HomeMy WebLinkAboutW-397108C / 5W L 0 Z 0 I- WATER PLAN GENERAL NOTES Standard Plan No. 300 1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CITY OF RENTON PUBLIC WORKS STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD SPECIFICATIONS, LATEST EDITION AS AMENDED BY THE CITY OF RENTON. A SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION. 2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL CALL 1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION. 3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND "CATALOG CUTS" FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CITY OF RENTON PRIORTO BRINGING ANY MATERIALS ON -SITE. 4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AWWA C 151 AND C 104. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250 AS PER ANSI/AWWA C110/A21.10-82. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE -TYPE, POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS. 5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS AND 48 INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER FOR ALL WATER MAINS SHALL BE 60 INCHES. ANY DEVIATIONS MUST BE APPROVED BY THE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTILITY CONFLICTS OCCUR, THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM COVER. PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALL TRENCH BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY AS DETERMINED BYTHE MODIFIED PROCTORTEST METHOD (MDD) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED AREAS. ALL PIPE ZONE COMPACTION SHALL BE 95 MDD. 6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL AND HORIZONTAL BENDS, FITTINGS AND BASE OF HYDRANTS. MEGA -LUGS (OR SIMILAR PRODUCT) MAYBE REQUIRED ON ALL MECHANICAL JOINTS IN ADDITION TO CONCRETE BLOCKING. 7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PRIORTO BEING FLUSHED, DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDER THE SUPERVISION OF A CITY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY, INSTALL AND REMOVE PLUGS, CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT/ BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL THE NEW PIPING HAS BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSURE AND PURITY TESTING. 8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP DURING THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, FLUSHED, AND THEN WATER SAMPLES SHALL BETAKEN FOR PURITY TESTING BYTHE PUBLIC WORKS INSPECTOR. 9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION. ��Y O STD. PLAN - 300.0 PUBLIC WORKS WATER PLAN GENERAL NOTES DEPARTMENT MARCH 2O10 Ell 11-1/4' BEND 22-1/2' BEND 45" BEND CAP TEE 90° BEND THRUST BLOCK BEARING AREA IN SQUARE FEET (SEE NOTES) FOR HORIZONTAL AND DOWNWARD VERTICAL BENDS SOIL FIRM SILT FIRM SILTY SAND COMPACT SAND COMPACT SAND & GRAVEL 90' 45- BEND 11 1/4' 90' 45• BEND 11 1/4' 90' 45• BEND 11 1/4' FITTING BEND TEE CAP OR PLUG & 22 1/2' BEND TEE CAP OR PLUG & 22 1/2' BEND TEE CAP OR PLUG & 22 1/2' BEND BEND BEND 4" 7.0 4.2 4.2 1.7 2.9 2.1 2.1 1.0 2.2 1.6�14O 1.0 6" 13.3 9.4 9.4 3.8 6.7 4.7 4.7 1.9 5.0 3.51.4 8 23.3 16.7 16.7 6.7 11.7 8.4 8.4 3.4 8.8 6.32.5 12" 53.0 37.5 37.5 15.0 26.5 18.8 18.8 7.5 20.0 14.05.6 AREAS CALCULATED ON 300 PSI TEST PRESSURE. 