HomeMy WebLinkAboutMFP17004487DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Franchise Permit: MFP17004487
IVR Number: 17004487
Permit Informa!on
Permit Name:Puget Sound Energy - Electric
Address/Loca!on:09/06/2017Applica!on Date:0923059116Parcel Number:850 MONROE AVE NE
Permit Type :11/07/2017Issue Date:Franchise
Permit Work Class:11/07/2018Expira!on Date :Minor U(lity
Job Number:101106285Franchise Type :Electric
Descrip!on:Removing old wire, installing new poles with UG riser and termina(on , and trenching from poles to private property .
Service across Monroe must be underground . Restora(on per City of Renton Standards .
Contacts
Name Address PhoneTypeBilling
ANISH KUMAR
PUGET SOUND ENERGY - ELECTRIC - BILLING
6905 S 228th St
Kent, WA 98032
B: (253) 208-2183Applicant
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: BL.005109Electrical Contractor : POTELI*344O4
Construc!on Contractor : POTELI*227PL
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
ANISH KUMAR
PUGET SOUND ENERGY - ELECTRIC - BILLING
6905 S 228th St
Kent, WA 98032
B: (253) 208-2183Specialized
Billing
X
General Condi!ons & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
This permit and plans must be posted at the job site at all times.
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Call (425) 430-7203 or go to: www.MyBuildingPermit.com one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 206.510.0575)(Puget Sound Energy at 425.457.5816) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Page 1 | Published: 3/30/2017
Planning Division | 1055 South Grady Way, 6th Floor | Renton, WA 98057 | 425-430-7200
Email: franchisepermits@rentonwa.gov Website: rentonwa.gov
FRANCHISE PERMIT APPLICATION
Published: 3/30/2017
TO THE APPLICANT: Submit an electronic copy of the plans with the Franchise Permit Application and the
Traffic Control Application to franchisepermits@rentonwa.gov. Permit cost is $360.50. Inspection fee for
trenching more than 60 lineal feet or installation of 6 or more poles will be billed at $60.00 per hour.
Franchise Agency:
Franchise Job Number: Phone:
Contact Name: Email:
Job Site Address: Project Name:
Description of Work:
Please check all that apply:
☐ New Construction ☐ Repair/Relocate ☐ Underground ☐ Overhead ☐ Sidewalk ☐ Street
☐ Open Trench ☐ Bore # of feet:
Contractor Name: Phone:
State Contractors License #: City of Renton Business License #:
“I certify that I am the owner or applicant’s authorized agent and do hereby agree to abide to the terms and conditions set forth under this permit and shall comply with the City of Renton’s Trench Restoration and Street Overlay Requirements. ”
Signature Date
INSPECTIONS SHALL BE REQUESTED 24 HOURS PRIOR TO COMMENCEMENT OF ALL WORK BY CALLING THE
INSPECTION LINE AT 425-430-7203 OR BY GOING TO MYBUILDINGPERMIT.COM
Jobs are required to be called in for job start, re-inspection and project final. Re-inspection fees are billed at $75/hour.
All Pre-Construction meetings shall be scheduled at a maximum of 14 days prior to the job start date.
Plan Review/Development Engineering Date Approved as submitted
Pre-Construction Meeting required
Site Construction Inspector Date Approved with comments or redlines
Camera inspection of utilities required
Development Engineering Manager Date
MFP17004487
Restoration per City of Renton Standards Service across Monroe must
be underground.
Holly Powers 11/3/2017
Justin Johnson 11-7-2017
CITY OF RENTON
TRAFFIC CONTROL PLAN
PROJECT NAME: PERMIT#
CONSTRUCTION COMPANY: PHONE#:
CONTACT NAME: PHONE#:
ADDRESS: CELL#:
E-MAIL ADDRESS: FAX#:
PROJECT LOCATION: N/E/S/W OF:
WORK TIME: APPROVED BY:
WORK DATE: APPROVAL DATE:
OFFICE COPY T-
CONTRACTOR
DEV. SERVICE, INSPECTION P. MILLER
DEV. SERVICE, PLAN REVIEW B. BANNWARTH
POLICE CHARLES KARLEWICZ
FIRE FIRE MARSHALL FS #13
Permit Holder agrees to all the following:
• Comply with all traffic regulations of the City of Renton and the State of Washington.
• Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for
all street and lane closures, and the plan shall be performed in compliance with the Manual on
Uniform Traffic Control Devices.
• Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
• Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200
through 47.36.220, 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
• Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments,
including all costs of defense and attorney’s fees incurred in defending against same, arising from and
related to implementation of the approved traffic control plans including claims arising from towing of
private vehicles and the acts of the Permit Holder’s agents and employees.
• The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or
judgment, and in such event shall indemnify and hold harmless the City for any such claims paid,
including the City’s reasonable attorney’s fees and litigation costs incurred resulting from such claim.
• In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder
will pay for legal counsel chosen by the City to defend against same.
• Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address
traffic or pedestrian safety or travel.
• By my signature herein, I acknowledge all the above requirements.
PRINT NAME: DATE:
SIGNATURE:
Reset FormPrint Form
MFP17004487
Justin Johnson
11-7-2017
8:00 am to 3:00 pm
SKETCH
I
-- NORTH --
I
NOTES:
• Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by sketch or reference to WSDOT.
• The plan must be submitted to the City’s PW/Transportation Division for review and/or approval at least three
working days prior to work.
• Approved Temporary Traffic Control Plan must be at the work site during work hours.
• Contractor or entity must call Renton School District (425-204-4455) or any public/private agency to be affected
by a temporary lane or road closure.
• Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded.
• Total road closure lasting more than 24 hours is subject to the approval by the City Council.
• Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
• Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
• Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
72 hours in advance of effective date and time.
• The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
• Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop
(3555 NE 2nd Street).
2121 1212P04P05
AREA UNDER CONSTRUCTION
THE PINES AT HIGHLANDS
MONROE AVE NEMONROE AVE NENE 9TH ST
PROPOSED RD/UNDER CONSTRUCTION
NE 8TH ST
REMOVE NEW
FROM TO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
NO PARK SIGNAGE WILL BE PLACED
ON BOTH SIDES OF MONROE AVE NE
SURROUNDING WORK ZONE
STOP
FLAGGER
STOP
FLAGGERONE LANEROADAHEADW20-4ROADWORKAHEADW20-1W20-7A200'200'200'ROADWORKAHEADW20-1100'
ONE LANE
ROAD
AHEAD W20-4ROAD
WORK
AHEAD W20-1W20-7A200'200'200'R9-11SIDEWALK
CLOSED
AHEADR9-9SIDEWALK
CLOSEDR9-9SIDEWALKCLOSEDR9-11SIDEWALKCLOSEDAHEADPATH OF INSTALLATION
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Job#101106285
850 Monroe Ave NE, Renton WA
August 23, 2017
Sheet 1 of 3 ryan.honeysett@pse.com
(425)457-5381
N
PSE PUGET
SOUND
ENERGY
Notes:
1. All signs and spacing to conform to the MUTCD
and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
4. Sign size can be a minimum of 48" x 48" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m.
TRENCH
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
WORK VEHICLE
SIGN LOCATION
WARNING FLAG
FLAGGER
STOPPuget Sound Energy
Traffic Control Supervisor:
Ryan Honeysett
Card No. 010760
Card Exp. 06/30/2021
ryan.honeysett@pse.com
(425)478-5381
Ryan H. Honeysett
SHEET IS FORMATTED
FOR 11 X 17
MFP17004487
2121
P01 1212P02
P05
AREA UNDER CONSTRUCTION
THE PINES AT HIGHLANDS
MONROE AVE NEMONROE AVE NENE 9TH ST
PROPOSED RD/UNDER CONSTRUCTION
NE 8TH ST
NEW
OH WIRE
CONSTRUCTION;REMOVE WIRE
BETWEEN P01 & P03, P03 & P05
FLAGGERS WILL TEMPORARILY
HOLD TRAFFIC FOR APPROX 5
MINUTES FOR WIRE WORK FROM
P03 & P05
DRIVEWAYS TO STAY CLOSED
DURING WIRE REMOVAL
FROM TO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
NO PARK SIGNAGE WILL BE PLACED
ON BOTH SIDES OF MONROE AVE NE
SURROUNDING WORK ZONE
RESIDENT(S) WILL BE INFORMED
OF POSSIBLE TEMPORARY
DRIVEWAY CLOSURE
STOP
FLAGGER
STOP
FLAGGERONE LANEROADAHEADW20-4ROADWORKAHEADW20-1W20-7A200'200'200'ROADWORKAHEADW20-1100'
P04
P03
PATH OF INSTALLATION
ONE LANE
ROAD
AHEAD W20-4ROAD
WORK
AHEAD W20-1W20-7A200'200'200'CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Job#101106285
850 Monroe Ave NE, Renton WA
August 23, 2017
Sheet 2 of 3 ryan.honeysett@pse.com
(425)457-5381
N
PSE PUGET
SOUND
ENERGY
Notes:
1. All signs and spacing to conform to the MUTCD
and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
4. Sign size can be a minimum of 48" x 48" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m.
TRENCH
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
WORK VEHICLE
SIGN LOCATION
WARNING FLAG
FLAGGER
STOPPuget Sound Energy
Traffic Control Supervisor:
Ryan Honeysett
Card No. 010760
Card Exp. 06/30/2021
ryan.honeysett@pse.com
(425)478-5381
Ryan H. Honeysett
SHEET IS FORMATTED
FOR 11 X 17
MFP17004487
2121 1212AREA UNDER CONSTRUCTION
THE PINES AT HIGHLANDS
P06
J01
V01
MONROE AVE NEMONROE AVE NENE 9TH ST
PROPOSED RD/UNDER CONSTRUCTION
NE 8TH ST
FROM TO
TOW AWAY AREA
PHONE 888-9999
INFRASOURCE LLC 000 0000000
NO PARKING
NO-PARK
NO PARK SIGNAGE WILL BE PLACED
ON BOTH SIDES OF MONROE AVE NE
SURROUNDING WORK ZONE
STOP
FLAGGER
STOP
FLAGGERONE LANEROADAHEADW20-4ROADWORKAHEADW20-1W20-7A200'200'200'REMOVE
P03
RESIDENT(S) WILL BE INFORMED
OF POSSIBLE TEMPORARY
DRIVEWAY CLOSURE
OH WIRE
CONSTRUCTION;REMOVE WIRE
BETWEEN P03 & P06
DRIVEWAYS TO STAY CLOSED
DURING WIRE REMOVAL
ONE LANE
ROAD
AHEAD W20-4ROAD
WORK
AHEAD W20-1W20-7A200'200'200'BEPREPAREDTOSTOPW3-4ROADWORKAHEADW20-1W20-7A100'100'100'
PATH OF INSTALLATION
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
Job#101106285
850 Monroe Ave NE, Renton WA
August 23, 2017
Sheet 3 of 3 ryan.honeysett@pse.com
(425)457-5381
N
PSE PUGET
SOUND
ENERGY
Notes:
1. All signs and spacing to conform to the MUTCD
and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
4. Sign size can be a minimum of 48" x 48" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m.
TRENCH
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
WORK VEHICLE
SIGN LOCATION
WARNING FLAG
FLAGGER
STOPPuget Sound Energy
Traffic Control Supervisor:
Ryan Honeysett
Card No. 010760
Card Exp. 06/30/2021
ryan.honeysett@pse.com
(425)478-5381
Ryan H. Honeysett
SHEET IS FORMATTED
FOR 11 X 17
MFP17004487
MONROE AVE NE1
TRACT D#2 ACSR867
863
859
855
851
820
822
ABCMonroe AVE NETHE PINES AT HIGHLANDS
PRE
11
100T
T9123
100T
T9124
SITE PLAN 101106285SCALE: 1" = 20'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Hong Nguyen 425-449-6609 8/5/2017
Hong Nguyen 425-449-6609 8/5/2017
C.Pompeani 253-208-2665 8/5/2017
Required City of Renton
The Pines at Highlands
SCH'L 73 Conversion
850 Monroe Ave NE Renton, WA 98056
Designed By: PSE
101106285
AS NOTED 1 of 3
King CSPSKEIN
23N 05E 9NE
2305E033 2305E040 2305E033 PRE-11
Century Link/QWEST Comcast Renton School District
SITE SPECIFIC NOTES
P01 318410-166868
- EXISTING POLE TO REMAIN
P02 318419-166868
- INSTALL NEW 45' CL-2 WITH GROUNDS
- INSTALL (1) 3Ø FG DEADEND ARM
- INSTALL (1) DEADEND POLE MOUNT
- INSTALL (1) DEADEND NEUTRAL
- INSTALL (1) TRI UNIT FIBERGLASS OH/UG TERMINATION
- INSTALL (3) L/I C/O FUSE @ 100T & (3) STIRRUP BOLT
- INSTALL SWITCH NUMBER T79123
- INSTALL 4" RISER CONDUIT ON NEW S/O BRACKET
- INSTALL (1) CNRC
- INSTALL (1) 7/16 PRIMARY AND 3/8 NEUTRAL DOWN GUY (NW)
- INSTALL (1) SINGLE HELIX 15'
- INSTALL GRID NUMBER 318419-166868
P03 318427-166868
- REMOVE 15kVA 120/240v 1Ø OH TRF
- REMOVE EXISTING RISER
- REMOVE STREETLIGHT
- WRECK OUT EXISTING 45' CL-3 POLE
- COMMUNICATIONS TO TRANSFER
P04 318412-166860
- INSTALL NEW 35' CL-3 SERVICE POLE
- INSTALL (1) RIGID CLEVIS
- INSTALL (1) 3" RISER ON NEW S/O BRACKET
- INSTALL GRID NUMBER 318412-166860
P05 318439-166852
- EXISTING POLE TO REMAIN
P06 318439-166868
- EXISTING POLE TO REMAIN
- INSTALL (1) TRI UNIT FIBERGLASS OH/UG TERMINATION
- INSTALL (3) L/I C/O FUSE @ 100T & (3) STIRRUP BOLT
- INSTALL SWITCH NUMBER T9124
- INSTALL 4" RISER CONDUIT ON NEW S/O BRACKET
- INSTALL (1) 7/16 PRIMARY AND 3/8 NEUTRAL DOWN GUY (SE)
- INSTALL (1) SINGLE HELIX 15'
J01 318438-166868
- INSTALL 4'-8' X 7' X 5' HH WITH 2-3' SQ DPC
- INSTALL (3) 200A 15kV 4 BUSHING
- INSTALL (7) 12kV ELBOW KIT
- INSTALL (5) 12kV DUST CAPS
- INSTALL GRID NUMBER 318438-166868
V01 318436-166869
- INSTALL 36" X 42" X 38" MINI PAD WITH GROUNDS
- INSTALL 25kVA PADMOUNT TRANSFORMER
- INSTALL (1) 12kV ELBOW KIT
- INSTALL (1) 12kV DUST CAP
- INSTALL GRID NUMBER 318436-166869
SPAN NOTES
P01 TO P02
- INSTALL 3Ø #2 ACSR OH WIRE ± 75'
P01 TO P03
- REMOVE EXISTING 3Ø #2 ACSR WIRE ± 172'
P02 TO J01
- INSTALL 3Ø 1/0 OH TO UG PRIMARY CABLE ± 238'
- INSTALL CABLE TAG AØ EHR270, BØ EHR271, CØ EHR272
- INSTALL 4" SCH'L 80 CONDUIT ± 188'
