Loading...
HomeMy WebLinkAboutP_Design_101102076_V1_180109PSE GENERAL SPECIFICATIONS General - All work is to be completed per PSE Standards & Practices. Copies of all PSE Standards are available upon request. - Work sites shall be kept clear of debris and all construction materials, equipment and packing shall be removed daily. - Return all unused and removed poles, transformers and hardware to PSE, storeroom. All copper shall be coiled and returned the day it is removed from the poles. Remove all unused pins and insulators. - Return all Street lights, area lights and floodlights to Sumner yard. - All fault indicators will be maintained in their current location on the 1/0 cables upon completion of the job. If it is noted to remove any of the indicators they shall be returned to local PSE first response department for re -issue. Preconstruction - Notify appropriate city, County or DOT authorities 48 to 72 hours, or as required by permitting agency, in advance of starting work in Right-of-way involving a Permit. - All system switching shall be approved by System Operations (425-882-4652) a minimum of 48 hours in advance. - Notify customers of all outages 48 hours in advance. Work Drawings & Documents - Field design changes shall be approved by PSE Project Manager or Engineer. - Mark all field changes, equipment ID numbers and Underground cable information in red on Foreman's copy of work sketch. - Return one Foreman's copy of work sketch to Project Manager at completion of job. - When permits are required, a copy shall be available on work site at all times. Safety Refer to PSE standards 6275.3000 and 6275.6000 for system ground requirements. - Refer to PSE standards 6275.9050 for personal protective grounding requirements. - Refer to PSE standards 6275.9150 for vehicle grounding and barricading requirements. - Proper line clearances shall be taken at the beginning, and released at the end, of each work day, or as otherwise instructed by the System Operator. ABANDONING PRIMARY CABLES PSE std. 6825.6200 In a Vault if the cable is In conduit, -Remove the cable Not in conduit or it cannot be pulled out, -Cut the cable off approximately one foot from the vault wall. -When practical, attach the old cable number to the cable stub. In a Mlnlpad hand hole In conduit, -Remove the cable Not in conduit or it cannot be pulled out, At Risers if the cable is -Cut the cable off as much as practical -When practical, attach the old cable number to the cable stub. -Stuff the tail into the bottom of the handhole. Be sure the new cables are not trapped by the old cables or the concentric neutrals. In Conduit -Remove Cable Direct buried or it cannot be pulled out, -Cut off & cap the cable at the top of the riser. and the pole will remain. -Attach the old cable number to the cable stub. DIRECT BURIED Direct buried or it cannot be pulled out, and the pole will be replaced -Remove the riser. -Cut off & cap the cable underground near the base of the pole. Traffic /Pedestrian control notes The cable is direct buried or it cannot be -Cut off & cap the cable underground near the base of the - Utilize flagging and other vehicle traffic control