3'-0' MIN. COVER FOR WATERMAIN LESS THAN 12". 4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER. MAX. HEIGHT OF THRUST BLOCK (FT) = 0.5 x DEPTH OF TRENCH MIN. HEIGHT OF THRUST BLOCK (FT) = O.D. PIPE + 1.0' iRUST BLOCK BEARING REA REFERS TO THE 10E OF BLOCK MEASURED IN SQUARE FEET NOTES: 1. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12"DIAMETER AND FOR SOIL TYPES DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENGINEER. 2. ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND. 3. ALL POURED THRUST BLOCKS SHALL BE BACKFILLED AFTER MIN. 1 DAY. PRESSURE TESTING SHALL OCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH. 4. ALL BLOCKING SHALL BE CONCRETE CL 5 (1-1/2•). 5. BLOCKING AGAINST FITTINGS SHALL BEAR AGAINST THE GREATEST FITTING SURFACE AREA POSSIBLE, BUT SHALL NOT COVER OR ENCLOSE BELL ENDS, JOINT BOLTS OR GLANDS REASONABLE ACCESS TO BOLTS AND GLANDS SHALL BE PROVIDED. PUBLIC WORK CONCRETE BLOCKING FOR STD. PLAN - 330.2 DEPARTMENT HORIZONTAL AND DOWNWARD VERTICAL BENDS MARCH 2O10 Call 2 Working Days Before You Dig 811 Utilities Underground Location Center (ID,MT,ND,OR,WA) EXISTING WATER LINE TESTING DETAIL * t8 FT PLAN VIEW NEW WATER LINE VERTICAL CROSS(MJxFL) FOR POLYPIGGING ONE BLIND FLANGE ON TOP WITH 2'TAP & 2'PLUG ONE BLND FLANGE ON BOTTOM ONE (MJ) PLUG WITH 2' TAP & 2' TEMPORARY BLOW-DFF TEMPORARY BLOCK CUT -IN (BY CITY FORCES) TEE <FLxFL) W/ CONC. BLOCK 3- GATE VALVES (FLxMJ) 2- SOLID SLEEVES (MJ) OR RO-MAC COUPLINGS 1- PLUG (MJ) W/2'TAP & TEMP. BLOW -OFF TEMP, BLOCK EXISTING WATER LINE EXISTING WATER LINE FINAL CONNECTION DETAIL AFTER ALL TESTING, CLEANING BY POLYPIG, AND DISINFECTION, REMOVE TEMP. BLOCK & BLOW -OFF & CONNECT WITH SLEEVE (MJ) & D.I. SPOOLS FINAL CONNECTION BY CITY FORCES XISTING WATER LINE - PUBLIC WORKS CONNECTION TO WATER MAIN STD. PLAN 300.4 DEPARTMENT CUT IN -LINE TEE & THREE VALVES WATER MAIN 2" CLOSE NIPPLE I 2" 90' ELBOW - CONCRETE BLOCKING IF ADDITIONAL ADJUSTMENT IS REQUIRED, INSTALL 2-2" CLOSE NIPPLE AND 2-2" 90' BEND, SCREWED AT THIS POINT. FIELD LOCATE PLASTIC METER BOX IN PLANTER OR CAST IRON BOX IN PAVED OR CONCRETE AREAS. 2" CLOSE NIPPLE 2" 90' ELBOW 2" GALVANIZED PIPE AS REQUIRED PLAN VALVE NUT EXTENSION AS REQUIRED TWO PIECE CAST IRON VALVE (SEE DWG BR46 / PAGE B090) EQUAL TO OLYMPIC FOUNDRY CO. GROUND LINE/ CONCRETE SIDEWALK STANDARD 8" TOP SECTION, 6" MAX. ` A WITH REGULAR BASE SECTION LENGTH TO FIT. 2" RESILIENT SEATED GATE VALVE, SCREWED 2" GALVANIZED PIPE 12" LONG 2" CLOSE NIPPLE BETWEEN CAP OR PLUG AND 2" 90' ELBOW _ °o ".° °° o °e �`� INSTgJLL 4 MIL POLYETHYLENE o oa: s° ° a 18 MAX. 00- ' 0 PLASTIC COVER OVER WASHED 0o4 GRAVEL. CUT HOLE FOR PIPE �o •o°0o00 ,00 o 10 CU. FT. WASHED GRAVEL PASSING 1-1/2" AND RETAINED ON 1/4" MESH FOR DRAIN DOES NOT NCEUDE ASBU ET NEORMAT ON ELEVATION 2 1/2" NST (HOSE) AND 2 1/2" FNST CAP WITH GASKET 2"x2%2" TEE AND 2" CAP 2" CLOSE NIPPLE BEWTEEN TEE AND 90' ELBOW. 