- INSTALL SPARE 4" SCH'L 80 CONDUIT ± 188'
P03 TO P05
- REMOVE EXISTING OH 1/0 SECONDARY TRIPLEX WIRE ± 115'
V01 TO P04
- INSTALL 350 KCMIL UG TO OH SECONDARY TRIPLEX CABLE ± 188'
- INSTALL 3" SCH'L 80 DISCONTINUOUS CONDUIT ± 148'
P04 TO P05
- INSTALL 350 KCMIL OH SECONDARY TRIPLEX WIRE ± 50'
- RECONNECT SERVICES "855", "859", "863"
P03 TO P06
- REMOVE EXISTING 3Ø #2 ACSR OH WIRE ± 104'
- REMOVE EXISTING 1/0 OH SECONDARY TRIPLEX ± 104'
P06 TO J01
- INSTALL 3Ø 1/0 OH TO UG PRIMARY CABLE ± 66'
- INSTALL 4" SCH'L 80 CONTINUOUS CONDUIT ± 16'
- INSTALL CABLE TAG AØ EHR274, BØ EHR275, CØ EHR276
- INSTALL SPARE 4" SCH'L 80 CONDUIT ± 14'
- INSTALL 90° SWEEP AT POLE AND 10' OF 4" SCH'L 80 STUB OUT
ON S/O BRACKET WITH CAP
J01 TO V01
- INSTALL 1Ø 1/0 PRIMARY CABLE ± 32', TAP A
- INSTALL CABLE TAG AØ EHR243
- INSTALL 2" SCH'L 80 DISCONTINUOUS CONDUIT ± 12'
V01 TO P06
- INSTALL 350 KCMIL UG TO OH SECONDARY TRIPLEX CABLE ± 85'
- INSTALL 3" SCH'L 80 DISCONTINUOUS CONDUIT ± 35'
- RECONNECT SERVICES "867", "871", "880"
OVERHEAD CIRCUIT MAP (2305E040)
SCALE: 6" = 1 MILE
JOB
SITE
THE PINES AT HIGHLANDS
N
Vicinity Map
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL (800) 424-5555
2 BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
No
No
No
Yes
Yes
Yes
"Flagging Required"
"Outages Required"
"Locates Required"
Hong Nguyen
425-449-6609 Cell Phone
Project Manager Contact Information:
Owner / Developer Contact Info
officeATTN:
Habour Homes
400 N. 34th St, STE 300
Seattle, WA 98103
J Waltier 206-315-8130PHONE
CABLE TV
504758367 101106285
N/A 583....
N/A 584....
N/A
N/A
N/A 108....
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
UG Expense
Removal
OH Expense 593....
594....
UG Expense
OH Expense
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
UTILITY POLE EROSION CONTROL DETAIL
TOP VIEW
DRY DRAINAGE DITCH or DRY VEGETATED SITE
SLOPE
Place gravel bags for
Sediment Trap
Place straw mulch
on disturbed areaExcavated or
Augered Hole
Pole
SLOPE
Not to scale Drainage ditches or Dry vegetated sites
JOB
SITE
GENERAL OVERHEAD NOTES
1) POLES, CONDUCTOR, DEVICES TO BE INSTALLED PER PSE
STANDARDS & SPECIFICATIONS.
2) POLES ARE TO BE INSTALLED OR RELOCATED AS STAKED.
3) ALL NEW POLES SET SHALL BE THE CLASS INDICATED ON THE SKETCH
OR BETTER.
4) INSTALL GROUND PLATE ASSEMBLY ON ALL NEW POLES.
5) INSTALL GRID NUMBERS ON ALL NEW OR EXISTING POLES AS
6) TREAT ALL FIELD-DRILLED POLE WITH COPPER NAPHTHENATE
OVERHEAD SECONDARY/PRIMARY NOTES:
PSE NOTES:
1) All work to be done per (PSE) Standard Practices.
Site Preparation - Prior to Construction, work area to be at or
near finished grade & clear of soil or construction materials which
would restrict construction access.
Equipment Access - Adequate space is to be maintained around
electrical equipment & facilities unimpeded by shrubbery, ponds,
fences, rockeries, walls, structures, etc..
4) Customer / Developer to coordinate between utilities.
2)
3)
WOOD PRESERVATIVE.
SHOWN ON SKETCH.
