HomeMy WebLinkAboutP_Sketch_101101327-V1_170525PSE GENERAL SPECIFICATIONS
ABANDONING PRIMARY CABLES PSE std. 6825.6200
General
In a Vault if the cable is
Existing Utilities:
- All work is to be completed per PSE Standards & Practices. Copies of all PSE Standards
Hand excavate (pothole) all marked utility crossings to verify exact location and depth at point
7. Remove all "Danger Do Not Operate" tags.
are available upon request.
In conduit,
-Remove the cable
- Work sites shall be kept clear of debris and all construction materials, equipment and
Not in conduit or it cannot be pulled out,
-Cut the cable off approximately one foot
packing shall be removed daily.
Maintain existing electrical system in service until new system is complete, tested, and ready* for service.
from the vault wall.
- Return all unused and removed poles, transformers and hardware to PSE, storeroom. All
installations. Transition trench or tunnel profile gradually as required at crossings. Maintain
-When practical, attach the old cable
copper shall be coiled and returned the day it is removed from the poles. Remove all unused
The general scope of this project is to remediate primary 1/0 cables within the project area by the most economic
number to the cable stub.
pins and insulators.
Excavation
The project involves replacing existing electrical cables in new conduit.
- Return all Street lights, area lights and floodlights to Sumner yard.
In a Minipad hand hole
36" of cover for primary conductors and 24" of cover for secondary conductors.
- All fault indicators will be maintained in their current location on the 1/0 cables upon
- Road crossings and all trenches within the Right-of-way shall be of sufficient depth to
Project location: 1805 GRANT AVE S., RENTON, WA 98055
completion of the job. If it is noted to remove any of the indicators they shall be returned to
In conduit,
-Remove the cable
local PSE first response department for re -issue.
- Back fill in road crossings and within the Right-of-way shall be compacted to 95% density or
Cable Footage Estimated : 5,035'
Preconstruction
Not in conduit or it cannot be pulled out,
-Cut the cable off as much as practical
Cable Numbers Repaired: 0
#2 Print Name
-When practical, attach the old cable number to
- Notify appropriate city, County or DOT authorities 48 to 72 hours, or as required by
Cable Numbers Replaced : 3430-32, 3983, 3975, 16079, 16080, ABD078, 3544-51, 10442, 4590-95
the cable stub.
permitting agency, in advance of starting work in Right-of-way involving a Permit.
- Vaults shall be placed level and 2" above final grade in landscaped areas and flush with
-Stuff the tail into the bottom of the
- All system switching shall be approved by System Operations (425-882-4652) a minimum
24-hour advance notice of no parking in work areas. Access will be maintained to all residences and their
handhole. Be sure the new cables are not
Of 48 hours in advance.
- All conduit entrances shall be grouted.
trapped by the old cables or the concentric
- Notify customers of all outages 48 hours in advance.
Traffic Revisions
neutrals.
Work Drawings & Documents
- Unless splices are called for, or otherwise noted or approved, conduit risers shall be
hours.
- Field design changes shall be approved by PSE Project Manager or Engineer.
At Risers if the cable is
- Install insulating caps on all unused primary bushings.
- Mark all field changes, equipment ID numbers and Underground cable information in red on
- Civil crew to install Conduit plug on each end until new cable to be installed.
HANDHOLE
Foreman's copy of work sketch.
In Conduit
-Remove Cable
- Return one Foreman's copy of work sketch to Project Manager at completion of job.
Direct buried or it cannot be pulled out,
-Cut off & cap the cable at the top of the riser.
- When permits are required, a copy shall be available On work site at all times.
and the pole will remain.
-Attach the old cable number to the cable stub.
Safety
POTELCO DESIGN AND
INDEX
- Refer to PSE standards 6275.3000 and 6275.6000 for system ground requirements.
X.F.M.R. = TRANSFORMER
QUALITY ASSURANCE
- Refer to PSE standards 6275.9050 for personal protective grounding requirements.
DIRECT BURIED
Direct buried or it cannot be pulled out,
-Remove the riser.
- Refer to PSE standards 6275.9150 for vehicle grounding and barricading requirements.
and the pole will be replaced
-Cut off & cap the cable underground near the base of the
- Proper line clearances shall be taken at the beginning, and released at the end, of each
❑ This design complies with PSE
Design/Engineering Standards.
pole.
work day, or as otherwise instructed by the System Operator.
Any/all variations have been
pre-approved/documented by the
Traffic /Pedestrian control notes
The cable is direct buried or it cannot be
-Cut off & cap the cable underground near the base of the
appropriate PSE Representative.
pulled out, and the pole will be removed.
pole.
- Utilize flagging and other vehicle traffic control as necessary and in conformance with local
signature "e'g,
PAGE 6 - CIVIL PLAN
traffic regulations.
�6
Print Name C!'t `i � �l > ih
-The uniform code of traffic control shall be adhered to at all times..
neutral is connected with a hot tap, replace it. If the transformer bank has a 2 -bolt connector on
-Provide signs, barricades, and traffic control in conformance with local permit regulations.
the neutral bus, replace it.
-Provide route for pedestrians when working on or near sidewalks.
NOTE: If the pole is to be replaced, remove the abandoned riser and elbow, and stand off brackets
(unless they support other conduits).
-Maintain traffic flow as required by permitting agency.
NOTE: If the riser is made of transite material, it shall
be removed following procedures in standard 0100.5000,
"Transite Pipe Removal and Disposal."
NOTE: Completely rebuild terminations. EXCEPTION: DO NOT REPLACE CUTOUTS
UNLESS THEY ARE THE OLDER "BOX TYPE" OR 50 AMP "TRIP LINK" TYPE CUTOUT.
-Remove (not abandon) aboveground transite riser when it is encountered in the field. Belowground transite may be left in
REPLACE J -BOXES IF REQUIRED. UTILIZE FEED-THRU T.U.T.S AND REMOVE
place and backfilled. (Transite is a mixture of asbestos
to moisture, low temperature, and corrosive agents).
and cement. Itis nonmetallic, flame-retardant, and resistant
J -BOXES IF POSSIBLE. REPLACE ALL TRANSFORMER JUMPERS WITH NEW 1/0
-For removal use an approved certified abatement contractor. Call the Environmental Services Department 24-hour pager
JACKETED CABLE.
(206-994-3186) to have a contractor dispatched.
Procedure to Abandon Primary Cables:
UNDERGROUND CONSTRUCTION
1. Call the Systems Operator to request a clearance.
2. Follow the directions to ensure the cable is de -energized, apply proper tags as specified in Standard Practice
Additional notes to standards.
0201. 1011, "Switching and Clearances Handbook,"
and report back to the Systems Operator.
-Erosion control must be placed before construction starts. Silt bags must be installed in
3. Obtain a clearance from the Systems Operator
on the cable to be abandoned.
A t t h b
4. Cut the ends of the cable.
owns ream ca c CIO HO. 5. The cable number tag may be left on the abandoned cable.
SURFACE IMPROVEMENT AND RESTORATION
1) FOLLOWING FINAL GRADING ACTIVITY, SOD SHALL BE PLACED ON EXPOSED
SOIL TO PROVIDE PERMANENT AND IMMEDIATE EROSION PROTECTION.
