Loading...
HomeMy WebLinkAboutLUA17-000263_2ndplsp2_RFA CommentsFIRE & EMERGENCY SERVICES DEPARTMENT M E M O R A N D U M   DATE: May 16, 2017     TO: Matt Herrera, Senior Planner     FROM: Corey Thomas, Plans Review Inspector     SUBJECT: SE 2nd Street Short Plat      Environmental Impact Comments: 1. The fire impact fees are currently applicable at the rate of $718.56 per single family unit. Credit would be granted for the removal of all existing homes. Code Related Comments: 1. The fire flow requirement for a single family home is 1,000 gpm minimum for dwellings up to 3,600 square feet (including garage and basements). If the dwelling exceeds 3,600 square feet, a minimum of 1,500 gpm fire flow would be required. A minimum of one fire hydrant is required within 300-feet of the proposed buildings and two hydrants if the fire flow goes up to 1,500 gpm. Existing hydrants appear adequate; the existing hydrants shall be retrofitted with a 5-inch storz fitting as neither has one now. Water availability certificate required from King County Water District 90. Fire department apparatus access roadways are adequate as they exist.