DEVELOPER CIVIL CONTRACTOR NOTES:
·REQUIRED TO PROVIDE AN 11' X 9' PIT AT J01.
·REQUIRED TO PROVIDE 6' X 6' WORK PIT AT V01.
·REQUIRED TO PROVIDE A 4' X 4' WORK PIT AT P02, P04, AND P06.
·REQUIRED TO PROVIDE 6” CRUSH ROCK FOR 3PH VAULTS.
·REQUIRED TO PROVIDE TRENCH ± 188' FROM P02 TO J01.
·REQUIRED TO PROVIDE TRENCH ± 148' FROM V01 TO P04.
·REQUIRED TO PROVIDE TRENCH ± 12' FROM J01 TO V01.
·REQUIRED TO PROVIDE TRENCH ± 35' FROM V01 TO P06.
·REQUIRED TO PROVIDE TRENCH ± 16' FROM J01 TO P06.
·REQUIRED TO PROVIDE AND HAVE EQUIPMENT TO PUMP OUT WATER FOR METER BASE PITS &
TRENCH AT ALL TIMES.
CUSTOMER IS RESPONSIBLE FOR ALL TRENCHING, SELECT BACKFILL, COMPACTION & RESTORATION PER
PUGET SOUND ENERGY STANDARDS# 6750.6500.
** DEVELOPER NEEDS TO FOLLOW ALL TRENCH DETAILS ON SELECT BACKFILL **
CONTRACTOR TRENCHING IN CITY OR COUNTY OR W.S. DOT RIGHT OF WAY NOTES:
PLEASE REVIEW THE CITY OR KING COUNTY TRENCHING REQUIREMENTS UNDER THE PERMIT.
IF A PRE-CON IS REQUIRED BY THE CITY, COUNTY OR W.S. DOT A PSE PROJECT MANAGER WILL SET-UP
AND SCHEDULE A MEETING WITH THE MUNICIPALITY BEFORE ANY EXCAVATION OR INSTALLATION
BEGINS
ALL INSPECTIONS ARE REQUIRED BY POTELCO INC
·IF A SECOND INSPECTION IS REQUIRED, ADDITIONAL FEE'S WILL BE APPLIED.
MFP17004487
INSTALL ± 85' 1Ø 350 KCMIL
INSTALL ± 66' 3Ø 1/0
INSTALL ± 188' 1Ø 350 KCMIL
INSTALL ± 238' 3Ø 1/0
INSTALL ± 33' 1Ø 1/0
INSTALL ± 75' 3Ø OF #2 ACSR
INSTALL ± 50'
1Ø 350 KCMIL
AØ EHR270
BØ EHR271
CØ EHR272
AØ EHR274
BØ EHR275
CØ EHR276
AØ EHR273
100T
T9123
100T
T9124
CUSTOMER SUPPLIED 11' x 9'
WORK PIT
CUSTOMER SUPPLIED 6' x 6'
WORK PIT
CUSTOMER SUPPLIED 4' x 4'
WORK PIT
CUSTOMER SUPPLIED
4' x 4' WORK PIT
INSTALL (2) ± 16' 4" SCH'L 80
INSTALL (1) ± 35' 3" SCH'L 80
INSTALL (2) ± 12' 4" SCH'L 80
INSTALL (1) ± 148' 3" SCH'L 80
INSTALL (2) ± 188' 4" SCH'L 80
REMOVE ± 109' 1Ø 1/0
REMOVE ± 104' 3Ø #2 ACSR
REMOVE ± 172' 3Ø #2 ACSR
REMOVE ± 115' 1Ø 1/0
CABLE ONE-LINE DIAGRAM
101106285SCALE: NONE
WIRE REMOVAL TABLE
Location
Wire Size & Type Quantity
Length
(per
conductor)RemarksFromTo
P01 P03 3Ø #2 ACSR 3 172
P03 P05 SEC TPX 1/0 1 115
P03 P06 3Ø #2 ACSR 3 104
P03 P06 SEC TPX 1/0 1 104
Total Feet (Wire Size & Type) Removed
POLE TABLE (NEW)
Site
#
Pole Data
Grid #Height Class Year Remarks / Location Ref.