as necessary and in conformance with local pulled out, and the pole will be removed. pole. traffic regulations. J ❑ -The uniform code of traffic control shall be adhered to at all times.. ' -Provide signs, barricades, and traffic control in conformance with local permit regulations. DISCONNECT: -Provide route for pedestrians when working on or near sidewalks. NOTE: If the pole is to be replaced, remove the abandoned riser and elbow, and stand off brackets age: (unless they support other conduits). -Maintain traffic flow as required by permitting agency. NOTE: If the riser is made of transite material, it shall be removed following procedures in standard 0100.5000, COMBINATION J-BOX/PADMOUNT XFMR "Transite Pipe Removal and Disposal." NOTE- Completely rebuild terminations. EXCEPTION: DO NOT REPLACE CUTOUTS Company ID#'s RECORDED in correct location on As -built. UNLESS THEY ARE THE OLDER "BOX TYPE" OR 50 AMP "TRIP LINK" TYPE CUTOUT. -Remove (not abandon) aboveground transite riser when it is encountered in the field. Belowground transite may be left in REPLACE J -BOXES IF REQUIRED. UTILIZE FEED-THRU T.U.T.s AND REMOVE place and backfilled. (Transite is a mixture of asbestos and cement. Itis nonmetallic, flame-retardant, and resistant RMAL OPEN (N.C.) to moisture, low temperature, and corrosive agents). J -BOXES IF POSSIBLE. REPLACE ALL TRANSFORMER JUMPERS WITH NEW 1/0 -For removal use an approved certified abatement contractor. Call the Environmental Services Department 24-hour pager JACKETED CABLE. (206-994-3186) to have a contractor dispatched. ❑ Procedure to Abandon Primary Cables: UNDERGROUND CONSTRUCTION 1. Call the Systems Operator to request a clearance. ILL NOT PHASE (WNO) 2. Follow the directions to ensure the cable is de -energized, apply proper tags as specified in Standard Practice Additional notes to standards. 0201.1011, "Switching and Clearances Handbook," and report back to the Systems Operator. -Erosion control must be placed before construction starts. Silt bags must be installed in 3. Obtain a clearance from the Systems Operator on the cable to be abandoned. downstream catch basins. 4. Cut the ends of the cable. CP— 5. The cable number tag may be left on the abandoned cable. TO UNDERGROUND CABLE TERM. NOTE: The cable number shall not be reused. Existing Utilities: 6. Call the Systems Operator and release the clearance. Hand excavate (pothole) all marked utility crossings to verify exact location and depth at point 7. Remove all "Danger Do Not Operate" tags. of crossing. Protect underground utilities during excavation. Use hand excavation methods if 8. The System operator will then close the Incident Number (1 -number). necessary to avoid damage to existing utilities. Fabricate and install adequate temporary Existing System: structures to support and protect underground utilities while exposed during construction. MAPPING i PAD MOUNT XFMR Maintain existing electrical system in service until new system is complete, tested, and ready for service. Maintain 6" minimum clearance at crossings between existing utilities and new duct Disable existing system only to make cutovers and connections as directed by