4'MIN
1' DEPTH 2% 4" ROCK
3
T SETTLING DEPTH
1.5' SEDIMENT STORAGE
V DEPTH 314"-1-12" WASHED GRAVEL
CROSS SECTION
NITS
1'OVERFLOW DEPTH
OUTFLOW
CHANNEL IF
CONSTRUCTED BY
T EXCAVATION.
FILTER FABRIC FENCING
NOTE:
MAY BE CONSTRUCTED BY EXCAVATION
OR BY BUILDING A BERM
`CY
PUBLIC WORKS SEDIMENT TRAP STD. PLAN - 211.00
DEPARTMENT
MARCH 2O08
ZI MAX SLOPE
2' MIN.
SWALE SPACING DEPENDS ON SLOPE GRADIENT
NOTES
1. CONDITION OF USE
1.1. REQUIRED AT:
1.1.1. THE TOP OF ALL SLOPES IN EXCESS OF 3HA V AND WITH MORE THAN 20 FEET OF VERTICAL RELIEF.
1.1.2. AT INTERVALS ON ANY SLOPES THAT EXCEEDS THE DIMENSIONS SPECIFIED BELLOW.
AVERAGE SLOPE
SLOPE PERCENT
FLOW PATH LENGTH
20H:1V
3-59/
300 FEET
10TO 20 H:1V
5-10%
200FEET
(4TO10)H:1\1
10-25%
100FEET
(2 TO 4)H:1V
25-50%
50 FEET
2. DESIGN AND INSTALLATION SPECIFICATIONS
2.1. FOR SLOPES STEEPER THAN 2HA V WITH MORE THAN 10 FEET OF VERTICAL RELIEF, BENCHES MAY BE CONSTRUCTED OR CLOSER
SPACED INTERCEPTOR SWALES MAY BE USED. THE DESIRE MEASURE MOST BE DESIGNED BY AN ENGINEER TO EFFECTIVELY
INTERCEPT THE HIGH VELOCITY RUNOFF TO A SEDIMENT POND OR TRAP.
2.2. CONSTRUCTION TRAFFIC OVER TEMPORARY SWALES SHALL BE MINIMIZED.
3. MAINTENANCE STANDARDS
3.1. DAMAGE RESULTING FROM RUNOFF OR CONSTRUCTION ACTIVITY SHALL BE REPAIRED IMMEDIATELY.
3.2. IF THE FACILITY DO NOT REGULARLY RETAIN STORM RUNOFF, THE CAPACITY AND/OR FREQUENCY OF THE SWALES SHALL BE
INCREASED.
PUBLIC WORKS INTERCEPTOR SWALE STD. PLAN - 217.10
DEPARTMENT
MARCH 2O08
Call 2 Working Days Before You Dig
811
Utilities Underground Location Center
(ID,MT,ND,OR,WA)
JOINTS IN FILTER FABRIC SHALL BE SPLICED
AT POSTS. USE STAPLES, WIRE RINGS, OR
EQUIVALENTTO ATTACH FABRICTO POSTS.
U
o mwn.
�
POST SPACING MAY BE INCREASED
TO 6' IF WIRE BACKING IS USED
272' BY 14 Ga. WARE OR
EQUIVALENT, IF STANDARD
STRENGTH FABRIC USED
FILTER FABRIC
BACKFILL TRENCH WITH
NATIVE SOIL
274" WOOD POSTS, STEEL FENCE
POSTS, REBAR, OR EQUIVALENT
NOTES
1. CONDITION OF USE
I.1. SILT FENCE MAY BE USED DOWNSLOPE OF ALL DISTURBED AREAS.
1.2. SILT FENCE IS NOT INTENDED TO TREAT CONCENTRATED FLOWS, NOR IS INTENDED TO TREAT SUBSTANTIAL AMOUNTS OF OVERLAND FLOW.
ANY CONCENTRATED FLOW MOST BE CONVEYED THROUGH THE DRAINAGE SYSTEM TO A SEDIMENT TRAP OR POND.
2. DESIGN AND INSTALLATION SPECIFICATIONS
2.1. THE GEOTEXTILE USED MOST MET THE STANDARD LISTED BELLOW. A COPY OF THE MANUFACTURER'S FABRIC SPECIFICATIONS MOST BE
AVAILABLE ON SITE.
30-10051EVE SIZE (0.60-015MM) FOR SILT FILM
AOS(ASTM 04751j
50-10D5IEVE SIZE (0.30-015MM) FOR OTHER FABRICS
WATER PERMITTIVITY JASTM D491
0.02SEC"-1 MINIMUM
GRABTENSIIE STRENCHT(ASTM D4632)
180LBS. MIN. FOR EXTRA STRENGH FABRIC
100 LBS. MIN. FOR STANDARD STRENGHT FABRIC
GRAB TENSILE ELONGATION (ASTM D4632)
30% MAX.
