
For grading and structural fill within lot areas -show standard notes for geo hazards (see section
policies for geo notes)
Clearing Limits
(1) Delineate clearing limits -colored survey tape may be used. Critical areas require plastic/
metal safety fence or stake and wire fences.
(2) Provide detail of fencing
EngineeringReviewChecklistFORM.doc le-ck.1-ercheck.pdf 10/10/2005 6 of 16
Activity Number: -------------
2.3.1.3 EROSION AND SEDIMENT CONTROL ISWDM Appendix Dl !continued)
OK SWDM
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
D.4.2
D.4.3
D.4.4
D.4.5
D.4.6
Cover Measures
(1) Specify the type and location of temporary and permanent cover measures. (Mulch, erosion
control nets, blankets, plastic, seeding and sodding)
(2) Specify the seed mixes, fertilizers and soil amendments to be used and application rates
(3) Areas receiving special treatment are specified Qute netting, rock lining or sod)
(4) Soil cover practices and locations of disturbed areas
Perimeter Protection
(1) Specify the location and type of perimeter protection to be used -silt fence, brush barriers,
and/or vegetated strips
(2) Provide details and specify type of fabric for silt fence
Traffic Area Stabilization
(1) Show construction entrance with detail (Figure D.4.G)
(2) Show proposed construction roads and parking areas. Specify details for stabilization.
Sediment Retention
(1) Show location of sediment pond or sediment trap. Very small areas can be treated with only
perimeter protection (see D.4.3).
(2) Sediment Trap -Can be used for drainage areas of 3 acres or less. Calculate surface area
using 2-year design storm. Show detail per Figure D.4.H.
(3) Sediment Pond -Determine pond geometry and show details on plan for required storage,
depth, length and width
(4) Show sediment pond cross section and detail (Figures D.4.J and K)
(5) Provide details of cell dividers and stabilization techniques for inlet/ outlet
(6) Specify mulch or recommended cover of berms & slopes
(7) Specify the 1-foot marker for sediment removal
(8) Indicate catch basins for protection and show design details (Figures D.4.L and M)
Surface Water Control
(1) Show conveyance of all surface water to a sediment pond or trap
(2) Discharge location shall be downslope from disturbed areas
(3) Show details for conveyance with interceptor dike, swales (Figures D.4.0, P).
(4) For ditches, determine capacity for 10-year storm with 0.5 feet freeboard. Show details for
check dams (Figure D.4.R). Determine check dam spacing and as needed, show inverts and
minimum slopes of open channels. Also show direction of open channel ftow.
(5) For pipe slope drains, determine capacity for 10-year storm. Show details per Figure D.4.Q.
(6) Determine level of protection for outlet (rock pad, outfall design, or level spreader). See
requirements in D-38 through D-40.
(7) Evaluate off-site flows entering the site and assure bypass of disturbed areas
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 7 of 16
Activity Number: -------------
2.3.1.3 EROSION AND SEDIMENT CONTROL (SWDM Appendix DI (contlnuedl
OK SWDM
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D.5.1
D.5.2
D.5.3
D.5.4
D.5.7
D.5.8
ESC Report
(1) Show detailed construction sequence (page D-70)
(2) All required calculations and soils reports contained in TIR
Wet Season Requirements
(1) Provide a list of all applicable wet season requirements (details on page D-42)
Critical Area Restrictions
(1) Consider phased construction during the dry season. See special recommendations on page D-
43.
Maintenance
(1) Plans shall list the name, address and phone number of the ESC Supervisor. A sign shall also
be posted on the construction site with information for contacting the ESC supervisor.
(2) Determine if site is Highly Critical (Soil Types C or D, 5 acres of disturbance, large areas with
slopes >10%, proximity to streams, wetlands, or lakes)
(3) On cover sheet of engineering plans, designate if highly critical site
NPDES Requirements
(1) Determine if project will disturb more than 5 acres
(2) If disturbed area is greater the 5 acres, show the following note on the plans:
"No construction or site disturbance for this project may begin before the applicant first obtains a
General Permit to Discharge Stormwater Associated with Construction Activity permit from the
Washington State Department of Ecology (DOE). For more information or application form,
please visit DOE's website at http://www.ecy.wa.gov/bibliolecy02085.html"
Forest Practices Permit
(1) Determine if project needs FPA permit. Contact DDES grading section.
(2) Provide a reference note on the cover sheet indicating whether or not an FPA permit has been
obtained.
Early Start Plan Review
(1) Standard cover sheet included with Title for Phased Early Start
(2) List the scope of work for early start (scope of work will vary for each project -evaluate clearing,
grading for roads, lot grading, utility installation, vault construction, off-site work)
(3) Update the sheet index to identify all plans with updated page numbers
(4) Include standard ESC plan prepared in accordance with all requirements listed above for
erosion and sediment control
(5) Include detailed construction sequence and identify ESC supervisor
(6) Show standard erosion control notes
(7) Show early start activity number on all plain sheets
EngineeringReviewChecklistFORM.doc 10/10/2005 6 of 16
Activity Number: -------------
DESIGN REQUIREMENTS
OK SWDM
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
3.2
3.27
3.3.6
3.3.7
4.0
4.5
4.7
4.9
4.9
4. 10
4.27
4.35
4.51
4.69
4.53
5.0
5.3
5.9
5. 11
Runoff Computation
Rational Method required for on-site conveyance (See Table 3.2)
KCRTS used for flow control design
Evaluate correct data: Rainfall region, scale factor, time step, record type, acreages, soil cover
groups, and percent impervious
For urban areas, unprotected forest modeled as pasture or grass
For rural areas, unprotected forest assumes 50% grass, 50% pasture
All pre-developed grassland modeled as pasture
All post developed grassland modeled as grass
Impervious coverage calculated based upon specific project -clearly summarize types and amounts
of impervious
For urban development, impervious for each lot, >= 4,000 sq ft or maximum allowed in zoning code
For rural development, impervious for each lot, >= 8,000 sq ft or maximum allowed in zoning code
Evaluate requirements for modeling with effective impervious area
Point of compliance -evaluate for on-site bypass and off-site closed depression
On-site closed depressions and ponding areas
Conveyance System Analysis and Design
Conveyance systems are in easements with BSBLs
Off-site easements must be recorded using standard forms (Reference 8H)
Determine which easements are public and private, label and dimension
Pipes are parallel to and alongside property lines
Minimum pipe size 12-inch, for private systems may allow 8 inch
Easements for pipes outside of right of way
For connecting pipes at structures, match crowns, 80% diameter, or inverts
Minimum velocity at full flow 3.0 feet per second
Minimum cover for pipes 2 feet
Debris barrier for pipes 18-36 inch
Outfall design criteria
Surcharges (backwater analysis may be required)
Maximum headwater allowed for culverts
Bridge design
Floodplain analysis
Open channels
Flow Control Design
Mandatory requirements for roof downspouts in order of preference. Must evaluate feasibility of
each.
