HomeMy WebLinkAboutMFP17003306DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Franchise Permit: MFP17003306
IVR Number: 17003306
Permit InformaƟon
Permit Name:Puget Sound Energy ‐ Electric
Address/LocaƟon:07/13/2017ApplicaƟon Date:0087000293Parcel Number:17033 108TH AVE SE
Permit Type:08/10/2017Issue Date:Franchise
Permit Work Class:08/10/2018ExpiraƟon Date:Minor UƟlity
Job Number:105085310Franchise Type:Electric
DescripƟon:ACCESS VAULT V01 AND INSTALL 2 NEW RUNS OF #350CMIL TRIPLEX TO NEW 30"X30" CONCRETE HANDHOLE AT HH 1
JOINT TRENCH TO INSTALL CONDUIT FROM HH1 TO M01. One asphalt cut anƟcipated. RestoraƟon per City of Renton
Standards.
Contacts
Name Address PhoneTypeBilling
ANISH KUMAR
PUGET SOUND ENERGY ‐ ELECTRIC ‐ BILLING
6905 S 228th St
Kent, WA 98032
B: (253) 208‐2183ApplicantX
VICKI HENSON
POTELCO INC
8001 212th St S
Kent, WA 98032
B: (253) 863‐0484Contractor
Business License Number: BL.005109Electrical Contractor: POTELI*344O4
ConstrucƟon Contractor: POTELI*227PL
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057‐3232
Owner
General CondiƟons & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
This permit and plans must be posted at the job site at all times.
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Call (425) 430-7203 or go to: www.MyBuildingPermit.com one working day in advance to schedule an inspections and for
ANY work in the Right of Way.
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010
) (Olympic Pipeline at 206.510.0575)(Puget Sound Energy at 425.457.5816) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
(Date)(Signature)
Page 1 of 2THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
MFP17003306
Holly Powers
Restoration per City of Renton Standards
Justin Johnson
8-10-2017
8-10-2017
MFP17003306
Justin Johnson
8-10-2017
8:00 AM to 3:00 PM
Monday through Friday
100T
SK00601
316678-166296
25kVA 120/240v
(105074339)108TH AVE SEROL
15
316801-166297
75kVA 120/240v
"10930"
"17033"
70'
ROW
JOB SITE
JOB SITE
7' X 7' WORK PIT
PSE TO INSTALL
±10' OF (2)
#350kCMIL UG TPX
RE-ROUTE (2)
RUNS CUST
OWNED TPX
504676281 105085310
504699285 104292543
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Perm. Service
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)105085310Owner / Developer Contact Info
officeATTN:
RENTON SPECIAL CARE COMMUNITY LLC
2731 77TH AVE SE
MERCER ISLAND, WA 98040
KEVIN CARL 206-778-4726
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
SITE PLAN
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
CIRCUIT ONE-LINE DIAGRAM
SCALE: NONE
11.
7.
6.
5.
4.
3.
2.
1.All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits
and crossings from the individual unit's meter base to the designated connection point.
Inclement weather conditions may cause delays in construction times and dates.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
8.
POWER GENERAL NOTES - COMMERCIAL PROJECT
9.
10.
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:BRAD ELKIN
425-495-6489
BRADLEY.ELKIN@PSE.COM
N
Vicinity Map
N/A
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
SCALE: 1" = 50'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
BRAD ELKIN 425-495-6489 06/19/17
BRAD ELKIN 425-495-6489 06/19/17
N/A N/A N/A
JUSTIN HANG 253-508-7880 06/19/17
RIGHTS REVIEW CITY OF RENTON
RENTON SPECIAL CARE COMMUNITY
INSTALL 1Ø SEC HANDHOLE & CONNECT CUST OWNED SVC
17033 108TH AVE SE, RENTON, WA 98055
N/A N/A
N/A 105085310
AS NOTED 1/1
KING N/A N/A CSPSKEIN
T23N, R05E, SEC 29 NW N/A N/A
2305E116 2305E136 2305E116 ROL-15
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
SITE SPECIFIC NOTES
V01 GRID NUMBER 316801-166297:
-EXISTING 75kVA MP TRF TO REMAIN
-RE-ROUTE (2) RUNS CUST SVC TO NEW SEC HH
-INSTALL, LABEL, & CONNECT (2) NEW RUNS #350kCMIL
TPX TO HH
IP1:
-RE-ROUTE 2 CUSTOMER SECONDARY SERVICES TO
NEW HANDHOLE (HH1)
HH1:
-INSTALL 30" X 30" CONCRETE HANDHOLE MID: 9995597
-INSTALL 3 - 6 POS FARGO BARS
-TAG AND CONNECT NEW CUST OWNED TPX RUN
M01:
-INSTALL 1 - 200AMP METER
SPAN SPECIFIC NOTES
V01 - HH1:
,167$//
2)N&0,/8*73;
594114857Misc UG
DEVELOPER CIVIL NOTES:
-REQUIRED TO PROVIDE A 5' X 5' WORK PIT AT NEW VAULT
VAULT HH1.
CUSTOMER SI RESPONSIBLE FOR ALL TRENCHING,
SELECT BACKFILL, COMPACTION & RESTORATION PER
PUGET SOUND STANDARDS #6750.6500.
DEVELOPER EXCAVATION NOTES:
-REQUIRED TO EXCAVATE & EXPOSE EXISTING PSE UG
FACILITIES 72 HOURS BEFORE CONSTRUCTION.