2) TEMPORARY COLD MIX SHALL BE PLACED ON EXPOSED GRAVEL
IN HARD SURFACE FOR IMMEDIATE EROSION PROTECTION AND HOT MIX ASPHALT
WILL BE APPLIED AT FINAL RESTORATION TO PROVIDE PERMANENT EROSION
PROTECTION.
EXPOSED SOIL PROTECTION NOTES:
AREAS WHERE THE GRADING ACTIVITIES, BORE PIT EXCAVATION OR UTILITY POT HOLING,
WILL BE TEMPORARILY STABILIZED BY ONE OF THE FOLLOWING METHODS WHICH ARE
BASED ON PERIOD OF EXPOSED SOILS ARE LEFT UNWORKED.
-THERE WILL BE NO EXPOSED SOILS ON SITE DURING CONSTRUCTION.
ALL SPOILS FROM EXCAVATION WILL BE VAC EXCAVATED INTO THE TRUCK.
EROSION & SEDIMENT CONTROL REQUIREMENTS
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR v'VORK IN SENSITIVE AREAS.)
Filter fabric skirt
Secured with grate.
Catch Basin Grate
Collected Sediment
M -4 --overflow
y
A, Filter fabric walls for
dewatering sediment
I
Catch Basin Insert
MID 9995728
Gravel bags (MID 9995692)
must be h gher at sides
than center.
6" Min
44"
Gravel Check Dam
EROSION CONTROL
NOT TO SCALE
NOTE: The cable number shall not be reused.
Existing Utilities:
6. Call the Systems Operator and release the clearance.
Hand excavate (pothole) all marked utility crossings to verify exact location and depth at point
7. Remove all "Danger Do Not Operate" tags.
of crossing. Protect underground utilities during excavation. Use hand excavation methods if
8. The System Operator will then close the Incident Number (1 -number).
necessary to avoid damage to existing utilities. Fabricate and install adequate temporary
Existing System:
structures to support and protect underground utilities while exposed during construction.
FUSED DISCONNECT:
J
Maintain existing electrical system in service until new system is complete, tested, and ready* for service.
Maintain 6" minimum clearance at CrOSSIngS between existing utilities and new duct
Disable existing system only to make cutovers and connections as directed br PSE System Operator.
installations. Transition trench or tunnel profile gradually as required at crossings. Maintain
SCOPE OF WORK
24" minimum separation between new trench or tunnel and parallel existing utilities or as
The general scope of this project is to remediate primary 1/0 cables within the project area by the most economic
required by the permit agency.
means possible using replacement, or abandonment.
Excavation
The project involves replacing existing electrical cables in new conduit.
- Trenching outside of the Right-of-way shall be of sufficient depth to provide a minimum of
❑
36" of cover for primary conductors and 24" of cover for secondary conductors.
Project type : Planned
- Road crossings and all trenches within the Right-of-way shall be of sufficient depth to
Project location: 1805 GRANT AVE S., RENTON, WA 98055
provide a minimum of 36" of cover for all conductors or as required by the permitting Agency.
CRUSHED SURFACING
- No rocks larger than 6" shall be included in backfill
Number of Cables: 24
- Back fill in road crossings and within the Right-of-way shall be compacted to 95% density or
Cable Footage Estimated : 5,035'
as required by the permitting Agency.
Cable Numbers Injected : 0
- Restore all excavated areas to original condition.
Cable Numbers Repaired: 0
#2 Print Name
Cable Numbers Abandoned: 0
Vaults & Hand holes
Cable Numbers Replaced : 3430-32, 3983, 3975, 16079, 16080, ABD078, 3544-51, 10442, 4590-95
- Refer to PSE standard 6775.0040 "Vault and Hand hole Installation"
Trench Footage Estimated : 3,757'
- Vaults shall be placed level and 2" above final grade in landscaped areas and flush with
There will be an advance notice provided by the contractor
I r when laced in hard surface areas.
n
final grade de p
24-hour advance notice of no parking in work areas. Access will be maintained to all residences and their
- A minimum 6�� bed of 5/8�� crushed rock shall be placed under all vaults.
driveways. When work is occurring directly in front of driveways, the contractor will work with the residence to
- All conduit entrances shall be grouted.
manage access.
Conductors & Conduit
Traffic Revisions
- Refer to PSE standard 6800.6000 "PVC Conduit Installation".
Flagging crews will maintain one lane; flaggers will assist vehicles alternating through the roadway during work
- Unless splices are called for, or otherwise noted or approved, conduit risers shall be
hours.
plumbed directly to road crossing conduits.
For more information on the project
- Install insulating caps on all unused primary bushings.
24-hour project information (888) 471-7339, (360) 825-5236
- Civil crew to install Conduit plug on each end until new cable to be installed.
HANDHOLE
- All "spare" conduits shall be capped at each end.
SINGLE PHASE, ONE WIRE/CABLE - 7.2 KV
Surface Restoration
_____ TRENCH PATH
Restore ground surface to original contour and original condition or better. Restore asphalt
ABBREVIATIONS
and concrete in accordance with requirements of local permitting agency. Cold patch or plate
w w w— EXISTING WATER
trench when necessary. Leave area in its original state or better at the end of construction.
P.E. = POLYETHYLENE
POTELCO DESIGN AND
INDEX
PHONE#
X.F.M.R. = TRANSFORMER
QUALITY ASSURANCE
Tom. EXISTING TELEPHONE
OVERHEAD APPARATUS
N.T.S. = NOT TO SCALE
—G—G—G—G—
PAGE 1 - GENERAL NOTES
When performing planned work on a pole with an existing transformer or device, the Service
INCIDENT
N/A
Order
N/A
SCALE
AS NOTED
❑ This design complies with PSE
Design/Engineering Standards.
PAGE 2 - SITE PLAN
Provider will change out bolted connectors to pressed connectors". Use unit 1-3A to charge
Any/all variations have been
pre-approved/documented by the
PAGE 3 - CONDUIT & CABLE
PAGE 4 - ONE -LINE DIAGRAM
time.
appropriate PSE Representative.
PAGE 5 - CIVIL PLAN
If you are working on a pole with the pole ground connected with a hot tap, replace it. If the
signature "e'g,
PAGE 6 - CIVIL PLAN
transformer has split bolts on the secondary neutral or services, replace them. If the primary
�6
Print Name C!'t `i � �l > ih
neutral is connected with a hot tap, replace it. If the transformer bank has a 2 -bolt connector on
Date 1r
the neutral bus, replace it.
SURFACE IMPROVEMENT AND RESTORATION
1) FOLLOWING FINAL GRADING ACTIVITY, SOD SHALL BE PLACED ON EXPOSED
SOIL TO PROVIDE PERMANENT AND IMMEDIATE EROSION PROTECTION.
2) TEMPORARY COLD MIX SHALL BE PLACED ON EXPOSED GRAVEL
IN HARD SURFACE FOR IMMEDIATE EROSION PROTECTION AND HOT MIX ASPHALT
WILL BE APPLIED AT FINAL RESTORATION TO PROVIDE PERMANENT EROSION
PROTECTION.
EXPOSED SOIL PROTECTION NOTES:
AREAS WHERE THE GRADING ACTIVITIES, BORE PIT EXCAVATION OR UTILITY POT HOLING,
WILL BE TEMPORARILY STABILIZED BY ONE OF THE FOLLOWING METHODS WHICH ARE
BASED ON PERIOD OF EXPOSED SOILS ARE LEFT UNWORKED.
