Loading...
HomeMy WebLinkAboutLUA17-000324_usbank2_RFA Comments.pdf CITY OF RENTON FIRE PREVENTION BUREAU MEMORANDUM _____________________________________________________________________________ DATE: June 22, 2017 TO: Clark Close, Senior Planner FROM: Corey Thomas, Plans Review Inspector SUBJECT: Comments for US Bank _____________________________________________________________________________ Environmental Impact Comments: 1. Fire impact fee of $0.21 per square foot of additional space shall be charged at time of building permit issuance. Code Related Comments: 1. Existing fire sprinkler system shall be extended into the building addition. Separate plans and permits are required to be submitted to and obtained from the Renton Regional Fire Authority. 2. Proposed building addition is in direct conflict with the existing established fire lane apparatus access roadway and a new fire lane roadway shall established around the proposed addition. Additional existing parking lot and parking spaces will have to be relocated/eliminated in order to accommodate a new fire lane. Fire lane width is required to be a minimum of 20-feet wide and turning radius are 25-feet inside and 45-feet outside. Fire lane signage required per city code. 3. Existing fire hydrant appears it will need to be relocated along with perhaps the fire department connection and backflow vault for the fire sprinkler system. Backflow vault shall be protected from vehicular traffic or replaced with a traffic rated vault. CT:ct usbank