HomeMy WebLinkAboutP_Utility Plan_101105002_V1-170510LIND AVE SW316471-165629
316474-165628
316465-165628
316471-165641
WORK
ZONE
SE 43RD ST
SW 43RD ST LIND AVE SWSW 41ST ST
WORK
ZONE
SITE PLAN
Owner / Developer Contact Info
officeATTN:
IKEA PROPERTY INC
420 ALAN WOOD RD
CONSHOHOKEN, PA 19428
JIM MEYER (425) 484-4100 101105002THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
SITE SPECIFIC NOTES
OVERHEAD CIRCUIT MAP(2305E124)
SCALE: 6" = 1 MILE
CIRCUIT FEET REMOVED: 160'
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
GAS
PHONE
CABLE TV
504547479 101105002
N/A 108100584
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Perm. Service
Relocation
Removal
Temporary
Job Order
Distribution
HP Main
HP Svc/MSA
DESIGNED BY
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
D. KUMAR (425) 516-5486 4/28/17
NATE LINVILLE (253) 970-7284 4/28/17
N/A N/A N/A
NATE LINVILLE (253) 970-7284
REQUIRED RENTON
IKEA - VAULT RELOCATION
REMOVE 3Ø JVAULT, INST. 2 - 3Ø VAULT,
601 SW 41ST ST, RENTON, WA 98057
PUGET SOUND ENERGY
N/A N/A
N/A 101105002
AS NOTED 1 OF 1
KING N/A N/A CSPSKEPM
NW-31-23-05E N/A N/A
2305E122 2305E124 2305E122 VIC-17
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SCALE: 6" = 1 MILE
UNDERGROUND CIRCUIT MAP
POWER GENERAL NOTES - COMMERCIAL PROJECT
8.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits
and crossings from the individual unit's meter base to the designated connection point.
Inclement weather conditions may cause delays in construction times and dates.
1.
2.
3.
4.
5.
6.
7.
9.
11.
10.
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:DEVENDRA KUMAR
(425) 516-5486
DEVENDRA.KUMAR@PSE.COM
N
Vicinity Map
N/A
AT J01: EXISTING
REMOVE EXISTING 575 VAULT, LID, AND JBUS
ABANDON EXISTING CABLES IN PLACE
AT J02: NEW
-INSTALL 5' X 7' X 5' VAULT & LID 6055.1030 (JB0X15L)
-INSTALL 3- 4POS J-BOX
-INSTALL 6- L/B ELBOWS & 6- DUST CAPS 6041.1000 (ELB10J)
-INSTALL GRID 316477-165628
AT J03: NEW
-INSTALL 5' X 7' X 5' VAULT & LID 6055.1030 (JB0X15L)
-INSTALL 3- 4POS J-BOX
-INSTALL 6- L/B ELBOWS & 6- DUST CAPS 6041.1000 (ELB10J)
-INSTALL GRID 316461-165628
SPAN NOTES:
IP1 TO J01
-INTERCEPT EXISTING CABLES AØACE543, BØACE544, CØACE545 RE-ROUTE TO J02
J02 TO J03
-INST. 3 - 1/0 AL SOL JKT CABLES 160'± ____ACTUAL
-INST. CABLE TAGS AØEHM618, BØEHM619, CØEHM620
IP2 T0 J03
-INTERCEPT EXISTING CABLES AØAGI337, BØAGI338, CØAGI339 RE-ROUTE TO J03
THREE PH PRIMARY J-BOX DETAIL
6055.1030-01Not to scale
7'-0"
4'-8"
4'-0"
1'-0"
Internal vault ground
installed by manufacturer
4760 lbs
Two 3' Sq Std Plate Doors
2490 lbS
Base
Cover
TRENCH DETAIL
Electric Service Cable in Conduit (NTS)
Electric Service Cable in Conduit
Excavated Dirt Pile
Final Grade
24" Min
24" Min
to
36" Max
Cover
12" Typical
(6" Min)
Backfill for Conduit
Free of rocks
larger than 8"
in diameter)
36" MINIMUM COVER
IN RIGHT OF WAY
To Excavated Dirt Pile
3" Schedule 40 Grey PVC
Backfill for In Conduit - The backfill layer shall be soil that is free from construction debris,
glass, sharp rocks, frozen clods, and rocks larger than 8" in diameter.
SCALE: 1" = 20'
CUSTOMER TO REMOVE
BRUSH AROUND
TRANSFORMER