-THERE WILL BE NO EXPOSED SOILS ON SITE DURING CONSTRUCTION.
ALL SPOILS FROM EXCAVATION WILL BE VAC EXCAVATED INTO THE TRUCK.
EROSION & SEDIMENT CONTROL REQUIREMENTS
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR v'VORK IN SENSITIVE AREAS.)
Filter fabric skirt
Secured with grate.
Catch Basin Grate
Collected Sediment
M -4 --overflow
y
A, Filter fabric walls for
dewatering sediment
I
Catch Basin Insert
MID 9995728
Gravel bags (MID 9995692)
must be h gher at sides
than center.
6" Min
44"
Gravel Check Dam
EROSION CONTROL
NOT TO SCALE
SS EXISTING SEWER
Trench and backfill requirements for primary electric line extension trenches
- A 12" layer of sand is required when excavated native material contains rocks up to 10" in diameter.
- A 3" layer of sand is allowed when excavated native material contains rocks no larger than 8" in diameter.
Excavated Dirt Pile
ROADSIDE
Final Grade
12" Typical 24 Mi — ►{ /i\//\/i\//\/i\
36" Min Cover (ROW)
24"Min Cover
(Pvt. Property)
48"
Max
TRENCH DETAIL
NOT TO SCALE
Backfill
P��f No rocks over 10" diameter)
j� 12" Min Sand Shading
j\ 3" Sand Bedding
—Primary Power in DB120 Conduit (ROW)
Primary Power in SCH80 Conduit (Pvt. Property)
Cables or Conduit
- iG r - 3�'A_iM 25T I
100T 1 30 CLX X5005
,}• ? X229 30�'
�. S 5 ST p'.' x5002 1
•''3
• I `° I i� I �, oNo aoo j 4oT S 04641 co
I I COCK N I N 04 CD �°' 7176 I zt
a..... I N o x �� 1' X7175
G j� ` x� 1 X X �X 100T
�• X
30: .. :3 �_� o �' o�1�t+25T�
• ••• Q colw NZoIN V I -r7 •'.30 • co a' 7174 ^ I 1 B P X1459
U21S.:. ' ,.� a I X G ccooc .:3b. o� �• � 1 I �� 15T.•...0
�I t I Y@ X r- X X 11007 C
r 'C 100TIOnX2297 •Y�100T ;��„ 40TS 7 STt................
A
0376 X5688 N X626 GRA A; ~off I I O .......A ••
1007 X8394 o� 2I N I
4 100T . 3 16 B : '-X i� � I i......... S
UG 188_ _ _ IW x
3b �'—•}_ _yi PHIL LIP
S •'s T 00385 s X1 0477 25TI I =I ARNOLD
•00098 14 ,� 1 I PARK
�••• c=�:.� = X4835 I �
. 3 fb
EAR -x'34••., GRA } c ccc - 405
15 r h ...... •.: 26 V y GRA
756•-330 30 �. , ; 00514 n; •i ;30 , .0
16
GRA
.30 ll05 7Ms ��:• '� ':..;A
26
J22113 . B ;30 t
' 3s� •s•U2217 s 723 T
1 r, -c N H
/C BC n� IC 1�oIC XLr) .'30: �•• :B S
' XN Lr)! I� �/ a� <S ..11 Z C, : :.,C•� ,35�...:
T '04 Min 257 40T C �'� X11262 �•.• ''s„ ; •� 25A
... 1 1 C 25T 1 N X25 '-
146 S q1 X _ X��S� A'.�8•'••••' 30':•' A
t m1 cn1 1 �� ; 16 S 65 a, ' .•C: B: :A
• c� C 40T Q' s'T :: ....
' .......
3�'•, 67 `11 1t` Qi 117 ST tti.' .•X4657 30 �..
CONO ::eo
C ......:A
L4J+fit , 1 / GRA •B �WN9 ; A. -'N..... :A
' BNa•
WN�1 o C 25 �1 %... •: "
ST t Q S A 19 Z1 _ �V�c
T�-A 2Y_ 00.30 3�'' I..... E B,C .B •:,C •(��
5T ..3 3 (/?¢ I• $ �- ......B (T
...- 16 �oX9 99 PU :.... • Y I c• A QJ
Vic c � ^ e 70106
?J rte¢ • .;•1 X1055 3 o : A
Q I o 't ST •
21S cM y WNO X247 'B ,'c•"A •..30 C • ...;.
:W
67 ZI BAB3� (/
0902 X11 a67 r �I 257 .I 1...3 : • . ....
' •.�
889 :A ... 1 I.••
U869 s
X11a6B x11164 :i i' . :3� .... 30:
657: TALBOT c:'Z :N�
iH/LL 3 A' C:'
V
:A ELEO ; B GRA
•';� �A •: 25 X7520 r' �o
NELSON po
1042 A' S 965 30- 'ys 6TI� X
B� X721 Q
Vic Q: ti. S 30 loor 407
16 A 'ST.'A A- ''N :' SK746 3�.ST 257 W SE 1257
W65 ' S '�.• . X S 27 t
B �uICO2358
.. X1781 063 21, '.� •' ,C m '•.D c. m� X 006 C — -IW Q I
100 . � . "�' _'�� B...• 'Z '•rte` :Q �so� SK 685'
OVERHEAD CIRCUIT MAP: 2305E088
SCALE 611 = 1 MILE
12" MIN
48" MAX
36" MIN (ROW)
24" MIN (Pvt. Property)
Primary Cable(S) -
in Conduit
12"
LEGEND
FOREMAN (CHECK BOX WHEN COMPLETED)
-�
12" MIN
ELECTRONIC MARKER
Q
SOLID BLADE DISCONNECT
J ❑
UNDERGROUND COMBINATION J-BOX/XFMR
'
FUSED DISCONNECT:
J
COMBINATION J-BOX/PADMOUNT XFMR
Material VERIFIED and CHANGES noted on Paperwork.
10T, 15T, 25T, 40T, 100T - INDICATES FUSE SIZE
❑
ASPHALT PATCH, 2" MIN
—I (—
NORMAL OPEN (N.O.)
J ■
NEW UNDERGROUND COMBINATION J-BOX/XFMR
❑
Indicate correct FUSE SIZE an As -built & VERIFY proper PHASE.
❑
❑
-j W b�
WILL NOT PHASE (WN0)
J A
NEW COMBINATION J-BOX/PADMOUNT XFMR
❑
CRUSHED SURFACING
I certify that the work performed meets PSE's standards and procedures
TOTAL UNDERGROUND XFMR (T.U.T.)
CD—
OVERHEAD TO UNDERGROUND CABLE TERM.
