HomeMy WebLinkAboutP_Design_105085007_V1316986-165284
NEW
25kVA 120/240v
316988-165283
SW 27TH
S
T
NACHES AVE SWRJN
27
RJN
27
JOB SITE
JOB SITE
15'
90°
4' X 4'
WORK PIT
PSE TO INSTALL
±15' OF 1-2" SCH'L 80
DISCONTINUOUS
GRAY PVC CONDUIT
BØEHE133
PSE TO INSTALL
±30' OF (1) 1/0 AL JKT
PRIMARY CABLE
504518232 105085007
594114373
504605496 104291511
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Misc UG
Perm Service
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)105085007Owner / Developer Contact Info
officeATTN:
CITY OF RENTON
1055 S GRADY WAY
RENTON, WA 98057
ERIC CUTSHALL 425-430-7423
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
SITE PLAN
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
CONDUIT DIAGRAM
11.
7.
6.
5.
4.
3.
2.
1.All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits
and crossings from the individual unit's meter base to the designated connection point.
Inclement weather conditions may cause delays in construction times and dates.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
8.
POWER GENERAL NOTES - COMMERCIAL PROJECT
9.
10.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:BRAD ELKIN
425-495-6489
BRADLEY.ELKIN@PSE.COM
N
Vicinity Map
N/A
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
SCALE: 1" = 50'
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
V01
316986-165284
25kVA
6247000
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
BRAD ELKIN 425-495-6489 05/15/17
BRAD ELKIN 425-495-6489 05/15/17
N/A N/A N/A
JUSTIN HANG 253-508-7880 05/15/17
EASEMENT REQUIRED CITY OF RENTON
GROUP HEALTH LONGACRES SIGNAL
INSTALLING 1Ø PRIMARY L/E & CONNECTING UG PERM SVC
SW 27TH ST & NACHES AVE SW, RENTON, WA 98058
N/A N/A
N/A 105085007
AS NOTED 1/1
KING N/A N/A CSPSKEIN
T23N, R04E, SEC 25 NW N/A N/A
2304E097 2305E124 2304E097 RJN-27
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SITE SPECIFIC NOTES
J01 GRID 316988-165283:
-INSTALL 1 - 12kV ELBOW KIT
V01:
-INSTALL 36" X 42" X 38" MP W/ UNITSTRUTS & GNDS
-INSTALL 25kVA 120-240v PADMOUNT TRANSFORMER
-INSTALL 1 - 12kV ELBOW KIT
-INSTALL 1 - 12kV DUST CAP
-INSTALL CABLE TAG: %(+(
-INSTALL GRID NUMBER: 316986 - 165284
-TAG & CONNECT CUSTOMER OWNED SVC
M01:
-INSTALL 1 - 200AMP METER
SPAN SPECIFIC NOTES
*** SEE PRIMARY CABLE & CONDUIT TABLE ***
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
0 SQ.
200AMPS
ELECTRIC
10KW
65A
0.8%
1.5%
CIRCUIT FEET ADDED: 15'
CABLE DIAGRAM
NOT TO SCALE
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT PRIMARY CABLE
ASBUILT INFORMATION
SIZE Qty LENGTH
Design
(ft)
BENDS PULL PULL Cable LENGTH
Design
(ft)
Cable Numbers Please Record Foreman - Complete
FROM TO (in)90°45°22°11°(lbs)
Rev
(lbs)Size A B C Manufacturer Compound Year Actual Amount Installed (Conduit & Cable)
J01 V01 2 1 15 1 146.2 145.9 1/0 AL JKT 30 EHE133
NOT TO SCALE
TOP VIEW
SIDE
VIEW
EXCAVATION:
4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
FRONT
FRONTVAULT DETAIL AT V01
SCALE: NONE