ULTRAVIOLATE RESISTANCE(ASTMI)1355)
70`>b MIN.
2.2. STANDARD STRENGTH FABRIC REQUIRES WIRE BACKING TO INCREASE THE STRENGTH OF THE FENCE. WIRE BACKING OR CLOSER POST
SPACING MAY BE REQUIRED FOR EXTRA STRENGTH FABRIC IF FIELD PERFORMANCE WARRANTS A STRONGER FENCE.
2.3. WHERE THE FENCE IS INSTALLED, THE SLOPE SHALL NOT BE STEEPER THAN 2HAV
2.4. IF A TYPICAL SILT FENCE IS USED, THE STANDARD 4X4 TRENCH MAY NOT BE REDUCED AS LONG AS THE BOTTOM 8 INCHES OF THE SILT FENCE
IS WELL BURIED AND SECURE IN A TRENCH THAT STABILIZES THE FENCE AND DOES NOT ALLOW WATER TO BYPASS OR UNDERMINE THE SILT
FENCE.
3. MAINTENANCE STANDARDS
3.1. ANY DAMAGE SHALL BE REPAIR IMMEDIATELY.
3.2. IF CONCENTRATED FLOES ARE EVIDENT UPHILL OD THE FENCE, THEY MUST BE INTERCEPTED AND CONVEYED TO A SEDIMENT TRAP OR POND.
3.3. IT IS IMPORTANT TO CHECK THE UPHILL SIDE OF THE FENCE FOR SIGNS OF THE FENCE CLOGGING AND ACTING AS A BARRIER TO FLOW AND
THEN CAUSING CHANNELIZATION OF FLOWS PARALLEL TO THE FENCE. IF THIS OCCURS, REPLACE THE FENCE OR REMOVED THE TRAP
SEDIMENT.
3.4. SEDIMENT MOST BE REMOVED WHEN SEDIMENT IS 6 INCHES HIGH.
3.5. IF THE FILTER FABRIC (GEOTEXTILE) HAS DETERIORATED DUE TO ULTRAVIOLET BREAKDOWN, IT SHALL BE REPLACED.
lzY � a� PUBLIC WORKS SILT FENCE STD. PLAN - 214.00
�R DEPARTMENT
MARCH 2O08
ROCK MUST COMPLETELY COVER THE
BOTTOM AND SIDES OF THE DITCH
6" MIN.
21V MIN.
0 oq�D C
2:1 SLOPES
NOTES
1. CONDITION OF USE
1.1. WERE CONCENTRATED RUNOFF FROM DISTURBED AREAS TO AND FROM PONDS OR TRAPS.
1.2. TO CONVEY RUNOFF INTERCEPTED FROM UNDISTURBED AREAS AROUND THE SITE TO A NON -EROSIVE DISCHARGE POINT.
2. MAINTENANCE STANDARDS
2.1. ANY SEDIMENT DEPOSITION OF MORE THAN 0.5 FEET SHALL BE REMOVED SO THAT THE CHANNEL IS RESTORED TO ITS ORIGINAL
DESIGN CAPACITY.
2.2. THE CHECK DAMS SHALL BE EXAMINED FOR SIGNS OF SCOURING AND EROSION OF THE BED AND BANKS. IF SCOURING AND EROSION
HAS OCCURRED, AFFECTED AREAS SHALL BE PROTECTED BY RIPRAP OR AN EROSION CONTROL BLANKET.
zY PUBLIC WORKS CHECK DAMS SPACING AND STD. PLAN - 217.40
DEPARTMENT CROSS SECTIONS
,T MARCH 2O08
DOES NOT NCEUDE
ASBU ET NEORMAT ON
0 FIRST SUBMITTAL
1 SECOND SUBMITTAL
2 THIRD SUBMITTAL
NO. I REVISION
Z3
m
�a
DRIVEWAYS SHALL BE PAVED TO THE EDGE
OF R-O-W PRIOR TO INSTALLATION OF THE
CONSTRUCTION ENTRANCE TO AVOID
\S,�NGRO�
DAMAGING OF THE ROADWAY
IT IS RECOMMENDED THAT THE
R = 25' MIN.
ENTRANCE BE CROWNED SO THAT
+
RUNOFF DRAINS OFF THE PAD
INSTALL DRIVEWAY CULVERT IF THERE
IS A ROADSIDE DITCH PRESENT, AS
PER CITY ROAD STANDARDS
4'A" QUARRY SPALLS
GEOTEXTILE
^8 ' �.