#1 Foreman's Signature
#1 Print Name
O�
NEW OVERHEAD TO UNDERGROUND CABLE
#2 Print Name
PAD MOUNT XFMR
OP MAP
N/A
TERMINATION
1■
NEW UNDERGROUND XFMR
O
FAULT INDICATOR
141
NEW PADMOUNT XFMR
—+--
CABLE SPLICE
PJ
UNDERGROUND J-BOX
FOREMAN #2
PRIMARY METERING
OS
UNDERGROUND SWITCH
I IMQ
CABLE TERMINATION BUS (J -BOX)
PULL VAULT - — — —
—
THREE PHASE WIRE/CABLE - 12.5 KV
Q
HANDHOLE
UTILITIES
SINGLE PHASE, ONE WIRE/CABLE - 7.2 KV
_____ TRENCH PATH
ABBREVIATIONS
— w—
w w w— EXISTING WATER
P.E. = POLYETHYLENE
P
—P —P EXISTING POWER
PHONE#
X.F.M.R. = TRANSFORMER
Tom. EXISTING TELEPHONE
N.T.S. = NOT TO SCALE
—G—G—G—G—
EXISTING GAS
INCIDENT
N/A
Order
N/A
SCALE
AS NOTED
SD
- SD - SD EXISTING STORM DRAIN
SS EXISTING SEWER
Trench and backfill requirements for primary electric line extension trenches
- A 12" layer of sand is required when excavated native material contains rocks up to 10" in diameter.
- A 3" layer of sand is allowed when excavated native material contains rocks no larger than 8" in diameter.
Excavated Dirt Pile
ROADSIDE
Final Grade
12" Typical 24 Mi — ►{ /i\//\/i\//\/i\
36" Min Cover (ROW)
24"Min Cover
(Pvt. Property)
48"
Max
TRENCH DETAIL
NOT TO SCALE
Backfill
P��f No rocks over 10" diameter)
j� 12" Min Sand Shading
j\ 3" Sand Bedding
—Primary Power in DB120 Conduit (ROW)
Primary Power in SCH80 Conduit (Pvt. Property)
Cables or Conduit
- iG r - 3�'A_iM 25T I
100T 1 30 CLX X5005
,}• ? X229 30�'
�. S 5 ST p'.' x5002 1
•''3
• I `° I i� I �, oNo aoo j 4oT S 04641 co
I I COCK N I N 04 CD �°' 7176 I zt
a..... I N o x �� 1' X7175
G j� ` x� 1 X X �X 100T
�• X
30: .. :3 �_� o �' o�1�t+25T�
• ••• Q colw NZoIN V I -r7 •'.30 • co a' 7174 ^ I 1 B P X1459
U21S.:. ' ,.� a I X G ccooc .:3b. o� �• � 1 I �� 15T.•...0
�I t I Y@ X r- X X 11007 C
r 'C 100TIOnX2297 •Y�100T ;��„ 40TS 7 STt................
A
0376 X5688 N X626 GRA A; ~off I I O .......A ••
1007 X8394 o� 2I N I
4 100T . 3 16 B : '-X i� � I i......... S
UG 188_ _ _ IW x
3b �'—•}_ _yi PHIL LIP
S •'s T 00385 s X1 0477 25TI I =I ARNOLD
•00098 14 ,� 1 I PARK
�••• c=�:.� = X4835 I �
. 3 fb
EAR -x'34••., GRA } c ccc - 405
15 r h ...... •.: 26 V y GRA
756•-330 30 �. , ; 00514 n; •i ;30 , .0
16
GRA
.30 ll05 7Ms ��:• '� ':..;A
26
J22113 . B ;30 t
' 3s� •s•U2217 s 723 T
1 r, -c N H
/C BC n� IC 1�oIC XLr) .'30: �•• :B S
' XN Lr)! I� �/ a� <S ..11 Z C, : :.,C•� ,35�...:
T '04 Min 257 40T C �'� X11262 �•.• ''s„ ; •� 25A
... 1 1 C 25T 1 N X25 '-
146 S q1 X _ X��S� A'.�8•'••••' 30':•' A
t m1 cn1 1 �� ; 16 S 65 a, ' .•C: B: :A
• c� C 40T Q' s'T :: ....
' .......
3�'•, 67 `11 1t` Qi 117 ST tti.' .•X4657 30 �..
CONO ::eo
C ......:A
L4J+fit , 1 / GRA •B �WN9 ; A. -'N..... :A
' BNa•
WN�1 o C 25 �1 %... •: "
ST t Q S A 19 Z1 _ �V�c
T�-A 2Y_ 00.30 3�'' I..... E B,C .B •:,C •(��
5T ..3 3 (/?¢ I• $ �- ......B (T
...- 16 �oX9 99 PU :.... • Y I c• A QJ
Vic c � ^ e 70106
?J rte¢ • .;•1 X1055 3 o : A
Q I o 't ST •
21S cM y WNO X247 'B ,'c•"A •..30 C • ...;.
:W
67 ZI BAB3� (/
0902 X11 a67 r �I 257 .I 1...3 : • . ....
' •.�
889 :A ... 1 I.••
U869 s
X11a6B x11164 :i i' . :3� .... 30:
657: TALBOT c:'Z :N�
iH/LL 3 A' C:'
V
:A ELEO ; B GRA
•';� �A •: 25 X7520 r' �o
NELSON po
1042 A' S 965 30- 'ys 6TI� X
B� X721 Q
Vic Q: ti. S 30 loor 407
16 A 'ST.'A A- ''N :' SK746 3�.ST 257 W SE 1257
W65 ' S '�.• . X S 27 t
B �uICO2358
.. X1781 063 21, '.� •' ,C m '•.D c. m� X 006 C — -IW Q I
100 . � . "�' _'�� B...• 'Z '•rte` :Q �so� SK 685'
OVERHEAD CIRCUIT MAP: 2305E088
SCALE 611 = 1 MILE
12" MIN
48" MAX
36" MIN (ROW)
24" MIN (Pvt. Property)
Primary Cable(S) -
in Conduit
12"
#2
FOREMAN (CHECK BOX WHEN COMPLETED)
-�
12" MIN
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
MIN
❑
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
❑
EXISTING
Field Changes RED -LINED on As -built.
❑
PAVEMENT / SIDEWIALK
1
Material VERIFIED and CHANGES noted on Paperwork.
❑
❑
ASPHALT PATCH, 2" MIN
❑
❑
Company ID#'s RECORDED in correct location on As -built.
MATCH EXISTING
❑
Indicate correct FUSE SIZE an As -built & VERIFY proper PHASE.
❑
❑
Correct QC Checklist(s) reviewed.
VERTICAL SAW
❑
CUT LINE
❑
CRUSHED SURFACING
I certify that the work performed meets PSE's standards and procedures
MATERIAL COMPACT
_
TO 95% MAX DENSITY.
12" Min Sand Shading
3" Sand Bedding
EXCAVATION AND HARD RESTORATION DETAIL
SCALE: NONE
#1
#2
FOREMAN (CHECK BOX WHEN COMPLETED)
❑
❑
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
❑
❑
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
❑
❑
Field Changes RED -LINED on As -built.
❑
❑
Material VERIFIED and CHANGES noted on Paperwork.
❑
❑
Total PRIMARY Cable noted on As -built.
❑
❑
Company ID#'s RECORDED in correct location on As -built.
❑
❑
Indicate correct FUSE SIZE an As -built & VERIFY proper PHASE.
❑
❑
Correct QC Checklist(s) reviewed.
❑
❑
Deviations noted on the As -built and their reason.
❑
❑
I certify that the work performed meets PSE's standards and procedures
Gas Wk Ctr
N/A
POWER WK CTR
QSEPRE
and that all quality requirements are met.