o Infiltration o Dispersion o Perforated stubouts
Dispersion system criteria including vegetated flow path
Perforated stub out, if used show detail per Fig. 5. 1.3.A
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 9 of 16
Activity Number: -------------
DESIGN REQUIREMENTS (continued)
OK SWDM
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
5.14
5.15
5.17
5.3
5.3.1
5.3.2
Forested open space flow control BMPs
o Show tracts or easements for FOS
o Show required notes on plan for plat recording
Roadway dispersion BMPs, check design criteria
BMPs for reducing facility size. Note: Facility sizing credit allowed for dispersion only if flowpath from
roofs ultimately drain to RID facility.
Detention Facilities
Emergency overflow -Evaluate flow path for safe and adequate conveyance
Setbacks
Flow-through system
Detention Ponds
Dam Safety Compliance
Two cross-sections through pond (one x-section to include control structure)
Review pond details in Figures 5.3.1.A and B
Designed as flow-through system
Side slopes interior 3H:1V or fenced
Vertical interior retaining walls Stamped by licensed structural civil engineer
For pond walls, min. 25% of perimeter vegetated and no steeper than 3:1
Berms greater than 4 feet require key excavation
Minimum berm width of 6 feet
Primary overflow (control structure with riser).
Secondary Inlet to the control structure
Emergency Overflow Spillway, 100 year developed peak flow
Soil and compaction requirements described (95% modified proctor)
Access road min. turning radius, maximum grade, min. width, fences or gates
Pond sign (Figure 5.3.1.D)
Fencing and planting requirements
Setbacks -5 feet from tow of exterior slope or 5 feet from water surface for cut slope
Detention Tanks
Flow-through system required
6" of dead storage in tank bottom
Minimum pipe diameter of 36"
Materials and structural stability
Control structure per Section 5.3.4
Buoyancy
Access risers and CBs are spaced properly with max. depth from finished grade to tank invert shall
be 20 feet and accessible by maintenance vehicles
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 10 of 16
Activity Number: -------------
DESIGN REQUIREMENTS fcontlnuedl
OK SWDM
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
5.3.3
5.3.4
5.4
6.0
6.1
6.2
6.2.2A
6.2.3
6.2.4
6.2.5
6.3
6.3.1
6.3.1.1
6.3.1
6.3.4
Detention Vaults
Structural package submitted for approval
Flow-through system required
Review design details per Fig. 5.3.3.A. Note: Grate over sump with 2' x 2' hinged access door
Access positioned a maximum of 50 feet from any location. (if over 3 foot cover use cone riser)
Access required to inlet pipe and outlet
Removable 5x1 O panel if vault greater than 1250 sq. ft. floor area
Maximum depth from finished grade to vault invert to be 20 feet
Minimum internal height shall be 7 feet, min. width shall be 4 feet min
Ventilation pipes provided in all four corners
Control Structures
Section and plan view shown to scale
Orifice size and elevation on plans match calculations. Minimum orifice 0.5".
(Note: Information Plate details are no longer required -see policy on Web site.)
Infiltration Facilities
Appropriate soils logs and testing procedures in TIR
Pond bottom at least 3 feet above seasonal high water
Permeable soil extends minimum 3 feet below bottom of pond
Geotechnical report states suitability and determines design infiltration rate
Overflow route identified with 100-yr overflow conveyance
Spill Control device upstream of facility
Presettling
Review setback requirements, page 5-60. Design water surface setback of 20 feet from external
tract, easement or property lines
Show the standard note regarding public rule for in operation facility (see section policies)
Water Quality Design
Water Quality Menus
Water Quality facilities
Water Quality Sequencing
Setbacks, slopes and embankments
Facility Liners
Flow Splitter Designs
Blofittration Facility
Biofiltration swales and soil amendments
Methods of Analysis
Swale geometry, plantings, flow conveyance, high flows, velocity
Road access requirements, page 6-43
Filter strip geometry (slopes)
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 11 of 16
Activity Number: -------------
DESIGN REQUIREMENTS (continued)
OK SWDM
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
Notes·
6.4
6.4.1.2
6.4.1.1
6.4.2
6.4.1.1
6.4.1.1
6.4.2.2
6.4.3
6.4.3.1
6.4.3.2
6.4.4
6.4.4.1
6.4.4.2
6.4.4.2
6.5
6.5.1
6.5.2
6.5.2.1
6.5.2.2
6.5.3
6.5.3.2
6.5.3.2
Wetpool Facility Designs
Wetpool geometry, 2 cells, minimum depth of first cell 4 feet
Flowpath length to width ratio 3:1. Note: If flow path achieved with berms or walls, top of berm must
be at 2-year water surface elevation.
Berms, Baffles, Slopes
Inlet/Outlet Design
Access, setbacks, and plantings
Wetvaults
Sizing basic or large
Berms, Baffles, Slopes
Two cells separated by wall or removable baffle
Vault bottom forms a broad "V" with 5% sideslopes
Inlet is submerged and outlet pipe designed for 100-year overflow
Gravity drain provided if grade allows
Minimum 50 square feet of grate over second cell
Stormwater Wetlands
Methods of Analysis
Design Criteria -Wetland geometry, liners, access, plantings
Combination Detention and Wetpool facilities
Methods of Analysis
Design Criteria -Detention and wetpool geometry, berms, baffles, slopes
Access and plantings
Media FIitration Facility Designs
Presettling/pretreatment
Sandfilters -Basic and Large
Methods of analysis
Design Criteria -Geometry, overflow/bypass, underdrain, and access
Sandfilter Vaults
Design Criteria -geometry, pretreatment, flow-spreading, energy dissipation
Overflow/bypass, underdrain and access
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 12of16
Activity Number: -------------
KING COUNTY ROAD STANDARDS (1993)
GENERAL REQUIREMENTS
KCRS
1.03A, B
1.03 D
Off-site and frontage improvements determined by reviewing agency
Note: For grading permits, the required extent of road improvements must be determined during
engineering review. For subdivisions, the requirements are determined during preliminary
review.