-REQUIRED TO PROVIDE WORK PITS 72 HOURS BEFORE
CONSTRUCTION.
-ALL EQUIPMENT MUST BE PROTECTED FROM VANDALS
WITH STEEL PLATE 72 HOURS BEFORE CONSTRUCTION.
-EXCAVATION AND CITY OF RENTON INSPECTION MUST BE
COMPLETED 72 HOURS BEFORE CONSTRUCTION.
CONTRACTOR TRENCHING IN CITY OR
COUNTY RIGHT OF WAY NOTES:
PLEASE REVIEW THE CITY OF RENTON TRENCHING
REQUIREMENTS UNDER THE PERMIT.
IF A PRE-CON IS REQUIRED BY THE CITY OR COUNTY, A
PSE PROJECT MANAGER WILL SE A SCHEDULE MEETING
WITH THE MUNICIPALITY BEFORE ANY EXCAVATION OR
INSTALLATION BEGINS.
ALL INSPECTIONS ARE REQUIRED BY PSE
IF A SECOND INSPECTION IS REQUIRED ADDITIONAL FEE'S
WILL BE APPLIED
ELECTRICIAN RESPONSIBILITY
-ELECTRICIAN WILL CALL THE DAY THE ELECTRICAL PANEL
HAS BEEN INSPECTED BY CITY OF RENTON.
-ELECTICIAN WILL CALL THE PSE PROJECT MANAGER
BRAD ELKIN, PHONE# 425-495-6489
SINGLE PHASE SECONDARY CONCRETE HANDHOLE
Not to scale 6050.2020-1
EXCAVATION: 5-1/3 CUBIC YARDS
2'-6"2'-6"
Handhole
820 lbs
SIDE VIEW
2'-4"6" Crashed rock
2"
TOP VIEW
5'-0"
5'-0"
Customer-installed grounding wires ( the "4th" wire on the
single-phase systems and the "5th" wire on the three-phase
systems) shall not be connected to PSE's ground or neutral
bus. They shall be removed by customer or cut off at the
vault wall.
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
329310.49305
-.49-
329310305
2017
ROL-15
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
N/A.
100AMPS
ELECTRIC
4.3kW
65A
0.1%
0.5%
CIRCUIT FEET ADDED: 0'
121214
14 1414SE 172ND ST 108TH AVE SE11 15
V01
HH1
5
STOP
FLAGGER
STOP
FLAGGER
BEPREPAREDTOSTOPW3-4ROADWORKAHEADW20-1100'100'BEPREPAREDTOSTOPW3-4ROADWORKAHEADW20-1 W20-7A100'X'100'
ONE L
A
N
E
ROAD
AHEA
D W20-4ROAD
WOR
K
AHEA
D W20-1100'100'ONE LANEROADAHEADW20-4ROADWORKAHEADW20-1W20-7A100'100'100'R9-11SIDEWALK
CLOSED
AHEAD R9-9SIDEWALK
CLOSED R9-9SIDEWALKCLOSEDR9-11SIDEWALKCLOSEDAHEADFLAGGERS WILL ASSIST
PEDESTRIANS WITH
SIDEWALK CLOSURE
USE MAXIMUM AVAILABLE
SPACE FOR SIGNS
FROM TO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
PLACE NO-PARK SIGNAGE
ON BOTH SIDES OF 108TH
AVE SE SURROUNDING
WORK ZONE
#17033
108TH AVE SEJob#105085310(RE)
17033 108th Ave SE, Renton WA
July 25, 2017
Sheet 1 of 2 ryan.honeysett@pse.com
(425)457-5381
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
N
PSE PUGET
SOUND
ENERGY
Notes:
1. All signs and spacing to conform to the MUTCD
and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
4. Sign size can be a minimum of 48" x 48" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m.
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
WORK VEHICLE
SIGN LOCATION
WARNING FLAG
FLAGGER
STOP
VAULTVault
Puget Sound Energy
Traffic Control Supervisor:
Ryan Honeysett
Card No. 010760
Card Exp. 06/30/2021
ryan.honeysett@pse.com
(425)478-5381
Ryan H. Honeysett
121214
14 1414SE 172ND ST 108TH AVE SE11 15
V01
HH1
5
STOP
FLAGGER
STOP
FLAGGER
ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1 W20-7A100'100'
ONE LANE
ROAD
AHEAD W20-4ROAD
WOR
K
AHEA
D W20-1100'ONE LANEROADAHEADW20-4ROADWORKAHEADW20-1W20-7A100'100'100'FROM TO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
PLACE NO-PARK SIGNAGE
ON BOTH SIDES OF 108TH
AVE SE SURROUNDING
WORK ZONE
#17033
108TH AVE SE100'Job#105085310(RE)
17033 108th Ave SE, Renton WA
July 25, 2017
Sheet 2 of 2 ryan.honeysett@pse.com
(425)457-5381
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
N
PSE PUGET
SOUND
ENERGY
Notes:
1. All signs and spacing to conform to the MUTCD
and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
4. Sign size can be a minimum of 48" x 48" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m.
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
WORK VEHICLE
SIGN LOCATION
WARNING FLAG
FLAGGER
STOP
VAULTVault
Puget Sound Energy
Traffic Control Supervisor:
Ryan Honeysett
Card No. 010760
Card Exp. 06/30/2021
ryan.honeysett@pse.com
(425)478-5381
Ryan H. Honeysett