#1 Foreman's Signature
#1 Print Name
Date
#2 Foreman's Signature
#2 Print Name
Date
PROJECT PHASE
NOTIF# ORDER#
SUPERIOR
FAILED SILICONE
REMOVAL
O&M
MAINTENENCE
EXPENSE
11260578 101101327
Approximate Trench Footage:
108097382
Abandon Cable Segments:
0
Replaced Cable Segments:
CABLE REPLACEMENT
REAL ESTATE/EASEMENT
Trench Method:
TRENCH
Approximate Trench Footage:
4110'
Abandon Cable Segments:
0
Replaced Cable Segments:
24
Approximate New 10/30 1/0 pri. Cable Footage:
4,390'/ 920'
Approximate 2"/4" Poly/DB120 Conduit Footage:
3985'/ 855'
Vaults:
2
"Locates Required" Yes No
VICINITY MAP
O
C)
N
4
Contact Information
PSE: PLANNER
355 - 110TH AVE NE
BELLEVUE, WA 98004
JOHN LERTKANTITHAM
425-462-3941
For contacts below dial 1 -888 -CALL PSE (225-5773)
MAKE NO CHANGES TO THIS JOB WITHOUT PRIOR APPROVAL
Notify Customers and Service Area
48 HRS Prior To Planned Outages
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
Yes
"Flagging Required" No
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
3
FUNCTION
CONTACT
PHONE NO
DATE
2
PROJECT MGR
C. YLENNI
253-720-9700
10/28/16
1
ENGR - POWER
A. BERRY
253-326-1524
10/21/16
REV# DATE
BY
DESCRIPTION
ENGR - GAS
N/A
N/A
N/A
COUNTY
KING
Emer Sect
N/A
Gas Wk Ctr
N/A
POWER WK CTR
QSEPRE
DRAWN BY
S. ANDREWS
253-234-6114
10/21/16
CHECKED BY
d1 ®>
1/4 SEC
SW -20-23-5
OP MAP
N/A
PLAT MAP
N/A
APPROVED BY
j>
FOREMAN #1
U -MAP NO (POWER)
2305EO79
OH CKT MAP
2305EO88
JUGCKTIMAP
2305E079
ICIRCUITNO
GRA -25
FOREMAN #2
IMAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONE#
PUGET
SOUNDGas
ENERGY
DESIGNED BY Potelco, Inc.
GRA -25 S ETHIER RD 2017 CRP
CABLE REMEDIATION PROGRAM
1805 GRANT AVE S., RENTON, WA 98055
INCIDENT
N/A
Order
N/A
SCALE
AS NOTED
P
MOP
Elect Order
101101327
PAGE
1/6
TYP
151
:K-
jL7)
PERMIT
CITY OF RENTON
3
FUNCTION
CONTACT
PHONE NO
DATE
2
PROJECT MGR
C. YLENNI
253-720-9700
10/28/16
1
ENGR - POWER
A. BERRY
253-326-1524
10/21/16
REV# DATE
BY
DESCRIPTION
ENGR - GAS
N/A
N/A
NN
COUNTY
KING
Emer Sect
N/A
Gas Wk Ctr
N/A
POWER WK CTR
QSEPRE
DRAWN BY
S. ANDREWS
\�
10/21/16
CHECKED BY
y>/
Secondary Gable
\
10
APPROVED BY
Secondary Cable
�-- DB 120
PVG
OH CKT MAP
2305EO88
UG CKT MAP
2305EO79
CIRCUIT INO
GRA -25
FOREMAN #2
2" DE 120 PVC -
Primary C.N. Cable
Secondary Cable J
Figure 2 Typical minipad
transformer installation with conduit
(loop construction)
L MINIPAD TRANSPOMER INSTALLATR
Not to scale 6045.1010
V/ CONDUIT
SITE PLAN
SCALE: 1:500
iA
SITE PLAN CONT.
SCALE: 1:50
0
0
w
N
4
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
3
FUNCTION
CONTACT
PHONE NO
DATE
2
PROJECT MGR
C. YLENNI
253-720-9700
10/28/16
1
ENGR - POWER
A. BERRY
253-326-1524
10/21/16
REV# DATE
BY
DESCRIPTION
ENGR - GAS
N/A
N/A
N/A
COUNTY
KING
Emer Sect
N/A
Gas Wk Ctr
N/A
POWER WK CTR
QSEPRE
DRAWN BY
S. ANDREWS
253-234-6114
10/21/16
CHECKED BY
y>/
1/4 SEC
SW -20-23-5
OP MAP
N/A
PLAT MAP
N/A
APPROVED BY
FOREMAN #1
U -MAP NO (POWER)
2305EO79
OH CKT MAP
2305EO88
UG CKT MAP
2305EO79
CIRCUIT INO
GRA -25
FOREMAN #2
MAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONE#
PUGET SOUND
ENERGY
DESIGNED BY Potelco, Inc.
GRA -25 S ETHER RD 2017 CRP
CABLE REMEDIATION PROGRAM
1805 GRANT AVE S., RENTON, WA 98055
INCIDENT
N/A
MAOP
N/A
Gas Order
N/A
Elect Order
101101327
SCALE
AS NOTED
PAGE
2/6
EXISTING UNDERGROUND MAP #: 2305EO79
SCALE: 1:100
1,300 - 1,365 lbs 6"
0
O
D 0
3,600 Ibs_�,, 3'-6"
�J
4'-8" 4,-8.
TOP VIEW
2"
7
00 00Crushed „
10011001 Rock 414
SIDE VIEW I
Excavation - 10-1 /3 cubic yards
VAULT & EXCAVATION DETAIL
Not to scale 6055.1010
TOP VIEW
Cables should enter the vault so that all of
the cables will lay in the same direction.
J- BOX CABLE ENTRY DETAIL @ J02A, J03A
NOT TO SCALE
ABANDONED / REMOVE / REPLACED CABLE SCHEDULE
CABLE
NO.
SAP
EQUIP
LOCATIONS
FROM TO
CABLE
(LF) EST
EXISTING CABLE EXISTING CABLE CABLE
MFG. NAME MFG. DATE REPLACED?
4590 i
UNK
P01
Vol
230
YES
4591 I
UNK
Vol
V02
265
YES
4592 (
UNK
V02
V03
181
YES
4593
UNK
V03
VO4
78
YES
4594 €
UNK
VO4
V05
164
YES
4595
UNK
V05
V06
153
YES
3551
10591213
V06
V07
483
YES
10442
UNK
V07
V08
165
YES
3550
UNK
V08
V09
91
YES
3549
UNK
V09
V10
91
YES
3548
UNK
V10
V11
133
YES
3547
UNK
V11
V12
134
YES
3546
UNK
V12
V13
101
YES
3545
UNK
V13
V14
142
YES
3544
UNK
V14
V15 "..