Subdivisions must have recorded public access except for private roads
DESIGN REQUIREMENTS
1.08 Road Variances
Activity No. Approval Date ----------
Design Issues
ROAD CLASSIFICATION TABLE
Name of Roadway KCRS Classification
OK KCRS
D 2.03C Maximum Superelevation (2.05)
D 2.03D Horizontal curvature (2.05)
D 2.03E Maximum grade (2.11)
D 2.03F Stopping Sight Distance (2.05, 2.12)
D 2.03G Entering Sight Distance (2.05, 2.13)
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10/10/2005 13of16
Activity Number: -------------
KING COUNTY ROAD STANDARDS (1993)
DESIGN REQUIREMENTS (conllnuedl
OK KCRS
D 2.03H
D 2.031
D 2.03J
D 2.03J
D 2.03K
D 2.03L
D 2.06
D 2.0667
D 2.07
D 2.08A
D 2.086
D 2.08E
D 2.08F
D 2.09
D 2.096
D 2.10A
D 2.10A
D 2.10A
D 2.106
D 2.10C
D 2.10E
D 2.11A
D 2.11 B
D 2.12D
D 2.16
D 2.18
D 2.20
D 3.01
D 3.01
D 3.02A
D 3.026
D 3.05
Minimum pavement width (Note: Footnote 9 -Neighborhood collectors require 36-feet at approach to
intersections with arterials)
Minimum roadway width
Minimum R/W width
Min. R/W width (Footnote 12 and 2.19B -include 1 foot extra ROW behind curb or sidewalk)
Curb or shoulder type road (2.01)
Minimum Half-Street width
Private Street Design Standards
Verify maximum potential of 16 lots
Half Streets
Minimum Cul-de-Sac diameters
Maximum Cul-de-Sac length
Maximum Cross Slope 6%
Bulb island shall be offset 2-feet
Alleys
Private Access Tracts (Note: Must meet all standards for minor access street, except curb cut
driveway design is allowed with property line radii dedication)
Angle of intersection between 85 and 95 degrees
Intersection curb radius
Intersection right-of-way radius
Intersection spacing
Intersection landing
Low Speed Curves
Maximum Grade -Use AC for grades >12%, Use PCC for grades >20%
Grade Brakes -maximum 1 % at intersections
Intersection stopping sight distance (125' SSD allowed for local access streets)
Bus zones -For arterials and neigh. collectors, the designer shall contact metro
Intersections with State Highways
Single access serving more than 100 lots
Driveways
Joint Use Driveways
Sidewalks (both sides for subcollectors and higher classification)
Location and width
Handicapped access ramp (Use updated detail from KC Road Engineer, 3/26/04)
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 1011012005 14 of 16
Activity Number: -------------
KING COUNTY ROAD STANDARDS (1993) ·
DESIGN REQUIREMENTS (continuedl
OK
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
KCRS
3.09
3.10
3.11
4.01
4.01F
4.01F
4.02
4.02
4.03
4.05
5.01
5.02
5.03
5.04
5.05
5.06
5.07
5.08
5.11
6.00
7.02A-D
7.03A
7.03L
7.04A
7.04E
7.05A
7.058
7.05E
8.02
8.038
School Access -asphalt walkway, sidewalk, or delineated shoulder
Bikeways
Equestrian Facilities
Road Section and Surfacing (drawings 1-001 -1-006)
Note: Neighborhood collectors require 3-inch asphalt concrete.
Perform saw cut of pavement at fog line
Pavement overlay for widening and channelization (show special note as approved by Development
Engineer -see section policies)
Residential street design
Poor subgrade evaluation
Arterial pavement design
Pavement markings, channelization, and tapers (Requires DOT review)
Rock facings (Dwg. Nos. 5-004 --5-007)
Side slopes, generally 2H:1V
Street trees and landscaping
Mail boxes (Dwg. Nos. 5-010 -5-012)
Street illumination
Survey Monuments to be disturbed are shown
Roadway Barricades
Bollards for walkways or maintenance roads
Roadside obstacles (Note: If variance required for utility pole, the utility company must apply for the
variance.)
Bridges (minimum width 28-feet)
Grass-lined, pipe or rock lined, special designed ditch
Minimum pipe size 12-inch diameter
Beveled ends for culverts in ROW
Maximum spacing between catch basins
CBs taller than 5' (grate to invert) are Type II, Max. depth 12-feet per Dwg. 2-005
Vaned grates
Through curb inlet frames for sag curves and intersections> 4%.
Notes: a) Through curb inlet not used on rolled curb
b) See section policies for policy on three flanking inlets
All covers and grates shall be locking
Utility pole locations and other obstacles
Open cuts on existing roadways, patch requirements
EngineeringReviewChecklistFORM.doc le-ckl-ercheck.pdf 10110/2005 15 of 16
Activity Number: -------------
KING COUNTY ROAD STANDARDS (1993)
DESIGN REQUIREMENTS fcontlnuodl
Notes:
Check out the DOES Web site at www.metrokc.gov/ddes
EngineeringReviewChecklistFORM.doc 10/10/2005 16 of 16
,
®
King County
DeJ)artment of Development
and Environmental Services
900 Oakesdale A venue Southwest
Renton, WA 98055-1219
March 31, 2006
Fanny and Philip Yee
11431 233th Street
Woodway, WA 98020
RE: Preliminary Approval for Short Subdivision No. L04S0065.
Dear Mr. and Mrs. Yee:
The Land Use Services Division (LUSD) has completed review of the short subdivision
application captioned above. The LUSD finds that the proposed short subdivision complies with
the King County Land Segregation Code (Title 19A), Zoning Code (Title 2 IA), and other
applicable codes as specified in King County Code (KCC) I 9A.08.060.
The short subdivision is granted preliminary approval subject to the Conditions of Preliminary
Approval attached hereto and incorporated herein by reference. Any aggrieved party may appeal
this decision by the appeal deadline, which is April 24, 2006. The appeal procedure is enclosed
for your information. The preliminary approval is valid for a period of 60 months from the date of
this Jetter, unless an appeal is filed. In the event that an appeal is filed, the preliminary approval is
valid for a period of 60 months from the date of the appeal decision. Enclosed are the following:
o Notice of Decision
o Conditions of Preliminary Approval
o Appeal Procedure
If you have any questions regarding this Jetter, please contact Fereshteh Dehkorcli, Program
Manager, at (206) 296-7173 and Curt Foster, Engineer, at (206) 296-7106.