PSE System Operator. installations. Transition trench or tunnel profile gradually as required at crossings. Maintain SCOPE OF WORK 24" minimum separation between new trench or tunnel and parallel existing utilities or as The general scope of this project is to remediate primary 1/0 cables within the project area by the most economic required by the permit agency. means possible using replacement, or abandonment. Excavation The project involves replacing existing electrical cables in new conduit. - Trenchingoutside of the Right-of-way shall be of sufficient depth to provide a minimum of g Y p SPLICE 36" of cover for primary conductors and 24" of cover for secondary conductors. Project type : Planned - Road crossings and all trenches within the Right-of-way shall be of sufficient depth to Project location: 2800 NE SUNSET BLVD., RENTON, WA 98056 provide a minimum of 36" of cover for all conductors or as required by the permitting Agency. - No rocks larger than 6" shall be included in backfill. Number of Cables: 40 - Back fill in road crossings and within the Right-of-way shall be compacted to 95% density or Cable Footage Estimated : 7,600" as required by the permitting Agency. Cable Numbers Injected : 0 - Restore all excavated areas to original condition. Cable Numbers Repaired: 0 Cable Numbers Abandoned: 0 Vaults & Hand holes Cable Numbers Replaced: 18102-116, 18120-131, 16889-891, 32855-857, & 7 JUMPERS - Refer to PSE standard 6775.0040 "Vault and Hand hole Installation" Trench Footage Estimated : 2,740' - Vaults shall be placed level and 2" above final grade in landscaped areas and flush with final grade when placed in hard surface areas. There will be an advance notice provided by the contractor - A minimum 6" bed of 5/8" crushed rock shall be placed under all vaults. 24-hour advance notice of no parking in work areas. Access will be maintained to all residences and their - All conduit entrances shall be grouted. driveways. When work is occurring directly in front of driveways, the contractor will work with the residence to manage access. Conductors & Conduit - Refer to PSE standard 6800.6000 "PVC Conduit Installation". Traffic Revisions - Unless splices are called for, or otherwise noted or approved, conduit risers Shall be Flagging crews will maintain one lane; flaggers will assist vehicles alternating through the roadway during work plumbed directly to road crossing conduits. hours. - Install insulating caps on all unused primary bushings. For more information on the project - Civil crew to install Conduit plug on each end until new cable to be installed. 24-hour project information (888) 471-7339, (360) 825-5236 - All "spare" conduits shall be capped at each end. Surface Restoration Restore ground surface to original contour and original condition or better. Restore asphalt and concrete In accordance with requirements of local permitting agency. Cold patch or plate trench when necessary. Leave area in its original state or better at the end of construction. OVERHEAD APPARATUS "When performing planned work on a pole with an existing transformer or device, the Service Provider will change out bolted connectors