HomeMy WebLinkAboutP_Utility Plan UW VMC MOB Sheet2_105084324_V1_17041915'
15'
8'11X11 WORK PIT
11X9 WORK PIT
4X4 WORK PIT
(1) RUN 3Ø 1/0 PRI, ± 50'
1-2" SCH'L 80 CONDUIT, ± 15'
(1) RUN 3Ø 4/0 PRI, ± 390'
1-2" SCH'L 80 CONDUIT, ± 370'
277'
82'
(1) RUN 1Ø 4/0 PRI, ± 35'
1-2" SCH'L 80 CONDUIT, ± 15'
SCALE: NONE
CIRCUIT ONE-LINE DIAGRAM
4'-0"
1'-0"
5'-8"
8"
7'-0"
Tubes for 1"
adjustable bolts ( 4)
Cover
2,490 lbs
Top Section
1,835 lbs
Base
4,760 lbs
4'-8"
(2) 3' Square
Plate Doors
NOTE: For Installations in pavement or sidewalks with adjustable cover
SIDE VIEW
TOP VIEW
9'-0"
11'-0"
2"
6'-0"
6"
Crushed
Rock
3-piece handhole, increase excavation Depth to 6'-6" and 24 cubic yards.
4'-8" x 7' Handhole ( 575) w/adjustable Cover
MID#: 7663206
VAULT & EXCAVATION DETAIL
Not to scale 6051.1500
Excavation - 20 cubic yards
Communications
Primary Power
Cables or Conduit
Excavated Dirt Pile
ROADSIDE
Final Grade
24" Min
4" Min
Separation
36"
Min
Cover
48"
Max
Backfill
(No rocks over 10" diameter)
Separation
12" Min
Gas
4" Sand Bedding
32" Typical
(Power, Gas, and
Communications)
JOINT TRENCH DETAIL
Primary-Mainline Gas & Communications (NTS)
Separation
12" Min
6" or 12" Min Sand Shading after Compaction
- A 6" layer of sand is allowed when excavated native material contains rocks no larger than 8" in diameter.
Trench and backfill requirements for primary electric line extension trenches (No PSE gas)
- A 12" layer of sand is required when excavated native material contains rocks up to 10" in diameter.
2"
Excavation - 20 cubic yards
10'-0"
7'-0"
8'-0"
8"
6'-2"
SIDE VIEW
6'-6"Crushed
6"
Rock
11'
11'
TOP VIEW
5'-6"
7'-0"
6775.0030Not to scale
VAULT & EXCAVATION DETAIL
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
BRAD ELKIN 425-495-6489 03/30/17
BRAD ELKIN 425-495-6489 03/30/17
N/A N/A N/A
J. REIBMAN N/A 03/30/17
EASEMENT REQUIRED CITY OF RENTON
UW VMC MOB
INSTALL 3Ø J-BOX & 3Ø L/E & PM TRF
400 S 43ST, RENTON, WA 98055
N/A N/A
N/A 105084325
AS NOTED 2/2
KING N/A N/A CSPSKEIN
T23N, R05E, NE SEC 31 N/A N/A
2305E121 2305E124 2305E121 VIC-16
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
Not to Scale
Standoff Bracket
15" Min Length
Conduit Clamp Conduit
Field Face
Quadrant
Climbing
Space
Road Face
Quadrant
Climbing
Space
5" Min
CL LCDirection of Vehicular Traffic
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
18" MIN
18" MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
6775.0035 Not to scale
5' MIN
5' MIN
5'
MIN
10' MIN OF CLEARANCE FOR NON COMBUSTIBLES