Sanders, Development Engineer
Engineering Review Section, LUSD
Enclosures
cc: De En Lang, Consulting Engineer
Applicant File
Letter frm/CoverLtr2000 SP.doc 3/9/00
iSM\)~~
Lisa Dinsmore, Supervisor
Current Planning Section, LUSD
A
®
KING COUNTY
DEPARTMENT OF DEVELOPMENT AND ENVIRONMENTAL SERVICES
LAND USE SERVICES DIVISION
900 Oakesdale Avenue Southwest
Re_nton, WA 98055-1219
REPORT AND DECISION
SHORT SUBDIVISION File No. L04S0065
DESCRIPTION OF THE PROPOSED SHORT SUBDIVISION:
This is a short subdivision of .96-acre site (two tax parcels) into six (6) lots for detached
single-family dwellings in the R-6 zone. The proposed density is 6 dwelling units per
acre. The proposed lot sizes range from approximately 3000 square feet to 5,300
square feet. Refer to Attachment 1 for a copy of the short plat map.
B. GENERAL INFORMATION:
Owner/Applicant:
Consulting Engineer:
STR:
Location:
Zoning:
Acreage:
Number of Lots:
Density:
Lot Size:
Proposed Use:
Sewage Disposal:
Water Supply:
Fire District:
School District:
Date Submitted:
Fanny and Philip Yee
11431 2381h Street ·
Woodway WA 98020
Lang Associates, Inc.
10658 Riviera Place NE
Seattle, WA 98125
SW Y. 33-23-05
12052 SE 129th Place
R-6
.96 acre
6
6 du/acre
Ranges from 3000 to 5,300 square feet
Residential
Soos Creek Water and Sewer District
Soos Creek Water and Sewer District
Fire District 40
Renton School District
Complete Application Date:
December 27, 2004
January 17, 2005
C. HISTORY and BACKGROUND
The Subdivision Technical Committee (STC) of King County has conducted an on-site
examination of the subject property. The STC has discussed the proposed
development with the applicant to clarify technical details of the application and to
determine the compatibility of this project with applicable King County plans, codes, and
other official documents regulating this development.
As a result of preliminary discussions, the applicant presented the Technical Com.mittee
with a revised site plan on January 9, 2006. The revision to address some of the
technical issues was minor. No change to the road or lot layout was made.
Report and Decision -I -L04S0065
D. NATURAL ENVIRONMENT
1. Topography: The site slopes down gently from west to east. The maximum slope
is3%.
2. Soils: One soil type is found on this site per King County Soil Survey, 1973.
The entire site is classified AgB. The following are characteristics of AgB soils:
AgB -Alderwood gravely, sandy loam; 0-6% slopes. Runoff is slow and the
erosion hazard is slight. This soil type has moderate limitations for low building
foundations due to a seasonally high water table, and severe limitations for
septic tank filter fields due to very slow permeability in the substratum.
3. Wetlands: A wetland and report was prepared by Altmann Oliver Associates
dated December 22, 2004. The report identified a small (175 sq.ft.) isolated
shallow wetland partly on site. This wetland is exempt from regulation. The site
lies within the Soos Creek drainage basin.
4. Vegetation: This site is primarily covered in grasses. Scattered evergreen and
deciduous trees and sherubs occur in limited numbers.
5. Wildlife: Small birds and animals may inhabit this site; however, their population
and species are limited due to nearby development. No threatened or
endangered species are known to exist on or near the property.
6. The Sensitive Areas Folio does not identify any mapped sensitive areas as being
present on this site.
· E. NEIGHBORHOOD CHARACTERISTICS:
F.
The property lies within a gradually urbanizing area east of the City of Renton. The
proposed subdivision of Fleuve Des Voies, KC File L04P0002, with 38 residential lots is
on parcels east of the site and is currently under review by DOES. There are larger lots
with potential for re-subdivision to the west and north of the site. The properties south
of the site are developed with single family residences. The site and the surrounding
parcels are zoned Residential (R-6) with six dwelling units per acre. The proposed
subdivision site is undeveloped.
DESIGN FEATURES
1. Lot Pattern and Density: The proposed density and lot layout meets the density
requirements of R-6 and the Short Subdivision Code.
2. Access/Roadway Section: The site obtains access to 1201
h Avenue SE via a 30-
foot wide easement extending east from the road to the site. The easement will
be improved to an urban minor access road standards consisting of curb, gutter
and sidewalks on the north side of the road.
3. Drainage: Currently drainage from the property leaves the site in the form of
sheet flow. After development, storm water runoff (from the proposed under
ground vault) will be conveyed eastward (same direction) to a proposed
development on the neighboring property. The applicant has received a letter of
agreement from the property owner directly east of the site to allow a drainage
easement across his property for this purpose.
The on-site vault will be located in the southeast corner of the property. It will be
designed for Level II flow control and basic water quality (1998 Surface Water
Design Manual).
3. Other Design Features: The proposal includes a 3,173-square-foot recreation
tract located southeast of the site. This tract will be improved with landscaping
and a toy structure for the benefit of the subdivision's future residents.
Report and Decision -2 • L04S0065
G.
G.
PUBLIC SERVICES
1. Sewage Disposal: The applicant proposes to serve the subject subdivision by
means of a public sewer system managed by the Soos Creek Water and Sewer
District. A Certificate of Sewer Availability, dated December 2004 indicates this
sewer distrids capability to serve the proposed development.
2. Water Supply: The applicant proposes to serve the subject subdivision with a
public water supply and distribution system managed by the Soos Creek Water
and sewer District. A Certificate of Water Availability dated December 17, 2004
indicates this water district's capability to serve the proposed development.
3. School facilities: The subject subdivision will be served by Benson Elementary,
Nelson Middle, and Lindberg Senior High Schools, all located within the Renton
School District.
4. School Access: The District has indicated that the future students from this
subdivision· will walk to Benson Elementary and the middle and high school
students will be bussed from the intersections of 120th Avenue SE and SE 1881h
Street and from the intersection of SE 1881
h and 116th Avenue SE respectively.