to pressed connectors". Use unit 1-3A to charge time. If you are working on a pole with the pole ground connected with a hot tap, replace it. If the transformer has split bolts on the secondary neutral or services, replace them. If the primary neutral is connected with a hot tap, replace it. If the transformer bank has a 2 -bolt connector on the neutral bus, reblace it. INDEX PAGE 1 - GENERAL NOTES PAGE 2 - SITE PLAN PAGE 3 - CABLE & CONDUIT DIAGRAM PAGE 4 - EXISTING UNDERGROUND MAP PAGE 5 - CIVIL SITE PLAN SURFACE IMPROVEMENT AND RESTORATION 1) FOLLOWING FINAL GRADING ACTIVITY, SOD SHALL BE PLACED ON EXPOSED SOIL TO PROVIDE PERMANENT AND IMMEDIATE EROSION PROTECTION. 2) TEMPORARY COLD MIX SHALL BE PLACED ON EXPOSED GRAVEL IN HARD SURFACE FOR IMMEDIATE EROSION PROTECTION AND HOT MIX ASPHALT WILL BE APPLIED AT FINAL RESTORATION TO PROVIDE PERMANENT EROSION PROTECTION. EXPOSED SOIL PROTECTION NOTES: AREAS WHERE THE GRADING ACTIVITIES, BORE PIT EXCAVATION OR UTILITY POT HOLING, WILL BE TEMPORARILY STABILIZED BY ONE OF THE FOLLOWING METHODS WHICH ARE BASED ON PERIOD OF EXPOSED SOILS ARE LEFT UNWORKED. -THERE WILL BE NO EXPOSED SOILS ON SITE DURING CONSTRUCTION. ALL SPOILS FROM EXCAVATION WILL BE VAC EXCAVATED INTO THE TRUCK. EROSION & SEDIMENT CONTROL REQUIREMENTS EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE 0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL & ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS. (LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION' STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.) Filter fabric skirt Secured with grate. Z7� Catch Basin — Overflow F ter fabric walls for Collected Sediment de,•vatering sediment Catch Basin Insert MID 9995728 Gravel bags (MID 9995692) must be higher at sides / than center. z:,, ✓iri,. 6" Min Gravel Check Dam EROSION CONTROL NOT TO SCALE LEGEND 0 ELECTRONIC MARKER Q SOLID BLADE DISCONNECT J ❑ UNDERGROUND COMBINATION J-BOX/XFMR ' FUSED DISCONNECT: ❑ Material VERIFIED and CHANGES noted on Paperwork. age: 1 T, 15T, 25T, 40'T, 100T -INDICATES FUSE SIZE J A COMBINATION J-BOX/PADMOUNT XFMR ❑ ❑ Company ID#'s RECORDED in correct location on As -built. CALL (800) 424-5555 ' -� I-- N RMAL OPEN (N.C.) ' J ■ NEW UNDERGROUND COMBINATION J-BOX/XFMR Correct QC Checklists) reviewed. THIS SKETCH N( T TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES ❑ ❑ Deviations noted on the AAs -built and their reason. -W —No ❑ ILL NOT PHASE (WNO) P-11 NEW COMBINATION J-BOX/PADMOUNT XFMR REQ- CITY OF RENTON 1/4 SEC NW -9-23-5 and that all quality requirements are met. PLAT MAP N/A #1 Foreman's Signature CP— OVERHEAD TO UNDERGROUND CABLE TERM. FOREMAN 1 TOTAL UNDERGROUND XFMR(T.U.T.) U -MAP NO (POWER) 2305EO34 #2 Print Name _ Date CIRCUIT NO PRE -11 FOREMAN2 N =W OVERHEAD TO UNDERGROUND CABLE MAPPING i PAD MOUNT XFMR �— TERMINATION F0_1 NEW UNDERGROUND XFMR O FAULT INDICATOR ❑4 NEW PADMOUNT XFMR CABLE SPLICE DJ UNDERGROUND J -BOX QM P IMARY METERING Q3 UNDERGROUND SWITCH - o C BLE TERMINATION BUS (J -BOX) PULL VAULT THREE PHASE WIRE/CABLE - 12.5 KV Q HANDHOLE - •I - S NGLE PHASE, ONE WIRE/CABLE - 7.2 KV -- CABLE TO REPLACE A BREVIATIONS P E. = POLYETHYLENE