86
YES
ABD078
UNK
V15
JO{
349
YES
3975
UNK
J02
V16 1470
YES
3983
UNK
J01
J02 (
416
YES
16080
UNK
J01
V1:6
44
YES
16079
UNK
J01
V' 6
112
YES
3430
UNK
J01
P01
377
YES
3431
UNK
J01
P31
377
YES
3432
10589449
J01
P01
377
YES
TOTAL
VAULT & EQUIPMENT TABLE
3,420'
CONSTRUCTION NOTES
P01:
-CUT OFF & CAP OLD CABLES AT TOP OF RISER
-ATTACH OLD CABLE # TO CABLE STUB
-REMOVE OLD C/O & TERM
-INST 10 LB C/O TERM F:40T STD 6043.1000 (TSU1C1)
-INST 1-2" RISER ON STAND-OFF BRKTS STD 6042.1000 (RIS2CSS)
-INST SW#X4657
P02:
-CUT OFF & CAP OLD CABLES AT TOP OF RISER
-ATTACH OLD CABLE # TO CABLE STUB
-REMOVE OLD C/O & TERM
-INST 30 LI C/O TERM F: 100T STD 6043.1000 (TSU31_IF)
-INST 1-4" RISER ON STAND-OFF BRKTS STD 6042.1000 (RIS2CSS)
-INST SW# T78428
P03:
-REPLACE FUSE WITH 100T FUSE
Standoff Bracket
15" Min Length
Conduit Clamp 5" Min
Climbing
Space
uit Field Face Road Face
Quadrant Quadrant
Climbing
Space
Direction of Vehicular Traffic
TOP VIEW
CONDUIT RISER REPLACEMENT DETAIL @ P01 & P02
NOT TO SCALE
Crew to provide all property owner's that are impacted by
project prior notice and make an effort to work with
property owner's to maintain their access to their property,
as well as, reduce the impact of our work on their use of
their property."
FOREMAN NOTE:
Call (800) 424-5555 Utility Notification Center 24/7 before beginning any
excavation prevents damage to underground facilities, service interruptions &
bodily injury.
CIVIL CREW FOREMAN NOTE:
Maintain on site, in good condition, a complete file of all work drawings. These
drawings shall be available at all times to a Puget Sound Energy representative.
Corrections and changes made during the job shall be recorded continuously on these
drawings. Mark all underground utilities encountered during construction on these
drawings. Furnish Puget Sound Energy a complete set of as -built prints (foreman's
copies) at the end of the job.
WIRE CREW FOREMAN NOTE:
ALL FAULT INDICATORS WILL BE MAINTAINED IN THEIR CURRENT LOCATION ON
1/0 CABLES AFTER NEIN CABLE IS INSTALLED UNLESS OTHERWISE SPECIFIED.
PLEASE RED -MARK ALL. FAULT INDICATORS ON "CABLE DIAGRAM" FOR MAPPING.
O
O
N
4
PRIMARY
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
SITE GRID
VAULT SIZE & TYPE & S= I BUSHINGS
TRANSFORMER
ID NUMBERS
REMARKS
NUMBER
COVER } EQUIPMENT IN VAULT
(COMPANY ID)
2
LB DC
PROJECT MGR
C. YLENNI
253-720-9700
317295
EXISTING J -BOX BELS 'GRADE
REPLACE ELBOWS & CONDUCTORS
J01
166127
JUNCTION Box W/ 3-1, EO J -B IS 8
EXISTING ING
REV# DATE
BY
WIRE CREW TO INSTALL GRID NUMBERS
ENGR - GAS
J -BOX EEtGRADE I
N/A
N/A
COUNTY
KING
J02
317312
EXISTING W/ 3-4 Eos 2
DRAWN BY
S. ANDREWS
REPLACE ELBOWS & CONDUCTORS
166141
CHECKED BY
JUNCTION Box
EX4STING
t:;
-
OP MAP
N/A
WIRE CREW TO INSTALL GRID NUMBERS
NEW
317240
HH 4'8"x4'8"X3'6" J -BOX BELOW GRADE I'
FOREMAN #1
INSTALL NEW 504 J -BOX
J02A
w/ 3' DOOR wt 1-4 POs. J -BUS I 4
MAT ID:: 7663900 MATID: 7625900
-
CIRCUITNO
GRA -25
WIRE CREW TO INSTALL GRID NUMBERS
166230
NEW
317282
HH 4'8"X4'8"X3'6" J -BOX BELOW GRADE
INSTALL NEW 504 J -BOX
J03A
W/ T sQ DOOR WI 2-4 POS. J -BUS 7
MAT ID: 7663900 MATID: 7625900
1
WIRE CREW TO INSTALL GRID NUMBERS
166152
CONTACT
REMOVE EXISTING VAULT LID AND
317201
1 OOkVA TUT XFMR
PHONE#
TUT XFMR & REPLACE WITH NEW VAULT
Vol
EXISTING
VAULT 120/240v 2
-
PUGET
SOUND
ENERGY
DESIGNED BY Potelco, Inc.
LID AND MINIPAD XFMER WITH NEW
166227
INCIDENT MAOP
N/A N/A
Gas Order Elect Order
N/A 101101327
SCALE PAGE
AS NOTED 3/6
ExlsrwG
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
317186 I
u7.5kVA TUT XFMR
TUT XFMR & REPLACE WITH NEW VAULT
V02166232
EXISTING 120/240V 1
-
LID AND MINIPAD XFMER WITH NEW
VAULT
EXISTING
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
317195
v 5^-A'A TUT XFMR
TUT XFMR & REPLACE WITH NEW VAULT
V03
EXISTING
E/2aov 2
-
LID AND MINIPAD XFMER WITH NEW
166222
VAULT
EXISTING
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
317202 L'�,VATUTXFMR
TUT XFMR & REPLACE WITH NEW VAULT
VO4
EXISTING
120/240v 2
-
LID AND MINIPAD XFMER WITH NEW
166221 VAULT EXISTING
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
317210 37.5kVA T ?XFMR
TUT XFMR & REPLACE WITH NEW VAULT
V05
EXISTING 12 G4 ' 2
-
LID AND MINIPAD XFMER WITH NEW
166229 VAULT
EXISTING }
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
31 50kVA TUT '1F!,,R
317221
TUT XFMR & REPLACE WITH NEW VAULT
V06
EXISTING
EXISTING
2
-
LID AND MINIPAD XFMER WITH NEW
221
EX€STI vG VAULT
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
317230 A T` T XFMR
TUT XFMR & REPLACE WITH NEW VAULT
V07
EXISTING 24_, 2411v 1
-
LID AND MINIPAD XFMER WITH NEW
166191 VAULT
EXISTING i
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
-I OOkVA T4 T X7MR
317238
TUT XFMR & REPLACE WITH NEW VAULT
V08
EXISTING
EXISTING
2�` E ,, 2