Currentlr there are no sidewalks along 1201
h Avenue SE to its intersection with
SE 188 1 Street. Sidewalk improvements are expected along SE 1881h Street by
other subdivision proposals in the area. This improvement together with the
required off-site pedestrian improvements (See SEPA condition below) will
complete a continuous walkway facility from the site to the school bus pick up
areas.
5. Parks and Recreation Space: The nearest public park is Soos Creek Park
located along SE 192"d Street a few miles southeast of the site. KCC 21A.14
requires subdivisions in the UR and R zone classifications to either provide on-
site recreation space or pay a fee to the Parks Division for establishment and
maintenance of neighborhood parks. At this time, the applicant is proposing to
provide a 3,100 square-foot recreation tract on the site.
The site of the recreation tract is encumbered by the Soos Creek utility
easement. The Soos Creek Water and Sewer District has agreed to reduce the
easement width to 10-foot wide for the water main. The District has no objection
to development of a recreation tract on the easement provided no toy structure is
anchored within the easement, see attachment ~-
KCC 21 A.14.190 requires subdivisions to provide tot/children play areas within
the recreation space on-site. The proposal must include a 270-square-foot play
area with the required recreation tract The recreation tract plan must be
reviewed and approved by the Soos Creek Utility District.
SEPA THRESHOLD DETERMINATION:
Pursuant to the State Environmental Policy Act (SEPA), RCW 43.21 C, the responsible
official of the LUSD issued a mitigated threshold determination of non-significance
(MONS) for the proposed development on March 24, 2006. This determination was
based on the review of the environmental checklist and supporting documentation filed
with the application, resulting in the conclusion that the proposal would not cause
probable significant adverse impacts on the environment provided the following
measures are attached to the project as conditions:
In accordance with the requirements with RCW 58.17.110 (2), the Applicant shall
improve 120th Avenue SE, from the plat entrance in the 19000 block northward to the
intersection of SE 188th Street/120th Avenue SE by providing a paved walkway along
the easterly side of 120th Avenue SE. The walkway, per Section 3.09 of the KCRS shall
be selected and designed by the Applicant's engineer in accordance with any one of the
following standards, and upon approval by DOES, constructed:
Report and Decision -3 -L04S0065
H.
I.
A A full width (8 feet) paved shoulder
8. A paved shoulder of no less than four (4) feet in width, separated by vehic)e
traffic by either an extruded curb or an unpaved gravel shoulder strip
C. A concrete curb and gutter, and sidewalk section
FINDINGS/CONCLUSIONS:
The subject subdivision will comply with the goals and objectives of the King County
Comprehensive Plan and will comply with the requirements of the Subdivision and
Zoning Codes and other official land use controls of King County ( e.g. 1993 King
County Road Standards, 1998 Surface Water Design Manual, etc.), based upon the
conditions for final short plat approval.
DECISION:
The proposed Short Plat revised and received January 9, 2006 (Attachment 1) is
granted preliminary approval subject to the following conditions of final approval:
1. The proposal shall comply with all platting provisions of King County Title 19A.
2. All persons having an ownership interest in the subject property shall sign on the
face of the final short subdivision.
3. All utilities within proposed rights-of-way must be included within a franchise
approved by the King County Council prior to final short plat recording
4. 1998 King County Surface Water Design Mariual /SWDM) /KCC 9)-The
proposed short plat qualifies for full drainage review as outlined in Chapter One
of the SWDM. Final short plat approval shall require full compliance with the
drainage provisions set forth in King County Code 9.04. A professional civil
engineer licensed in the State of Washington shall prepare drainage plans and a
technical information report as outlined in Chapter 2 of the drainage manual.
· The drainage plan submittal shall demonstrate compliance with all applicable
Core and Special Requirements.
Compliance may result in reducing the number and/or location of lots as shown
on the preliminary approved short plat. Preliminary review has identified the
following conditions of approval, which represent portions of the drainage
requirements. All other applicable requirements in KCC 9.04 and the Surface
Water Design Manual (SWDM) must also be satisfied during engineering and
final review.
A. Engineering plans and analysis shall comply with the SWDM. Prior to
short plat recording, the applicant shall submit engineering plans to
address the required short plat improvements. King County approval of
drainage and roadway plans is required prior to any construction. Permit
fees for review and inspection shall be paid as required by County codes
and policies. Bonding for the drainage plans will also be established as
determined by ODES prior to plan approval. After receiving drainage plan
approval, the applicant shall contact the DOES Land Use Inspection
Section to schedule a pre-construction meeting prior to performing work
on the site.
B. Current standard plan notes and ESC notes, as established by.
ODES Engineering Review shall be shown on the engineering plans.
C. The following note shall be shown on the final recorded plat:
"All building downspouts, footing drains, and drains from all impervious
surfaces such as patios and driveways shall be connected to the
permanent storm drain outlet as shown on the approved construction
drawings# on file with ODES and/or the Department of
Transportation. This plan shall be submitted with the appJication of any
.;-
Report and Decision . 4. L04S0065
building permit. All connections of the drains must be constructed and
approved prior to the final building inspection approval. For those lots
designated for perforated stubouts, dispersion, or infiltration systems, the
designs shall be constructed at the time of the building permit and shall
comply with the plans on file."
SITE SPECIFIC CONDITIONS:
The conceptual drainage plan for this short plat proposes to discharge
surface water run-off into a future piping system. The future piped
conveyance would be constructed and located on the adjace t property to
the east under a proposed subdivision application (LO 02). Prior to
engineering plan approval, the applicant shall provi e proof that assures
the offsite conveyance will be constructed and located in easements
where appropriate.
D. Should the proposed offsite conveyance not be available at engineering
review, and prior to plan approval the applicant shall submit a revision to
this application with a new conceptual drainage plan. Since this will
require a substantial change this project may be re-vest to the current
SWDM (20.20.080 KKC).
5. 1993 King County Road Standards /KCRS) /KCC 14)-Final short plat approval
shall require full compliance with the provisions set forth in the King County Road
Standards (KCRS), including engineering plans for all road and site
improvements. The engineering plans shall be prepared by a professional civil
engineer licensed in the state of Washington. DOES strongly recommends that
the engineering plans be submitted at least two years prior to the expiration date
of the project.
All construction and upgrading of public and private roads within this short plat
shall comply with the following requirements unless otherwise approved by
ODES (KCRS Section1 .03).