X F.M.R. = TRANSFORMER N T.S. = NOT TO SCALE Trench and backfill requirements for primary electric line extension trenches A 12" layer of sand is required when excavated native material contains rocks up to 10" in diameter. A 3" layer of sand is allowed when excavated native material contains rocks no larger than 8" in diameter. Excavated Dirt Pile ROADSIDE 12" Typical we 24" Min Final Grade 36" Min Cover (ROW) 24"Min Cover (Pvt. Property) 48" Max TRENCH DETAIL NOT TO SCALE Backfill (No rocks over 10" diameter) 12" Min Sand Shading -1,-�` t — 3" Sand Bedding — Primary Power in DB120 Conduit (ROWj Primary Power in SCH80 Conduit (Pvt. Property) Cables or Conduit - W WN0 ' ME 22 .sr .. 6 A f C� 2o---�_- j 15 A'. .B - 103B - - W ' Q C C i r`; i ..... I N 40T N� C' 6 T C 1��i 1004 �� �wll X12520 15T _55 T NE 2e 77 TWJ25!t25 _t x X76779 4 �r- 40TH 4oT�� �40T 25T 1 :C I IC OTi 40T' `t 1 NE 20 ST I \ , : C / *25T 5T Z i W ( EO �B�,%�76780 C r. J a t X11864 40T • : C • •� C; Ofd I 25T 0T - ' No 30 WNL NE j8 S CO2370'. ,.;'Q- _B X10425 Q' I CI Q #m - ~ _ A 40T J� 25T @::-,X91,387 - X �25T Ir T }- - 0 � 1 X5128 25T}� -�• A 25T; 25T _40 T WN0 ti 00 r , I A0 : ...... I X104248 >5T �25T� 25T.11 X14791 15 X16 40T ' • C �' L_ _ T _ _ Z� X626o X150g %8�! f_ _ lYT t x X9508 t 4o Wt NE 16 25T B S �65r Y -p.•••. .B ...0 :S A � T- QZI BiW r6 It r. •'U0321 38 'i - IQ Z ce)_ .:::� .. :..SSE .aLIADA o 00' 00 01 io 25rQ11 � A� `' ' X3317c3� =X1508 ; AO A' `'��I U `:4 25T IW V IC ©L- Q I - 40T 4 40T 9 `l I I - 40T24»- T I '30 C lu HIG —1 L� cool 86 775_ p.. •A 3DA 25, �� '3 ;! Z1 158 • HIG T X42154201 I U315 77 637. •X3310 65T U317'\_ioo8 W 17 ss U 7_'•. .30 •S X 1506. . c 159 r •ai. 30 65T 0 X00429 � M X8360"40T X s •.. Y.. I...:,NE 12 ST A S ?403 ' X7554'%`o NE 12 ST4 IG �1� U315� .3� : T �o - NO �X X� �25T , I 21 novo 165Ti�_ '� 0� 17 1513 B: I m �� , — C 16 A HIG LANDS" C: I } B 3 B0 �--� Qr� 1m OR _ SUB TATI ON X10276 ��V15T 65T 165 65T I t-- 40TC l o NO 34,..I•'' •: 3' FT 40T ��, I ss Ofd _ _ I12 A. . • •X1060 1 h� J� X677 1 o- -- o IA c� �`�� .:.�.. ..� `5 `�D� W I' t a�-� }c� yC 30 80K a�, }O�o�h = I rn r_ R; 1121 Wr A NO C X110 _ Hlc • X1503 65T• I o°021 1004 40T __ , 13 40T I A "tx E-�_ NE 10 � 2 X9235X4452 40T C- 19 S_T Q C '30 40T o, 1 Z I 10 - -A 25T B" X40®0_ _ B_ A CO C 30'..11 �:3� PRE X� Y O 65T �- NE t0 Sr _-11, 001110 ICD -NE 9 PL, 11 v I X9848 - i WNO 80 A0 �u� 1 wil AIS A•; co: 65T I X9850 Q `-- -� 40TXS ==1N _NE 9 ST 25T ���� Imo I o. 10755 ZI 65T y� t J B" X9673 IIS -T- OIb �� ��XI B0 65T ; -r 40 INO /%e_9 N 14 X0812 ,„ 00 6�OT 40T ---; i NO ST i I 25 o I 100T ► i I L�� �25 NO /) '25--- B 4r e ST 'B0 1001. 25T "\ r 1--1--�---� - ��� 80'--1 25 -, : # I A I © 7 X985100 M , X678 r 65 30•� 401 �A IA B �NK442 65T o Io0 4080 1 I +Ic-- _ _ NDS 9973 /I/�c- X857 B. r Y o h 5435 1 - NE 6 HIGHLANDS . • ''g S 1�1- A - -??� i 25 ELEM NE R B - CK06387 _T, I 25 AO ( 25TI 651 100T X1930 30'651 401 • :.40T 100 00 MO ' � I 25T' `� p�� I� %, ■ X1929 = 100 o0 T I QI•-- HIG C , �� •� BI 10 65T I N -6 PL W nE T Pc'� 4O .' I lAO Z, 16 �. % A r =I 2 �� t I �If-- 65T L40T- `�� �� ���0 I ATA '-Q �I O IVE 6_PL� A0 1---�- 1 k Z > A100TIC04260 c 40T t.