-
LID AND MINIPAD XFMER WITH NEW
166188 i' T
EXISTING
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
317245 EXISTING 50k"A TUT XFMR
REPLACE ELBOWS & CONDUCTORS
V09
166190 VAULT 120:2 2
EXISTING
-
WIRE CREW TO INSTALL GRID NUMBERS
317247 EXISTING 75kVA TUT XFMR
REPLACE ELBOWS & CONDUCTORS
V10
166181 - VAULT 2 `` 1
ING
EXISTING
-
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
1 OOkVA TUT XFMR
317254
TUT XFMR & REPLACE WITH NEW VAULT
V11
EXISTING 1201240V 1
-
LID AND MINIPAD XFMER WITH NEW
166174 FAULT
EXISTING
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
75kVA PM XFMR
317251 EXISTING
REPLACE ELBOWS & CONDUCTORS
V12166166
VAULT 120/240v 1
EXISTING
-
WIRE CREW TO INSTALL GRID NUMBERS
317264i EXISTING 75kVA PM XFMR
REPLACE ELBOWS & CONDUCTORS
V13166159VAULT
120/240v 2
EXISTING
-
WIRE CREW TO INSTALL GRID NUMBERS
75kVA PM XFMR
317273 EXISTING
REPLACE ELBOWS & CONDUCTORS
V14
1
_
166154 VAULT EXISTING
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
317278 75kVA TUT XFMR
TUT XFMR & REPLACE WITH NEW VAULT
V15
EXISTING 120/240v 2
-
LID AND MINIPAD XFMER WITH NEW
166154 VAULT EXISTING
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
REMOVE EXISTING VAULT LID AND
25kVA TUT XFMR
317292
TUT XFMR & REPLACE WITH NEW VAULT
V16
EXISTING
12o/2aov 1
-
LID AND MINIPAD XFMER WITH NEW
166119 VAULT EXISTING
i
ELBOWS & CONDUCTORS
WIRE CREW TO INSTALL GRID NUMBERS
TOTALS:1 46
1
CONSTRUCTION NOTES
P01:
-CUT OFF & CAP OLD CABLES AT TOP OF RISER
-ATTACH OLD CABLE # TO CABLE STUB
-REMOVE OLD C/O & TERM
-INST 10 LB C/O TERM F:40T STD 6043.1000 (TSU1C1)
-INST 1-2" RISER ON STAND-OFF BRKTS STD 6042.1000 (RIS2CSS)
-INST SW#X4657
P02:
-CUT OFF & CAP OLD CABLES AT TOP OF RISER
-ATTACH OLD CABLE # TO CABLE STUB
-REMOVE OLD C/O & TERM
-INST 30 LI C/O TERM F: 100T STD 6043.1000 (TSU31_IF)
-INST 1-4" RISER ON STAND-OFF BRKTS STD 6042.1000 (RIS2CSS)
-INST SW# T78428
P03:
-REPLACE FUSE WITH 100T FUSE
Standoff Bracket
15" Min Length
Conduit Clamp 5" Min
Climbing
Space
uit Field Face Road Face
Quadrant Quadrant
Climbing
Space
Direction of Vehicular Traffic
TOP VIEW
CONDUIT RISER REPLACEMENT DETAIL @ P01 & P02
NOT TO SCALE
Crew to provide all property owner's that are impacted by
project prior notice and make an effort to work with
property owner's to maintain their access to their property,
as well as, reduce the impact of our work on their use of
their property."
FOREMAN NOTE:
Call (800) 424-5555 Utility Notification Center 24/7 before beginning any
excavation prevents damage to underground facilities, service interruptions &
bodily injury.
CIVIL CREW FOREMAN NOTE:
Maintain on site, in good condition, a complete file of all work drawings. These
drawings shall be available at all times to a Puget Sound Energy representative.
Corrections and changes made during the job shall be recorded continuously on these
drawings. Mark all underground utilities encountered during construction on these
drawings. Furnish Puget Sound Energy a complete set of as -built prints (foreman's
copies) at the end of the job.
WIRE CREW FOREMAN NOTE:
ALL FAULT INDICATORS WILL BE MAINTAINED IN THEIR CURRENT LOCATION ON
1/0 CABLES AFTER NEIN CABLE IS INSTALLED UNLESS OTHERWISE SPECIFIED.
PLEASE RED -MARK ALL. FAULT INDICATORS ON "CABLE DIAGRAM" FOR MAPPING.
O
O
N
4
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
3
FUNCTION
CONTACT
PHONE NO
DATE
2
PROJECT MGR
C. YLENNI
253-720-9700
10/28/16
1
ENGR - POWER
A. BERRY
253-326-1524
10/21/16
REV# DATE
BY
DESCRIPTION
ENGR - GAS
N/A
N/A
N/A
COUNTY
KING
Emer Sect
N/A
Gas, Wk Ctr
N/A
POWER WK CTR
QSEPRE
DRAWN BY
S. ANDREWS
253-234-6114
10/21/16
CHECKED BY
1/4 SEC
SW -20-23-5
OP MAP
N/A
PLAT MAP
N/A
APPROVED BY
FOREMAN #1
U -MAP NO (POWER)
2305EO79
OH CKT MAP
2305EO882305EO79
FUGCKTMAP
CIRCUITNO
GRA -25
FOREMAN#2
MAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONE#
PUGET
SOUND
ENERGY
DESIGNED BY Potelco, Inc.
GRA -25 S ETHIER RD 2017 CRP
CABLE REMEDIATION PROGRAM
1805 GRANT AVE S., RENTON, WA 98055
INCIDENT MAOP
N/A N/A
Gas Order Elect Order
N/A 101101327
SCALE PAGE
AS NOTED 3/6
PRIMA
NOT TO
AEX095 - CO (EXISTING)
23161 - CO (EXISTING)
LOCATION
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
CONDUIT
FUNCTION
CONTACT
PHONE NO
DATE
PRIMARY CABLE REMARKS
FROM
TO
SIZE
(in)
QTY
DESIGN ACTUAL
LENGTH LENGTH
(ft) (ft)
TYPE
DB120 POLY SCH 80
90
BENDS
45 22 11
PULL
(Ibs)
PULL
REV
(lbs)
CABLE
SIZE
DESIGN ACTUAL
LENGTH LENGTH
(ft) (ft)
CABLE NUMBERS PLEASE RECORD FOREMAN - COMPLETE
A B C MANUFACTURER COMPOUND YEAR
P02
J01
4
1
560
- - X
2
- 1
- 985.3
996.6
1/0 AL JKT
605
EHN900 EHN901 EHN902
J01
J02
4 1
1
295
- - X
2
- -
- 1465.6
469.0
1/0 AL JKT
315
- EHN903 EHN904
J01
V16
2
1
20
- - X
-
- -
- 32.8
32.8
1/0 AL JKT
40
- EHN905 -
J01
J03A
2
1
385
- - X
