DATE: June 22, 2017
TO: Clark Close, Senior Planner
FROM: Corey Thomas, Plans Review Inspector
SUBJECT: Comments for US Bank
_____________________________________________________________________________
Environmental Impact Comments:
1. Fire impact fee of $0.21 per square foot of additional space shall be charged at time
of building permit issuance.
Code Related Comments:
1. Existing fire sprinkler system shall be extended into the building addition. Separate
plans and permits are required to be submitted to and obtained from the Renton Regional
Fire Authority.
2. Proposed building addition is in direct conflict with the existing established fire lane
apparatus access roadway and a new fire lane roadway shall established around the
proposed addition. Additional existing parking lot and parking spaces will have to be
relocated/eliminated in order to accommodate a new fire lane. Fire lane width is required
to be a minimum of 20-feet wide and turning radius are 25-feet inside and 45-feet
outside. Fire lane signage required per city code.
3. Existing fire hydrant appears it will need to be relocated along with perhaps the fire
department connection and backflow vault for the fire sprinkler system. Backflow vault
shall be protected from vehicular traffic or replaced with a traffic rated vault.
CT:ct