�� P� �� I 1 iy W I Q Q CK443 X2339 ©I1 ---N- --- '•...s 'W 405 100 X10T 25T 359 IQ) - _ X1111C03521 E r - = q! X1100? :....,. ....:. OK255A = NE 6 .• ST •:' o~� 1 C c� iW ESPL'30: 40T�N IZ 0;30 :..t..3 :. _ •' •� �• A• �rn r40T i� I .•A • 1 m A� 401 11 �' •• I Aix Z:.: PRE 1' 42Sj to 25// `\ I B e.... 9 �• . B.. 30 1, � 401 •C L _ 3 0� X89i.- •1, ��e. N N S U128 _ _ 3Sd' e: ,•30 • c 1. TE I'FE/,'iVDAU ' ....C.. d� o X363 '• 30 ...:..... .. .....;.�\j�o X3935 R....... t''30 : X47444310nnTl QST OVERHEAD CIRCUIT MAP: #2305E040 SCALE 6" = 1 MILE 12" MIN 12"MIN 12" MIN / PAVEMENT/ SIDEWALK A PHALTPATCH, 2" MIN S / MATCH EXISTING VERTICAL SAW 48" MAX CUT LINE 36" MIN (ROW) CRUSHED SURFACING 24" MIN (Pvt. Property) MATERIAL COPMACT TO 95% MAX DENSITY. 12" Min Sand Shading Primary Cable(S) 1 in Conduit a 3" Sand Bedding EXCAVATION AND HARD RESTORATION DETAIL NOT TO SCALE #1 1 #2 FOREMAN (CHECK BOX WHEN COMPLETED) ❑ I ❑ PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition PROJECT PHASE ❑ ❑ Grid, Cable, and Switch numbers INSTALLED & VERIFIED. 2,875' ❑ ❑ Field Changes RED -LINED on As -built. MAKE N CHANGES TO THIS JOB WITHOUT PRIOR APPROVAL ❑ ❑ Material VERIFIED and CHANGES noted on Paperwork. age: ❑ ❑ Total PRIMARY Cable noted on As -built. 574,745' ❑ ❑ Company ID#'s RECORDED in correct location on As -built. CALL (800) 424-5555 ❑ ❑ indicate correct FUSE SIZE on As -built & VERIFY proper PHASE. ENGR - GA ❑ ❑ Correct QC Checklists) reviewed. THIS SKETCH N( T TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES ❑ ❑ Deviations noted on the AAs -built and their reason. No ❑ ❑ I certify that the work performed meets PSE's standards and procedures CHECKED BY Orr,(� REQ- CITY OF RENTON 1/4 SEC NW -9-23-5 and that all quality requirements are met. PLAT MAP N/A #1 Foreman's Signature #1 Print Name i Date FOREMAN 1 #2 Foreman's Signature U -MAP NO (POWER) 2305EO34 #2 Print Name _ Date CIRCUIT NO PRE -11 FOREMAN2 PROJECT PHASE NOTIF# ORDER# SUPERIOR FAILED SILICONE REMOVAL O&M MAINTENENCE EXPENSE 11267517 f 101102076 2,875' 108098039 DATE 0 MAKE N CHANGES TO THIS JOB WITHOUT PRIOR APPROVAL CABLE REPLACEMENT Trench Method: Approximate Trench Footage: Abandon Cable Segments: Replaced Cable Segments: Approximate New 10/30 1/0 pri. Cable Approximate 2"/4" Poly Conduit Footag Vaults: "Locates Required" Yes "Outages Required" Yes "Flagging Required" Yes VICINITY MAP PSE: PLANNER 355 - 11 PTH AVE NE BELLE IIUE, WA 98004 RICK B6ELL 425-462-3936 O N 4 3 TRENCH/BORE For con3cts below dial 1 -888 -CALL PSE (225-5773) FUNCTION 2,875' PHONE NO DATE 0 MAKE N CHANGES TO THIS JOB WITHOUT PRIOR APPROVAL 40 Notify dustomers and Service Area age: 25'/5,420' 48 HR Prior To Planned Outages 574,745' ENGR - POWER C. TOBIN 2 CALL (800) 424-5555 REV# DATE BY 2 BUSINESS DAYS BEFORE YOU DIG ENGR - GA N/A No N/A THIS SKETCH N( T TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES No as Wk Ctr N/A POWER WK CTR QSEPRE No F. SHANK REAL ESTATE/EASEMENT PERMIT 09-20-17 CHECKED BY Orr,(� REQ- CITY OF RENTON 3 FUNCTION CONTACT PHONE NO DATE 2 PROJECT MGR C. YLENNI 253720-9700 09-27-17 1 ENGR - POWER C. TOBIN 253-548-4516 09-20-17 REV# DATE BY