A. The proposed road and cul-de sac serving the property shall be
constructed to urban minor access street standard per KCRS, Section
2.03. It shall extend from 1201h Avenue SE and continue into the site
terminating into a cul-de-sac bulb as shown on the site plan per KCRS
Section 2.08. ·
B. The off-site portion of the road improvements may remain in the existing
easement. A note conveying an equally undivided responsibility (to each
future lot owner) for the offsite maintenance cost (for roadway and
facilities within the easement) shall be placed on the final recorded map
page or recorded separately. Additionally, the note shall include a
statement allowing the maintenance responsibility to be modified if agreed
to by all beneficiaries of the original easement including right of way
dedication to a public agency.
C. The on-site improvements shall be placed in a tract. The tract shall be an
undivided ownership to the lots it serves, and the lot owners shall be
responsible for its maintenance.
0. The proposed road improvements shall address the requirements for road
surfacing outlined in KCRS Chapter 4. As noted in section 4.01 F, full
width pavement overlay is required where widening existing asphalt.
E. Modifications to the above road conditions may be considered by King
County pursuant to the variance procedures in KCRS 1.08.
F. The following notes shall be shown on the final recorded short
subdivision:
Report and Decision -5 -L04S0065
(1) All private easements and/or tracts to be maintained, repaired,
and/or rebuilt by the owners of the parcels having legal access
there from and their.heirs, assigns or successors, unless and until
such roads are improved to King County standards and are
dedicated and accepted by King County for maintenance.
(2) All restrictions, easements, tracts, and their purpose shall be
shown on the final recorded short subdivision.
6. Health (KCC 13)-This project is exempt from further King County Heath
Department review. However, if improvements are required from the Sewer
and/or the Water District, then verification shall be required from said District(s)
that the improvements have been bonded and/or installed, prior to final recording
of the short plat.
7. Building and Construction Standards (Title 16)-The applicant shall comply with
all applicable provisions of KCC 16.82. including the significant tree retention
requirements.
8. Fire Code (KCC 17) -Section 902 of the 1997 Edition of Uniform Fire Code
The applicant must obtain the approval of the King County Fire Protection
Engineer for the adequacy of the fire hydrant, water main and fire flow standards
of Chapter 17 .08 of the King County Code prior to the final short plat approval.
9. Density and Dimensions (KCC 21A.12) -All lots shall meet the density and
dimensions requirements of the R-6 zone classification or shall be as shown on
the face of the approved preliminary short subdivision, whichever is larger. Minor
revisions to the short subdivision, which do not result in substantial changes
and/or do not create additional lots may be approved at the discretion of the
Department of Development and Environmental Services.
10 Street Trees (KCC 21A.16)-Street trees shall be provided as follows (per KCRS
5.03 and KCC 21 A.16.050):
A. Trees shall be planted at a rate of one tree for every 40 feet of frontage
along all roads. Spacing may be modified to accommodate sight distance
requirements for driveways and intersections.
B. Trees shall be located within the street right-of-way and planted in
accordance with Drawing No. 5-009 of the 1993 King County Road
Standards, unless King County Department of Transportation determines
that trees should not be located in the street right-of-way.
C. If King County determines that the required street trees should not be
located within the right-of-way, they shall be located no more than 20 feet
from the street right-of-way line.
D. The trees shall be owned and maintained by the abutting lot owners or the
homeowners association or other workable organization unless the
County has adopted a maintenance program. Ownership and
maintenance shall be noted on the face of the final recorded plat.
E. The species of trees shall be approved by ODES if located within the
right-of-way, and shall not include poplar, cottonwood, soft maples, gum,
any fruit-bearing trees, or any other tree or shrub whose roots are likely to
obstruct sanitary or storm sewers, or that is not compatible with overhead
utility lines.
F. The applicant shall submit a street tree plan and bond quantity sheet for
review and approval by DOES prior to engineering plan approval.
Report and Decision -.6. L04S0065
G. The street trees must be installed and inspected, or a performance bond
posted prior to recording of the plat. If a perfo~m~nce bond is posted, .the
street trees must be installed and inspected within one year of recording
of the plat. At the time of inspection, if the trees are. found to be installed
per the approved plan, a maintenance bond must be submitted or the
performance bond replaced with a maintenance bond, and held for one
year. After one year, the maintenance bond may be released after ODES
has completed a second inspection and determined that the trees have
been kept healthy and thriving.
11. Sensitive Areas (KCC 21A.24)-The small size Class Ill wetland located near the
northeast property line is exempt from the Sensitive area requirements.
12. Road Mitigation Payment System -The applicant or subsequent owner shall
comply with Road Mitigation Payment System (MPS), King County Code 14.75,
by paying the required MPS fee and administration fee as determined by King
County Department of Transportation. The applicant has an option to either:
A. Pay the MPS fee at final short plat recording. If this option is chosen, the
fee paid shall be the fee in effect at the time of short plat application and a
note shall be placed on the face of the short plat that reads, "All fees
required by King County code 14.75, Mitigation Payment System (MPS)
have been paid." Or
B. Pay the MPS fee at the time of building permit issuance. If this option is
chosen, the fee paid shall be the amount in effect as of the date of the
building permit application.
13. Recreation Tract. KCC 21A.14-As shown on the site plan, a recreation tract
shall be provided consistent with the requirements of KCC 21A.14.180 and KCC
21A.14.190 (i.e., sport court[s], children's play equipment, picnic table[s],
benches, etc.). A detailed recreation space plan (i.e., landscape specs,
equipment specs, etc.) consistent with KC 21A.16 shall be submitted for review
and approval by DOES and King County Parks prior to submittal of the final plat
documents or concurrent with the Engineering Review phase. The recreation
plan must show only a 10-foot wide easement within the tract as agreed by the
Soos Creek Utility District. No toy structure shall be placed within the 10-foot
wide utility easement. The recreation tract shall be fully fenced.
A performance bond for recreation space improvements shall be posted prior to
recording of the plat.
14. A homeowner's association or other workable organization shall be established
to the satisfaction of ODES which provides for the ownership and continued
maintenance of the recreation tract.
15. To implement KCC 21A.38.230 which applies to the site, a detailed tree retention
plan shall be submitted with the engineering plans for the subject plat. The
tree retention plan and the engineering plans shall be consistent with the
requirements of KCC 21A.38.230, as well as the conceptual tree retention plan
which is part of the hearing record for this project. No clearing of the subject
property is permitted until the final tree retention plan is approved by LUSO.