12' MIN. THICKNESS - _ _ , _ PROVIDE FULL WIDTH OF
NOTES INGRESSI=GRESS AREA
1. CONDITION OF USE
1.1. CONSTRUCTION ENTRANCE SHALL BE STABILIZED WHEREVER TRAFFIC WILL BE LEAVING A CONSTRUCTION SITE AND TRAVELING ON
PAVED ROADS OR OTHER PAVED AREAS WITHIN 1,000 FEET OF THE SITE.
GRAB TENSI LE STREBNGTH(ASTM D4751)
200 PSI MI N.
GRAB TENSILE ELONGATION(ASTM D4632)
30%MAX.
MULLEN BURSTSTRENGTH (ASTM D3786-SOA)
40C PSI MIN.
ADS(ASTM D4751)
20-45(U.S. STAN DARD SIEVE SIZE)
2. DESIGN AND INSTALLATION SPECIFICATIONS
2.1. HOG FUEL (WOOD BASED MULCH) MAY BE SUBSTITUTED FOR OR COMBINED WITH QUARRY SPALLS IN ARES THAT WILL BOT BE USED
FOR PERMANENT ROADS. HOG FUEL IS NOT RECOMMENDED FOR ENTRANCE STABILIZATION IN URBAN AREAS. THE INSPECTOR MAY
AT ANY TIME REQUIRE THE USE F QUARRY SPALLS IF THE HOG FUEL IS NOT PREVENTING SEDIMENT FROM BEING TRACKED ONTO
4 S O Q S O O G
PAVEMENT OR IF THE HOG FUEL IS BEING CARRIED ONTO PAVEMENT.
2.2. FENCING SHALL BE INSTALLED AS NECESSARY TO RESTRICT TRAFFIC TO THE CONSTRUCTION ENTRANCE.
2.3. WHENEVER POSSIBLE, THE ENTRANCE SHALL BE CONSTRUCTED ON A FIRM, COMPACTED SUBGRADE. THIS CAN SUBSTANTIALLY
INCREASE THE EFFECTIVENESS OF THE PAD AND REDUCE THE NEED FOR MAINTENANCE.
3. MAINTENANCE STANDARDS
3.1. QUARRY SPALLS SHALL BE ADDED IF THE PAD IS NO LONGER IN ACCORDANCE WITH THE SPECIFICATIONS.
3.2. IF THE ENTRANCE IS NOT PREVENTING SEDIMENT BEING TRACKED ONTO PAVEMENT, THEN ALTERNATIVE MEASURES TO KEEP THE
STREETS FREE OF SEDIMENT SHALL BE USED. THIS MAY INCLUDE STREET SWEEPING, AN INCREASE IN THE DIMENSIONS OF THE
ENTRANCE, OR THE INSTALLATION OF THE WHEEL WASH. IF WASHING IS USED, IT SHALL BE DONE ON AN AREA COVERED WITH
CRUSHED ROCK, AND WASHED WATER SHALL DRAIN TO A SEDIMENT TRAP OR POND.
3.3. ANY SEDIMENT THAT IS TRACKED ONTO PAVEMENT SHALL BE REMOVED IMMEDIATELY BY SWEEPING. THE SEDIMENT COLLECTED BY
SWEEPING SHALL BE REMOVED OR STABILIZED ON SITE. THE PAVEMENT SHALL NOT BE CLEANED BY WASHING DOWN THE STREET,
EXCEPT WHEN SWEEPING IS INEFFECTIVE AND THERE IS A THREAT TO PUBLIC SAFETY. IF IT NECESSARY TO WASH THE STREETS, A
SMALL SUMP MUST BE CONDUCTED. THE SEDIMENT WOULD THEN BE WASHED INTO THE SUMP WHERE IT CAN BE CONTROLLED AND
DISCHARGED APPROPRIATELY.
3.4. ANY QUARRY SPALLS THAT ARE LOOSENED FROM THE PAD AND END UP ON THE ROADWAY SHALL BE REMOVED IMMEDIATELY.
3.5. IF VEHICLES ARE ENTERING OR EXITING THE SITES AT POINTS OTHER THAN THE CONSTRUCTION ENTRANCE(S), FENCING SHALL BE
INSTALLED TO CONTROL TRAFFIC.
zY PUBLIC WORKS STABILIZED STD. PIAN - 215.10
DEPARTMENT CONSTRUCTION ENTRANCE
MARCH 2O08
B DRAINAGE GRATE
m GRATE FRAME
o p
SEDIMENT AND DEBRIS �.
FILTERED
WATER
LAX
TRIM
a a
OVERFLOW BYPASS
Pep. BELOW INLET GRATE DEVICE
o� 4
o Q A.