DESCRIPTION ENGR - GA N/A N/A N/A COUNTY KING Emer Sect N/A as Wk Ctr N/A POWER WK CTR QSEPRE DRAWN BY F. SHANK 253-234-6114 09-20-17 CHECKED BY Orr,(� 1/4 SEC NW -9-23-5 OP MAP N/A PLAT MAP N/A APPROVED BY FOREMAN 1 U -MAP NO (POWER) 2305EO34 OH CKT MAP 2305E040 UG CKT MAP 2305E034 CIRCUIT NO PRE -11 FOREMAN2 MAPPING i JOINT FACILITIES ARRANGEMENTS UTILITIES CONTACT PHONE# SOUND A, rD V ENERGY DESIGNED BY Potelco, Inc. PRE -11 SUNSET HWY 2017 CRP CABLE REMEDIATION PROGRAM 2800 NE SUNSET BLVD., RENTON, WA 96056 INCIDENT MAOP N/A N/A Gas Order Elect Order N/A 101102076 SCALE PAGE AS NOTED 1/5 PAVED PARKING -- J ❑ ----- BP24 BP-25 ...... .................................... BORE 120' 318580 O'A J09 166620 NX ° BP - 1110 -10 L P# 0923059161 O '8-1 2 ' EDGE OF O I m PAVEMENT PAVED PARKING O BP -22 ' 2502 P# 0923059058 MATCHLINE "A" SEE ABOVE VAULT &EQUIPMENT TABLE CIRCUIT FEET REMOVED: 2,875' CIRCUIT FEET ADDED: 4,745' t/ r MATCHLINE "A" SEE BELOW EXISTING J -BOX BELOW GRADE PRIMARY KING N/A M N 0 .; VAULT SIZE & TYPE &SIZE BUSHINGS TRANSFORMER D NUMBERS - PLAT MAP N/A 2502 m I COVER EQUIPMENT IN VAULT N/A 101102076 P# 0923059058 O CKT MAP H 2305E040 U G CKT MAP 2305E034I CIRCUIT NO PRE -11 FOREMAN#2 J05 318496 LB DC (COMPANY ID) - J01A o HH 4'8"X7'X5' J -BOX BELOW GRADE JUNCTION BOX 50kVA TUT XFMR INSTALL NEW 575 NEW LU W/ 3-4 POS. J -BUS MATID: 7625900 9 3 120/240v EXISTING WIRE CREW TO INSTALL GRID NUMBERS 166701 J02A I L J -BOX BELOW GRADE J -BOX BELOW GRADE 5 INSTALL NEW 575 3 � 166713 318541 , BP -21 J08 SX ' 166633 ,......�..�.... W/ 3-4 POS. J -BUS MATID: 7625900 � VCL 5 p L WIRE CREW TO INSTALL GRID NUMBERS J01 v O EXISTING J -BOX BELOW GRADE W/ POS. U � REPLACE ELBOWS &CONDUCTORS o BP -2 ROW 105' 3-4 J -BUS EXISTING 9 - WIRE CREW TO INSTALL GRID NUMBERS J -BOX BELOW GRADE J -BOX BELOW GRADE EOP 60' PAVED PARKING -- J ❑ ----- BP24 BP-25 ...... .................................... BORE 120' 318580 O'A J09 166620 NX ° BP - 1110 -10 L P# 0923059161 O '8-1 2 ' EDGE OF O I m PAVEMENT PAVED PARKING O BP -22 ' 2502 P# 0923059058 MATCHLINE "A" SEE ABOVE VAULT &EQUIPMENT TABLE Standoff Bracket 15 Min Length 'Conduit Clamp �5-- Min i j Climbing Space uit Field Face; Road Face Quadrant ' Quadrant J04 318467 EXISTING J -BOX BELOW GRADE PRIMARY KING N/A SITE GRID VAULT SIZE & TYPE &SIZE BUSHINGS TRANSFORMER D NUMBERS - PLAT MAP N/A NUMBER COVER EQUIPMENT IN VAULT N/A 101102076 REMARKS REMARKS O CKT MAP H 2305E040 U G CKT MAP 2305E034I CIRCUIT NO PRE -11 FOREMAN#2 J05 318496 LB DC (COMPANY ID) - J01A 318468 HH 4'8"X7'X5' J -BOX BELOW GRADE JUNCTION BOX 50kVA TUT XFMR INSTALL NEW 575 NEW W/2-3' SQ DOORS MAT ID: 7663200 W/ 3-4 POS. J -BUS MATID: 7625900 9 3 120/240v EXISTING WIRE CREW TO INSTALL GRID NUMBERS 166701 J02A 318502 HH 4'8"X7'X5' J -BOX BELOW GRADE J -BOX BELOW GRADE INSTALL NEW 575 NEW 166713 W/ ADJ ANTI-SKID MAT ID: 9996162 W/ 3-4 POS. J -BUS MATID: 7625900 7 5 8 WIRE CREW TO INSTALL GRID NUMBERS J01 318521 EXISTING J -BOX BELOW GRADE W/ POS. JUNCTION BOX SokvATUT XFMR REPLACE ELBOWS &CONDUCTORS 166730 WIRE CREW TO INSTALL GRID NUMBERS JUNCTION BOX 3-4 J -BUS EXISTING 9 - WIRE CREW TO INSTALL GRID NUMBERS J -BOX