Flagging and temporary fencing of trees to be retained shall be provided,
consistent with KCC 21A.38.23084. The placement of impervious surfaces, fill
material, excavation work, or the storage of construction materials is prohibited .
within the fenced areas around preserved trees, except for grading work
permitted pursuant to KCC 21A.38.23084d(2).
A note shall be placed on the final plat indicating that the trees shown to be
retained on the tree retention plan shall be maintained by the future owners of
the proposed lots, consistent with KCC 21A.38.23086. Please Note that the
tree retention plan shall be included as part of the final engineering plans
for the subject plat.
Report and Decision -7 -L04S0065
16. The following has been established under SEPA:
In accordance with the requirements with RCW 58.17.11 O (2), the Applicant shall .
improve 120th Avenue SE, from the plat entrance in the 19000 block northward
to the intersection of SE 188th Street/120th Avenue SE by providing a paved
walkway along the eastward side of 120th Avenue SE. The walkway, per Section
3.09 of the KCRS, shall be selected and designed by the Applicant's engineer in
accordance with any one of the following standards, and upon approval by
DOES, constructed.
A. A full width (8 feet) paved shoulder
B. A paved shoulder of no less than four (4) feet in width, separated by
vehicle traffic by either an extruded curb or an unpaved gravel shoulder
strip
C. A concrete curb and gutter, and sidewalk section
Other Considerations
A. Preliminary approval of this application does not limit the applicant's
responsibility to obtain any required permit or license from the State or other.
regulatory body. This may include, but not be limited to, obtaining a forest
. practice permit, an HPA permit, building permits, and other types of entitlements
as necessitated by circumstances.
B. The short subdivision shall conform to KCC 16.82 relating to grading on private
property.
C. Development of the subject property may require registration with the
Washington State Department of Licensing, Real Estate Division
Parties and Persons of Interest:
BULEN, BRENDA & KEN
19007 120TH AVENUE SE RENTON, WA 98058
BUSH, BEN & GERALDINE
19124 121ST PLACE SE RENTON, WA 98058
LABRIE, ERIC
ESM CONSULTING ENGINEERS 720 S 348TH STREET FEDERAL WAY, WA 98003
LANG ASSOCIATES
DE EN LANG 10658 RIVIERA PLACE NE SEATILE, WA 98125
YEE, FANNY & PHILIP
11431-238TH STREET WOODWAY, WA 98020
CLAUSSEN. KIM PROGRAM MANAGER Ill DDES/LUSD
DEHKORDI, FERESHTEH PROJECT MANAGER II DDES/LUSD
FOSTER, CURT SR. ENGINEER DDES/LUSD
LISA DINSMORE. SUPERVISOR, CURRENT PLANNING SECTION
JIM SANDERS, DEVELOPMENT ENGINEER< ENGINEERING REVIEW SECTION
Report and Decision -8 -L04S0065
Appeal Information and Parties of Record
RIGHT TO APPEAL
This action may be appealed in writing to the King County Hearing Examiner, with a fee of
$250 (check payable to King County Office of Finance).
As required by KCC 20.20.090 and 20.24.090, the appeal period shall be twenty one (21)
calendar days and shall commence on the third day after the notice of decision is mailed.
Filing an appeal requires actual delivery to the King County Land Use Services Division prior
to the close of business (4:30 p.m.) on April 24, 2006. Prior mailing is not sufficient if actual
receipt by the Division does not occur within the applicable time period. The Examiner does
not have authority to extend the time period unless the Division is not open on the specified
closing date, in which event delivery prior to the close of business on the next business day is
sufficient to meet the filing requirement. ·
If a timely Notice of Appeal has been filed, the appellant shall file a statement of appeal within
a 21-day calendar period commencing three days after the notice of decision is mailed. The
statement of appeal shall identify the decision being appealed (including file number) and the
alleged errors in that decision.
The statement of appeal shall state: 1) specific reasons why the decision should be reversed
or modified; and 2) the harm suffered or anticipated by the appellant, and the relief sought.
The scope of an appeal shall be based on matters or issues raised in the statement of appeal.
Failure to timely file a notice of appeal, appeal fee, or statement of appeal deprives the
Examiner of jurisdiction to consider the appeal.
Appeals must be submitted to the Department of Development and Environmental Services,
addressed as follows;
LAND USE APPEAL
Land Use Services Division
Department of Development and Environmental Services
. Black River Corporate Park
900 Oakesdale Avenue Southwest
Renton, WA 98055-1219
Any party may make a request for a pre-hearing conference. For more information regarding
appeal proceedings and pre-hearing conferences, please contact the Office of the Examiner
for a Citizens' Guide to the Examiner Hearings and/or read KCC 20.20 and 20.24.
Report and Decision . 9 • L04S0065
• SOOS CREER v\TAT~ .~ & SEWER DISTRICT
14616 s.E. 192nd St. • P.O. Box 58039 • Renton, WA 98058-1039 • Phone (253) 630-9900 • Fax (253) 630-
September I, 2005
Ms. Fanny Yee
RE: Short Plat
Dear Fanny:
K.C. D.D.E.S.
1L04S0065
/ This letter is in response to your request for a letter to reduce a JO-foot construction easement
that Soos Creek now holds for the installation of a water line to a IO-foot easement.
Soos Creek will require a minimtun ofa 30-foot easement for the installation of the water line;
however, we have no problem reducing that to a I 0-foot easement after the line is constructed.
The easement we are discussing is from Alaskan House Movers to King County Water District
No. 58 (33-23-5-21 ).
Sincerely,
fW4<~
Ron Speer
District Manager
RS:lks
C:\Linda\LETrERS\FannyYee.doc
www.soo.sc rcc k.co n1
ATTACHMENT~Z..~~
' OF 1 PAGE -""P"A"G"'E=-
/
"
,..., ... ,--_.
MENT OF OEvt'LOPMENT AND EN"1RONMENTAL SER"1CES
j ond approved this --day of ---~ 20_~ Examined and approved th,19 __ day of 20 __
" "' ""
, land Use Servfce:s Division ~-
d and approved thlf:I __ doy of ---~ 20_~ Deputy Aeseaaor
Account Number
nent Engineer
1 CASED MON .. HO MARr-OFFSETS fOR t.AON.
00)
" )>
-; ~ i! ..