P P D
SECTION VEW
DRAINAGE GRATE
RECTANGULAR GRATE SHOWN
UP,
BELOW INLET GRATE DEVICE
RETRIEVAL SYSTEM (TYP.)
OVERFLOW BYPASS (TYP.)
ISOMETRIC VIEW
NOTES
1. Size the Below Inlet Grate Device (BIGD) for the stone waterstructure R Will service.
2. The BIGD shall have a built-in high -flow relief system (overflow bypass).
3. The retrleval system must allow removal of the BIGD without spllling the collected materlal.
4. Perform maintenance in accordance with Standard Specification 8-D1.3(15).
zY a� PUBLIC WORKS CATCH BASIN FILTER STD. PLAN - 218.30
DEPARTMENT
MARCH 2O08
7
k �" �r
..f >; ' 43"P'�$•Y : . �C�.7�-,a;y i:' .,�.. z,�4 'u.. ,,w,h 'A. ; .r.4 e+r ,d`aEY ,p:,:siA,r, ; z •a", a" e"
-,'^
' T z - �'§•'% 'Y" '�'IF6 '"ar ^as x • �' ... ,{::
:� ^3° -•:a ::4 .:1vn-3,T.,V�, ..,x°.�'la"y`' ,%¢j,. 4�,Y,.r=• " a s =n�
1 .9• . E of stairs
5 -0'
3: 1 sond and -
cement grout
.- 6'-0" 1. Manufacturer sholI submit shop drawings of pipe rolling for rev
•4 bar at each post 4, Midth of stairs and landing ( Design shalt De in accortlonce with AASHTO specifications.
oy 3.. when gutter and y
16 gage galvanized s roil are omitted eeQ 2. Aluminum pipe roiling sholI hove no external surface welds;..,,
steel sleeve hp % 9"
m
�iP ooc zr a•4' Tr,
+✓ ,1 1 .0% 2 r x
Non -Shrink grout y< Per (TYP)
1/2 -I 4'0 v t $
{yeQ1� rot sr y
. .o O • ar e m P 4• o MIN .aey
3 See Post 10'/z MAX (EYE) •4 Bars at t �n 3��° landing
_ F Base Deto 6..� l' 6%i OC s I Y 2 -0
POST BASE DETAIL *� ,+, a SLAB AND GRADING SECTION
A
Vie•f i�� x
. ✓�,a ,f c`
�g'Ss us'eaf F` `° c`r^•W r'w T !: 1 ,2. ,;,;,„�s;
•4 BAR AT EACH POST a n�°ate Jam.
_ � Gradeot
Dinn
0 2" MIN
r? ,,°sC^ •T`.I' ` ^yZ::},.s eke 6• R '.
e r
:.,"
( 'Compacted subgrade ..,R ��+ f�' VP�•>
c - ok
o �
c -
0
Qasks et
°i 1%t' Schedule 40 g ! -
o Pipe rat I in MY1NT L�
n • 4E OP NASIt,
I' MAX
2" MINI
azx �O 10536
/2 R MAX
'/_" keyed, Dremolded
joint filler (TYP)
Grade line
J'
Grade I'/i' �` •4. Scirs 8't 1OYi' MAX
point
Concrete Closs 4000 (TYP)
ESM 08/30/17 SURVEYED:
ESM 11/15/17 DESIGNED:
ESM 01/03/18 PDG
DRAWN:
DCL
CHECKED:
BY I DATE I APPR I APPROVED
NOTE:
FOR STAIRS WITH LESS THAN 6
RISERS NO HANDRAIL NEEDED.
SCALE: A
A
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATU M
STY-1'6 G\?
sIONAL E�
a�
N ~ See Contract EXPIRES JANUARY I7, 1999
11'MIN, 12'MAX
YA., CEMENT CONCRETE STAIRWAY
CONSTRUCTION DETAILS
TREAD SHAPE DETAIL STANDARD PLAN H- 10
_ ADOPTED
n.Eoa.�.amw.�P. tiSY p CITY OF RENTON
STANDARD PLANS
LAST DATE:05/29/1998
SP PAGE H023
ORC TY OF
RENTON
Planning/Building/Public Works Dept.
FINISHED GRADE
12" MIN. THICK
OF 1 1 /2" CRl
DRAIN ROCK
PERFORATED 6"
FILTER FABRIC
OLLOW BLOCK MANUFACTURER
JSTALLATION RECOMMENDATIONS
PER PLANS
(MAX. 3')
- FINISHED GRADE
12"
BLOCK WALL DETAIL
NOT TO SCALE
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
EARLINGTON TOWNHOMES
GRADING & T.E.S.C. DETAILS & NOTES
UTILITY PERMIT #
01/03/18
FIELDBOOK:
PAGE:
DRAWING NO:
GR-05
SHEET: OF:
12 55