HomeMy WebLinkAboutP_Design_105086706_V1_171110WORK
ZONE
WORK
ZONE
J 3600VERIZONE VALLEY HWY316636-165776
316622-165788
T80
316654-165789
T79
316657-165778
SL1018852
316624-165777
SL1018722
316636-165787
50 kVA 120/240V (A)
75kVA 120/240V (A)
SITE PLAN
N
Vicinity Map
N/A
Owner / Developer Contact Info
officeATTN:
VERIZON WIRELESS
PO BOX 2375
SPOKANE, WA 99210
Amber Kerr (360) 438-8002
SITE SPECIFIC NOTES
OVERHEAD CIRCUIT MAP (2305E124)
SCALE: 6" = 1 MILE
ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
CIRCUIT LOADING TABLE
AS OF
EXIST. PEAK LOAD
EST. NEW LOAD
TOTAL
CIRCUIT:
A PHASE B PHASE C PHASE
VIC-16
6/13/17
239 196 226
.98 --
239.98 196 226
GAS
PHONE
CABLE TV
N/A 101108383
N/A 108103292
N/A 583057976
505051718 104297057
N/A N/A
N/A
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
HH Replacement
HH Removal
TRF Removal
Service Connection
Job Order
Distribution
HP Svc/MSA
POWER GENERAL NOTES - COMMERCIAL PROJECT
8.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits
and crossings from the individual unit's meter base to the designated connection point.
Inclement weather conditions may cause delays in construction times and dates.
1.
2.
3.
4.
5.
6.
7.
9.
11.
10.
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
X
X
X
X
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:Val Buzunov
(425) 457-9938
VAL.BUZUNOV@PSE.COM
SCALE: 1" = 50'105086706THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Val Buzunov (425) 457-9938 10/24/17
Nate Linville (253) 970-7284 10/24/17
N/A N/A N/A
Nate Linville (253) 970-7284
N/A City of Renton
Verizon SEA Teasdale TRF Upgrade
REPL 1Ø 120/240V PM TRF, REPL SEC HH, CONN SVC
3600 EAST VALLEY RD, RENTON, WA 98057
N/A N/A
N/A 105086706
AS NOTED 1 OF 1
KING N/A N/A CSPSKEPM
SE-30-23-05E N/A N/A
2305E120 2305E124 2305E120 VIC-16
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
Service Stubs
105086706
N/A
N/A
504967927
N/A
CIRCUIT FEET ADDED: 0
LRC:
% V. Drop:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
0 SQ.
200 AMPS
NONE
6KW
65A
1.7%
0.6%
SW 41ST ST
SW 34TH ST
AT V01: EXISTING
EXISTING 42" X 36" MP HAND HOLE TO REMAIN
REMOVE EXISTING 50kVA 120/240V PM TRANSFORMER AND RETURN TO PSE YARD
-INST. 1 - 4" 48" X 48" SPLIT RISER W/22" X 26" ACCESS HOLE (MID: 9998565)
-INST. 1 - 75kVA 120/240V PM TRANSFORMER
RECONNECT EXISTING SECONDARY CONNECTION BLOCKS
AT HH1: REPACE
CUSTOMER TO EXCAVATE AROUND EXISTING SECONDARY HAND HOLE
EXISTING B/O CONCRETE HAND HOLE TO BE REMOVED
-INST. 1 - 2'8" X 3'8" CONCRETE HAND HOLE W/STD PLATE LID PER STD 6050.2020 (HH16500SP)
-INST. 3 - 6POS #6 - 500KCMIL SECONDARY CONNECTION BLOCKS PER STD 6050.2020 (MID: 7651001)
CONNECT AND TAG 1 - RUN CUSTOMER INSTALLED, OWNED, MAINTAINED 250KCMIL TPLX SVC
PSE METER DEPARTMENT TO SET CL20 METER
FOREMAN NOTE
PM TO COORDINATE OUTAGES
GATE CODE 7011
DEVELOPER & CUSTOMER NOTES:
THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL TRENCHING, SELECT BACKFILL, COMPACTION &
RESTORATION PER PUGET SOUND ENERGY STANDARDS 6750.6500
-REQUIRED TO PROVIDE 6' X 7' WORK PIT & 1 CUBIC YARD OF 5/8" MINUS AT HH1
-REQUIRED TO FOLLOW ALL TRENCH DETAILS ON SELECT BACKFILL
-REQUIRED TO PROVIDE EQUIPMENT TO PUMP OUT WATER FOR WORK PITS & TRENCH AT ALL TIMES
-EXCAVATE & EXPOSE EXISTING PSE UG FACILITIES 48 HOURS PRIOR TO CONSTRUCTION
-PSE INSPECTION IS REQUIRED PRIOR TO FINAL BACKFILL
-PSE WILL NOT ENERGIZE FACILITIES UNTIL BACKFILL IS COMPLETE
-L&I INSPECTION & APPROVAL IS REQUIRED 72 HOURS PRIOR TO CONNECTION
-RESPONSIBLE FOR ALL TREE TRIMMING AND BRUSH CLEARING
AT HH1 - SINGLE PHASE SECONDARY CONCRETE HANDHOLE
Not to scale 6050.2020-2
Steel Door
Handhole
1900 lbs
Typical customer run
service conductors in duct
Seal conduit
with foam
Install PVC bell ends
and grout into wall
Conduits and conductors shall enter from
ends of handhole through knockouts provided
TOP VIEW
SIDE VIEW
3'-4"
EXCAVATION: 5-1/3 CUBIC YARDS
7'-0"
6'-0"
6" Crashed rock
2"
Customer-installed grounding wires ( the "4th" wire on the single-phase systems and the "5th" wire on
the three-phase systems) shall not be connected to PSE's ground or neutral bus. They shall be
removed by customer or cut off at the vault wall.
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
V01
316636-165787
75kVA
6247150
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
V01
316636-165787
50kVA
UNDERGROUND CIRCUIT MAP (2305E120)
SCALE: 1" = 50'