S.E. 188th ST.
BM
'-0 ;..I
I q
0 ,,
r
w
U>
w
~
~
(',j ...-
$ ~ m z -;
"
~
jj
,s
i,
i
11111 1ht1
~IG
6199000041
RS-6-50
<,f--____ _
TRACT 6 3-13.oo·
GARDEN TRA<
~ VOL. 47, PAGE 90 J
I
,.: 6199000120
.,. RS-6-50
-30" EASEMENT FOR
----INGRESS, EGRESS, ---~, I
0
0 N av~;9•20• W
I ru o D
l~ l,
"'
SCALE: 1 • = 50' -~ D .• ·,;_,_
PORTION OF
SE 1/4 of SW 1/4, S. 33 T. 23 N., R. 5 E., W.M.
EXISTING LOTS
I
I
I~
6199000050
RS-6-50
~
N OIP.lii" H
6199000059
RS-6-50
I
\' I( FOUND REBAR
AND CAP
LS 16898 \ I 0.36' N. Of LINE
N 89"54'28" W i.BX t: I . / 7 \ . . _
6199000080
RS-6-50
,..__
~~~riA~\ w @l @ \ @,' ~ ~ ~\\&li O ~ /'04
5 6199000125 PlPE I 3'
RS-6-50 .P-•
f, 8 ///,
'~
0
<II
I \ .. LOT 1 ~
"' "' '£
j .
911·
-,--,
ii
"" \
PruVATE STREIT
11
'1
~...-f~WeUand Aroo
175 Sq. Ft .
o LOT6
~@ 'll_,@ z
6199000210
RS-6-50
RECREATION SPACE
I
6199000220
•· RS-6-50
, FOUND 2• IRON PIPE
30' WATER MAIN EASEMENT
RtC. NO. 7810020168C,:~
E IN PO\\Ul POLE
'· 505.27 !1
~lo
/. I :
:c
I
I
I
I
6199000142
RS-6-50
I
I
~
I ~ I'.·~
Ir ~@
I
6199000140 : RS-6-50
.;
I '
I
LEGEND
a_
0
N
.q
[ill
PO\\Ul POI.£
BOUARD
WATER VALVf.
FlRE HYDRANT
WATER METER
I
LEGAL DESCRIPTI'oN
TRACT 6, NORTHWESTERN GARDEN TRACTS, DIVISION NO. 5,
ACCORDING TO THE PLAT THEREOF, RECORDED IN VOLUME
47 OF PLATS, PAGE 90, IN KING COUNTY, WASHINGTON.
EXCEPT THE WEST 343.00 FEET THEREOF.
() z
0
b rn
(I)
. c::,
<i>
~
0
~
00
0
0
~
~
•
Laureen M. Nicolay
From:
Sent:
To:
Subject:
Laureen M. Nicolay
Monday, September 21, 2009 12:45 PM
Stacy Tucker; Kayren K. Kittrick; Jennifer T. Henning
LUA09-122, YEE (AKA HITONE) SHORT PLAT TRANSFERRED FROM KC WITH PREL
APPROVAL -Needs assigned
6-LOT SHORT PLAT PLANNING FILE TRANSFERRED FROM KC ON 9-21-2009 AFTER APPROVAL BUT PRIOR TO RECORDING.
UNSURE OF STATUS OF ENGINEERING OR LOCATION OF THOSE PLANS (IF ANY)
HAS SMALL UNREGULATED WETLAND ON-SITE ACCORDING TO COUNTY STAFF REPORT
Laureen Nicolay, Senior Planner
City of Renton Development Planning
1055 S. Grady Way
Renton, WA 98057
(425) 430-7294 phone
(425) 430-7231 fax
lnicolay@rentonwa.gov
I
Hitone Short Plat -Engineering File
Status -Final review comments not yet sent to applicant.
/'.>c.
Pa~ially prepared redlines are shown on attached plans
received June 30, 2009.
Strdctural plans for storm vault not yet submitted by
applicant.
Tree retention review comments also enclosed and not yet
sent to applicant.
D e, Pete
From:
Sent:
To:
Subject:
Attachments:
Pete:
r
I
'
Engell, Bruce
Thursday, August 20, 2009 11 :45 AM
Dye, Pete
FW: Hitone S.P. # L07SR019
SigTreeSoilsPlatDirectionsCAO.doc; ls-inf-SoilPost-ConStd.pdf;
SigTreeExPlantSoilsBond.doc
This is the corrected copy that needs to be sent.
From:
Sent:
To:
Cc:
Subject:
Pete:
Engell, Bruce
Thursday, August 20, 2009 11:38 AM
Dye, Pete
Dobkins, Doug
Hitone S.P. # L07SR019
2nd Comment List Tree / Soils Review
I have completed the second review of the above referenced short plat for Significant Tree Retention, Soils Amendments
and Bonding and have the following comments:
1. The Significant Tree Retention Plan shall follow the specific directions (attached). This is so all Tree Plans are
consistent and clear for documentation, recording, construction and inspections. The wording as shown in the directions
have blanks that must be filled in by the applicant. (4 copies are needed). It should be noted that this request was sent
previously on January 24, 2008, but not followed on this revised submittal.
2. A Soils Amendment Plan shall be submitted along with the forms that need to be filled out (see attached ... 4 copies
are needed). It should be noted that this request was sent previously on January 24, 2008, but not followed on this
revised submittal.
3. A Significant Tree Retention Bond Quantity Form shall be completed and submitted (4 copies are needed). Sent
previously but not followed on revision.
4. The lot boundary shall be shown on the tree site plan along with existing and proposed utility corridors and easements.
Requested previously but not followed on revision.
5. If there are adjacent buildings, trees or shrubs within 10 feet of the plat boundary lines that could be impacted by
clearing and grading of this, short plat they shall be shown on the plan with an explanation on how they will be protected
both above and below ground level (as in the case of impacting root structures by excavation). The applicant is
responsible for all damage to existing/adjacent buildings, trees and shrubs negatively impacted by construction occurring
on this short plat.
6. I need a valid charge and billing number in order to charge my review time to this application. Note: Is this in the City
of Renton now??
The applicant or consultant needs to read and understand the directions and information attached. If there are questions
have them contact me via e-mail at bruce.engell@kingcounty.gov .. I will need 4 copies of all plans and documents
requested.
Thanks.