3
- -
- 178.5
187.4
1/0 AL JKT
405
EHN906 - -
J03A
J03A
-
-
- I
- - X
-
- -
- -
-
1/0 AL JKT
20
EHN907 - -
J03A
V15
2
1
85
- - X
2
- I -
- 76.9 1
82.0
1/0 AL JKT
105
EHN908 - -
V15
V14
2
1
60
- - X
-
- -
- 38.3
38.3
1/0 AL JKT
80
EHN909 - -
J03A
V13
2
1
285
- - X
3
- -
- 158.0
160.4
1/0 AL JKT
305
EHN910 - -
V13
V12
2
1
45
- - X
-
- -
36.2
36.2
1/0 AL JKT
65
EHN911 - -
J03A
V11
2
1
525
- - X
3
1 -
- 260.1
237.8
1/0 AL JKT
545
EHN912 - -
J03A
J02A
2
1
770
- - X
2
- -
- 214.1
217.1
1/0 AL JKT
790
EHN913 - -
J02A
V09
2
1
405
- - X
3
- 2
- 213.6
224.3
1/0 AL JKT
425
EHN914 - -
V09
V10
2
1
80
- - X
2
- -
- 78.1
78.1
1/0 AL JKT
100
EHN915 - -
V10
V08
2
1
45
- - X
2
- -
- 36.2
36.2
1/0 AL JKT
65
EHN916 - -
V08
V07
2
1
200
- X -
-
1 -
- 65.1
67.9
1/0 AL JKT
220
EHN940
J02A
P01
2
1
335
- - X
1
1 -
- 107.5
119.2
1/0 AL JKT
380
EHN917 - -
J02A
V06
2
1
285
- - X
2
- -
- 123.4
146.6
1/0 AL JKT
305
EHN918 - -
V06
V05
2
1
150
- - X
1
2 -
- 94.2
90.2
1/0 AL JKT
170
EHN919 - -
V05
V01
2 1
1
125
- - X
1
2 -
- 85.3
89.3
1/0 AL JKT
145
EHN920 - -
V01
VO4
2
1
85
- - X
2
- -
- 80.0
78.5
1/0 AL JKT
105
EHN921 - -
VO4
V03
2
1
105
- - X
1
2 -
- 84.0
82.5
1 1/0 AL JKT
125
EHN922 - -
V03
V02
2
1
195
- - X
2
- -
- 101.11
101.1
1 1/0 AL JKT
215
EHN923 - -
TOTAL 4"
855'
- - -
4
- 1
-
TOTAL 30
920'
TOTAL 2"
4,185'
- - -
30
9 2
-
TOTAL 1O
4,610'
QTS OF GLUE 1 8.8 I GALS OF LUBE I 18.9
CIVIL CREW NOTE: ALL 2" - 90° BENDS MIN 48" RADIUS SCH-80 PVC
ALL 2" - 450 BENDS SCH-80 PVC
ALL 4" - 900 BENDS MIN 60" RADIUS SCH-80 PVC
ALL 4" - 450 BENDS SCH-80 PVC
- ALL CONDUITS SHALL BE CAPPED AT EACH END UNTIL
CABLE IS INTALLED
X
D
Z
D
m
O
O
w
no
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
3
FUNCTION
CONTACT
PHONE NO
DATE
2
PROJECT MGR
C. YLENNI
253-720-9700
10/28/16
1
ENGR-POWER
A. BERRY
253-326-1524
10/21/16
REV# DATE
BY DESCRIPTION
ENGR - GAS
N/A
N/A
N/A
COUNTY
KING
Emer Sect Gas Wk Ctr
N/A N/A
POWER WK CTR
QSEPRE
DRAWN BY
S. ANDREWS
253-234-6114
10/21/16
CHECKED BYp
/
1/4 SEC
SW -20-23-5
OP MAP
N/A
PLAT MAP
N/A
APPROVED BY
FOREMAN #1
U -MAP NO (POWER)
2305EO79
OH CKT MAP
2305EO88
JUGGKTMAP
2305EO79
ICIRCUITNO
GRA -25
FOREMAN #2
MAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONE#
PUGET
SOUND
ENERGY
DESIGNED BY Potelco, Inc.
GRA -25 S ETHIER RD 2017 CRP
CABLE REMEDIATION PROGRAM
1805 GRANT AVE S., RENTON, WA 98055
INCIDENT ENT MN OP
Gas Order Elect Order
N/A 101101327
SCALE PAGE
AS NOTED 416
� . = ' `�
\
,'' / � y+ • '� � .
1 1 030625 �-..._---
1 �317305-16616
.� 'i. ' /
`;75kVA 120/2 v
7
1620
UNIT
{10 6948}
Oe
1201
317302-16 6
~f
/
75 kVA 120/240v
Jl %
N
1104
®
UNC �� •�
,-
; _
/
�J `, 3 7305®156 5
'
1203 ,
7 kVA 1201
\
®�
,
a .
/ —5kV
'117297-
.------------------------------- ---- 8
Q1,
17296 1661
l
7kVA 120/ 40v 1204 5
v
3172
Qa
L
� � s Ps
�
1200 50 kV
0 72 - T�
165 1
\ \ s�.
17237-166169
SS
/ d
Q��
\ Ps
•
75 120/2 v
zi N
S
�`
9758 X14
r
I DO3 �' �
� 317279-166166�
A SS
P02
s,
P#2023059014
1101
/..
W
3:;
133
:......... ..........
V 14
1203 /
QS
z
\ Q \�
r
/ d
•� / PS
0—
'N%
W
_
a
1726 16617Co
1205
1201 Ps
Z_
N
V 1 3
1303
_
317265-166092SL
Q
1
®
O
LJ
Wool
CIVIL PLAN
REAL ESTATE/EASEMENT PERMIT
SCALE: 1:30
CITY OF RENTON
3 FUNCTION CONTACT PHONE NO
DATE
2 PROJECT MGR C. YLENNI 253-720-9700
10/28/16
1 ENGR - POWER A. BERRY 253-326-1524
10/21/16
REV# DATE BY DESCRIPTION ENGR - GAS N/A N/A
N/A
COUNTY Emer Sect Gas Wk Ctr POWER WK CTR DRAWN BY S. ANDREWS 253-234-6114
10/21/16
KING N/A N/A QSEPRE CHECKED BY
1/4 SEC OP MAP PLAT MAP APPROVED BY C/llfjrZS �%
SW-20-23-5 N/A N/A FOREMAN #1
U-MAP NO (POWER) OH CKT MAP UG CKT MAPCIRCUIT NO FOREMAN #2
2305EO79 2305EO88 2305EO79 GRA-25 MAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONES#
PUGET INCIDENT MAOP
GRA-25 S ETHER RD 2017 CRP N/A N/A
SOUND CABLE REMEDIATION PROGRAM Gas Order Elect Order
101101327
ENERGY
1805 GRANT AVE S., RENTON, WA 98055 SCALELE
PAGE
DESIGNED BY Potelco, Inc. AS NOTED
5/6
u
u
C
0
u
Li
0
L
C
F
e.
pi
SCALE: 1:30
CIVIL PLAN (CONTINUED)
SCALE: 1:30
0
0
w
N
4
REAL ESTATE/EASEMENT
PERMIT
CITY OF RENTON
3
FUNCTION
CONTACT
PHONE NO
DATE
2
PROJECT MGR
C. YLENNI
253-720-9700
10/28/16
1
ENGR - POWER
A. BERRY
253-326-1524
10/21/16
REV# DATE
BY DESCRIPTION
ENGR - GAS
N/A
N/A
N/A
COUNTY
KING
Emer Sect Gas Wk Ctr
N/A N/A
POWER WK CTR
QSEPRE
DRAWN BY
S. ANDREWS
253-234-6114
10/21/16
CHECKED BY
1/4 SEC
SW -20-23-5
OP MAP
N/A
PLAT MAP
N/A
APPROVED BY
FOREMAN #1
U -MAP NO (POWER)
2305EO79
OH CKT MAP
2305EO88
JUG CKT MAP
2305EO79
CIRCUIT NO
I GRA -25
FOREMAN #2
MAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONE#
UGET
SGas
�-�/
ENERGY
DESIGNED BY Potelco, Inc.
GRA -25 S ETHER RD 2017 CRP
CABLE REMEDIATION PROGRAM
1805 GRANT AVE S., RENTON, WA 98055
INCIDENT
N/A
Order
N/A
SCALE
AS NOTED
MAOP
N/A
Elect Order
101101327
PAGE
6/6