2" 90' ELBOW PUBLIC WORKS 2" BLOW -OFF STD. PLAN - 340.1 DEPARTMENT PERMANENT ASSEMBLY MARCH 2O10 0 FIRST SUBMITTAL 1 SECOND SUBMITTAL 2 THIRD SUBMITTAL NO. I REVISION FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-511D OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2" HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR, 4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE PAINT No. 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED. MIN. 18" TO 20" BEHIND BACK OF CURB OR 12" BEHIND BACK OF 3' SIDEWALK THAT IS ADJACENT TO CURB 4.875" x 5" STORZ 5'x5'x6" THICK CONCRETE PAD AROUND HYDRANT. FINISH TO MATCH SIDEWALK. 0o EXPANSION JOINT AT 2"-1 CI OF SIDEWALK �CONCRETE SIDEWALK OR PLANTING STRIP 36" MIN COVER CONCRETE J THRUST BLOCK 16" x 8" x 4" MININUM CONCRETE BEARING BLOCK UNDER HYDRANT 1 �6 CUT TWO-PIECE CAST IRON VALVE BOX WITH LUG TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8" TOP SECTION WITH REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT EXTENSION AS REQUIRED. RAISED PAVEMENT MARKER TYPE 88-A STIMSONITE TWO-WAY BLUE REFLECTIVE CONCRETE BLOCKING MAIN LINE TEE. WITH 6" FLANGE SIDE OUTLET. 6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT 6 DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT 2-3/4" COR-TEN STEEL TIE RODS. 1/2 YARD OF 1-1/4" WASHED DRAIN ROCK 1' ABOVE BOOT FLANGE. PLACE 8 MIL POLYETHYLENE FILM AROUND TOP AND SIDES OF GRAVEL. FIRE HYDRANT ASSEMBLY LEVEL ALL GROUND MIN 3' RADIUS 6" CONCRETE PAD ONE MAN ROCK- 1 6p LEVEL ALL GROUND MIN 3' RADIUS 6" CONCRETE PAD FI LL HYDRANT LOCATION IN CUT OR FILL `S Y + + PUBLIC WORKS FIRE HYDRANT ASSEMBLY STD. PLAN - 310.1 DEPARTMENT INSIDE HOUSE PREFERRED CONFIGURATION �y) 5 0 2 3 10 8 10 4 2 FLOW ADJACENT TO WATER METER PROPERTY LINE SAWDUST 5 6 9 5 FILL 7 24" MIN • 7 6" 1 FROM WATER TYP .:t° :::., ::r METER 1 103 10 8 10 4 I O2 FLOW 2 FOR 3/4" AND 1" SERVICE (3/4" SHOWN) # ITEM AMT 1 90' GALVANIZED STEEL ELBOW 4 EA. 2 3/4" PACKING JOINT COUPLING W/MALE IRON PIPE 2 EA. THREAD FOR COPPER PIPE SERVICE: FORD C84-33 OR EQUIVALENT FOR GALVANIZED PIPE SERVICE:FORD C85-33 OR EQUIVALENT 3 PRESSURE REDUCING VALVE W/STRAINER - 3/4" 1 EA. WITH UNION COUPLINGS AT INLET AND OUTLET, WILKINS 600 SERIES OR EQUAL (WITH INTERNAL BYPASS AND STRAINER) 4 3/4" CLOSE UNION - BRASS (M X F) 1 EA. 5 3/4" BRASS VALVE VARIABLE 6 12" STANDARD METER BOX W/SOLID COVER 1 EA. CONCRETE: 17 1/4 X 28 5/8 INSIDE DIMENSIONS, EQUAL TO FOG TITE METER SEAL CO. +2 PLASTIC: 13 X 24 j INSIDE DIMENSIONS, EQUAL TO BROOKS METER BOX 7 3/4" GALVANIZED STEEL PIPE, THREADED, LENGTH AS VARIABLE REQUIRED 8 3/4" X 1/4" X 3/4" STD. BRASS TEE 1 EA. 9 1/4" PETCOCK (M X F) 1 EA. 10 3/4" BRASS NIPPLE VARIABLE FUNCTION THE FUNCTION OF A PRESSURE REDUCING VALVE IS TO REDUCE HIGH-WATER PRESSURES IN THE SERVICE CONNECTION TO AN ACCEPTABLE RANGE OF 55 TO 75 PSI INSTALLATION OF A PRESSURE REDUCING VALVE IS REQUIRED WHERE THE SERVICE CONNECTION