P02 318419-166868 44 2 2017 PSE Equip #
P04 318412-166860 35 3 2017
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P03 318427-166868 45 3 1985
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT PRIMARY CABLE
ASBUILT INFORMATION
SIZE Qty LENGTH
Design
(ft)
BENDS PULL PULL Cable LENGTH
Design
(ft)
Cable Numbers Please Record Foreman - Complete
FROM TO (in)90°45°22°11°(lbs)
Rev
(lbs)Size A B C Manufacturer Compound Year Actual Amount Installed (Conduit & Cable)
P02 J01 4 1 188 1 2 228 714 1/0 3Ø 238 EHR270 EHR271 EHR272
J01 V01 2 1 12 33 33 1/0 1Ø 32 EHR273
P06 J01 4 1 16 1 59 374 1/0 3Ø 66 EHR274 EHR275 EHR276
REMOVAL DIAGRAM
SCALE: NONE CONDUIT DIAGRAM
SCALE: NONE
CONDUIT RISER PLACEMENT DETAIL
TOP VIEW
Not to Scale
Standoff Bracket
15" Min Length
Conduit Clamp Conduit
Field Face
Quadrant
Climbing
Space
Road Face
Quadrant
Climbing
Space
5" Min
CL LCDirection of Vehicular Traffic
TOP VIEW
SIDE
VIEW
EXCAVATION:
4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"
36"
38"
42"
42"FRONTFRONT
VAULT DETAIL
Not to Scale
2"
Excavation - 19-1/2 cubic yards
SIDE VIEW
5'-4"Crushed
6"
Rock
TOP VIEW
9'
11'
THREE PHASE J-BOX AND EXCAVATION DETAIL
NOT TO SCALE MID # 7663200
TV & TEL Electric Service Cable in Conduit
3" Schedule 40 Grey PVC
Excavated Dirt Pile
Final Grade
24" Min
24" Min
to
36" Max
Cover
Backfill for Conduit
Free of rocks
larger than 8"
in diameter
Separation
6" Min
in Conduit
Schedule 40 White PVC
Gas Service Line
32" Typical
(Power, Gas,
Phone & Cable)
Separation
4" Min
12" Min
Separation
36" MINIMUM COVER
IN RIGHT OF WAY
JOINT TRENCH DETAIL
Joint Service Line in Conduit (NTS)
To Excavated Dirt Pile
Backfill for In Conduit - The backfill layer shall be soil that is free from construction debris,
glass, sharp rocks, frozen clods, and rocks larger than 8" in diameter.
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Hong Nguyen 425-449-6609 8/5/2017
Hong Nguyen 425-449-6609 8/5/2017
C.Pompeani 253-208-2665 8/5/2017
Required City of Renton
The Pines at Highlands
SCH'L 73 Conversion
850 Monroe Ave NE Renton, WA 98056
Designed By: PSE
101106285
AS NOTED 2 of 3
King CSPSKEIN
23N 05E 9NE
2305E033 2305E040 2305E033 PRE-11
Century Link/QWEST Comcast Renton School District
MFP17004487
AØ EHR 274
BØ EHR275
CØ EHR276
AØ EHR273
AØ EHR270
BØ EHR271
CØ EHR272 101106285SCALE: 1" = 50'
AFTER UNDERGROUND CIRCUIT MAP (2305E033)
SCALE: 1" = 50'
BEFORE UNDERGROUND CIRCUIT MAP (2305E033)
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Hong Nguyen 425-449-6609 8/5/2017
Hong Nguyen 425-449-6609 8/5/2017
C.Pompeani 253-208-2665 8/5/2017
Required City of Renton
The Pines at Highlands
SCH'L 73 Conversion
850 Monroe Ave NE Renton, WA 98056
Designed By: PSE
101106285
AS NOTED 3 of 3
King CSPSKEIN
23N 05E 9NE
2305E033 2305E040 2305E033 PRE-11
Century Link/QWEST Comcast Renton School District
MFP17004487