PRESSURE EXCEEDS 80 POUNDS PER SQUARE INCH IN ACCORDANCE TO THE UNIFORM PLUMBING CODE. INSTALLATION THE PRESSURE REDUCING VALVE SHALL BE LOCATED ON THE CUSTOMER'S PROPERTY "DOWNSTREAM" OF THE METER BOX. RESPONSIBILITY FOR PROPER INSTALLATION, OPERATION, AND MAINTENANCE OF THE VALVE SHALL BE ASSUMED BY THE CUSTOMER. THREE POSSIBLE CONFIGURA11ONS FOR INSTALLATION OF THE VALVE ARE SHOWN ABOVE. A BUILDING DEPARTMENT PLUMBING PERMIT IS REQUIRED PRIOR TO INSTALLATION + PUBLIC WORKS 34" & 1" INDIVIDUAL PRESSURE REDUCING STD. PLAN - 340.5 DEPARTMENT VALVE ASSEMBLY N gyp$ MARCH 2O10 ESM 08/30/17 SURVEYED: ESM 11/15/17 DESIGNED: ESM 01/03/18 PDG DRAWN: DCL CHECKED: BY I DATE I APPR I APPROVED SCALE: NITS ONE INCH AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY VERTICAL: NAVD 1988 HORIZONTAL: NAD 1983/1991 DATUM 13N24" PLASTIC METER BOX EQUAL TO MID -STATES PLASTIC, INC. BCF SERIES MSBCF 1324-18 WITH 1.75" THICK DUCTILE IRON DIAMOND PLATE COVER EQUAL TO MID -STATES PLASTICS, INC. MSCBC-1324-R WITH READER LID AND 2" DRILLED HOLE FOR TOUCHREAD PIT LID (SEE DETAIL A -A) 9" MIN 12" MAX FINISH GRADE L `✓ a w ) 0 36" MIN1 COVER, N M U CITY PRIVATE PIPING PIPING IIN UNIMPROVED RIGHT OF WAY INSTALL METER BOX AT PROPERTY LINE WITH 12" w LONG COPPER TAILPIECE. w a I SIDEWALK a TOUCHREAD WATER METER TO BE 12 SUPPLIED BYTHE ¢ 0 CITY TYPE "K" SOFT o COPPER TUBING NEW DUCTILE IRON WATERMAIN IF SERVICE LINE TO HOUSE IS 3/4" OR 1" TO BE INSTALLED IN THE FUTURE GALVANIZED INSTALL FORD C14-33 OR 44 FIPT PLUG x COMPRESSION COUPLING LOOP DOWN TO CENTERLINE OF WATER MAIN TO PROVIDE SLACK IN COPPER COPPERSETTER FOR 5/8"x3/4" METER: FORD SERVICE LINE TO METER. VBH72-15W-44-33G, OR McDONALD BRASS: 21-215WCQQ33, OR MUELLER: 3/4-B-2470-2 WITH ANGLE BALL VALVE ON INLET AND SINGLE CHECK VALVE ON OUTLET CORPORATION STOP WITH BALL VALVE. FORD COPPERSETTER FOR 1" METER: FORD VBH72-15W-44-44G, OR TAPERED THREAD (CC). QUICK JOINT McDONALD BRASS: 21-415WCQQ44, OR MUELLER: 1-B-2470-2 (3/4" FB1000-3-Q) OR AY MCDONALD 4701E BOTH INLET AND OUTLET WITH QUICK JOINT. PADLOCK WINGS ON (1" FB1000-4-Q) OR AY MCDONALD 4701E INLET ANGLE BALL VALVE AND SINGLE CHECK VALVE ON OUTLET. ALL FITTINGS SHALL BE WITH QUICK JOINT. NOTE: ALL METER BOXES INSTALLED WITHIN CONCRETE OR PAVED DRIVEWAYS SHALL BE CAST-IRON EQUAL TO OLYMPIC FOUNDARY. EXPANSION JOINTS MUSH BE INSTALLED ON BOTH SIDES OF METER BOX. A- A DRILL 2" DIA. HOLE FOR AMR (AUTOMATIC METER READ) TOUCHREAD DEVICE L 2-1/2" MIN. FROM NEAREST AND FRONT EDGE OF PIT LID TYPICAL RIB NOTE: THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM UNDERNEATH RIBS UNLESS THE RIB SPACING ALLOWS THE NUT TO TIGHTEN AGAINST THE OPEN SIDE OF MORE THAN ONE RIB. f1UBLIC WORKS 34" AND 1" WATER SERVICE STD. PLAN - 320.1 + � � .r T�np,M1,F?TA,T1G'1"TT • C TY 0E UR RENTON V439• Planning/Building/Public Works Dept. IN COMPLIANCE WITH CITY OF RENTON STANDARDS EARLINGTON TOWNHOMES WATER DETAILS & NOTES UTILITY PERMIT # 01/03/18 FIELDBOOK: PAGE: DRAWING NO: WA-06 SHEET: OF: �fd 45 55 U D u0 u- W-397108