BELOW GRADE J -BOX BELOW GRADE J02 318503 EXISTING W/ 2-3 & 1-4 POS. J -BUS 1 _ 8 REPLACE ELBOWS &CONDUCTORS 166714 REPLACE ELBOWS &CONDUCTORS JUNCTION BOX 50kVA TUT XFMR JUNCTION BOX 50kVATUT XFMR WIRE CREW TO INSTALL GRID NUMBERS WIRE CREW TO INSTALL GRID NUMBERS 120l240v EXISTING 120/240v EXISTING J -BOX BELOW GRADE J -BOX BELOW GRADE J03 318488 EXISTING W/ 3-4 POS. J -BUS 8 _ 8 REPLACE ELBOWS &CONDUCTORS 166687 REPLACE ELBOWS &CONDUCTORS JUNCTION BOX 37.5kVA TUT XFMR JUNCTION BOX 75kVATUT XFMR WIRE CREW TO INSTALL GRID NUMBERS WIRE CREW TO INSTALL GRID NUMBERS 120/240v EXISTING 120/240v EXISTING Standoff Bracket 15 Min Length 'Conduit Clamp �5-- Min i j Climbing Space uit Field Face; Road Face Quadrant ' Quadrant J04 318467 EXISTING J -BOX BELOW GRADE '! r , !r KING N/A ABANDON J04 PER PSE 166701 CHECKED BY JUNCTION BOX W/ 3-4 POS. J -BUS EXISTING 0 - PLAT MAP N/A STANDARDS 6775.1050 - � , FOREMAN #1 N/A 101102076 J -BOX BELOW GRADE O CKT MAP H 2305E040 U G CKT MAP 2305E034I CIRCUIT NO PRE -11 FOREMAN#2 J05 318496 EXISTING W/ 2-3 & 1-4 POS. J -BUS 8 - REPLACE ELBOWS &CONDUCTORS 166681 JUNCTION BOX 50kVA TUT XFMR WIRE CREW TO INSTALL GRID NUMBERS 120/240v EXISTING J -BOX BELOW GRADE J06 318501 EXISTING W/ 3-3 POS. J -BUS 8 _ REPLACE ELBOWS & CONDUCTORS 166661 JUNCTION BOX SokvATUT XFMR WIRE CREW TO INSTALL GRID NUMBERS 120/240v EXISTING J -BOX BELOW GRADE J07 318515 EXISTING wi 3-3 Pos. J -Bus 8 - REPLACE ELBOWS &CONDUCTORS 166647 JUNCTION BOX 50kVATUT XFMR WIRE CREW TO INSTALL GRID NUMBERS 120/240v EXISTING J -BOX BELOW GRADE J08 318541 EXISTING w/ 2-3 & 1-4 Pos. J -Bus 8 - REPLACE ELBOWS &CONDUCTORS 166633 JUNCTION BOX 75kVATUT XFMR WIRE CREW TO INSTALL GRID NUMBERS 120/240v EXISTING ! J -BOX BELOW GRADE I J09 318580 EXISTING wi 2-3 & 1-4 Pos. J -Bus 5 _ REPLACE ELBOWS &CONDUCTORS 166650 JUNCTION BOX 25kVA TUT XFMR WIRE CREW TO INSTALL GRID NUMBERS 120l240v EXISTING Vol 318466 EXISTING 45kVA PM XFMR REPLACE ELBOWS & CONDUCT -ORS 166700 VAULT 277/480v EXISTING 3 - WIRE CREW TO INSTALL GRID NUMBERS TOTALS:j 74 8 ROW 70' U . g 3 / % �° it ,,,a EOP 30' 40T / �. X1502 21 3 0 0 % �,,✓ .� � /f �/ r/ r �.a ;r' � 2,490 lbs �1 P01 318538 o% �;I 166721 91 °Ty \ 2800' Q % o; iA 0�' r1 �r � �r 318534-166740 � 4,750 lbs � e!����,r,�y�,s,,Kriri:,��;�,r,,r„ ",,i i [,j" t i 7E1 'A 120/��k� i 4-01, TO VIEW 2 11 / r BOA � / \rim:, 79° / 4 I 611 41 '' 1313❑ 1313❑ r „ 7 -0�� 0130 000 ! Crushed 5'4" ❑00 ❑❑❑ I / r 3 " , `.; ..1 R 71 �' 4'-8" "N 000 000 I% Rock Ulrectlon of Venlcular Traffic i X01 BP -2 ; . ROW 65 6� sr ham/ EOP 30' SID VIEW BP -3 2801 CONDUIT RISER REPLACEMENT 1 � 086 / ° ', \ / O Excavation - 19-1/2 cubic yards AlBP 5VAULT & EXCAVATION DETAIL J01A, J02A BP- e0` ��7 Not to scale 60P5.1030 `LO ` 4v / 6 J 01 318 21 °Ty rJP �,o \ 1 166730 �L `� �"y'' 1 // REPLACE \� ��FOJ 3 Vent Grate 3118517-16663991\1: O ` Vent Door / COVER ' 4' x 6' 8" X`., BP -4 /4-8"6'-0" x3' Sq Door \\2 i/ BP -19 �rw � � .,."/ / ROW 100' P02 318519, r , e / 166739 �a o 65T I 6" BP -18 ' \ ,• �-..._.._.. i X1504 � 318515 EOP 60' .. J07166647 ;' �� �O 2725 I OO 07 BP -7 318508-1 r 166696 __ 2 P03 / � 3185 ,,,,, p OPEN TRENCH 30' _......... 2 0 -1040T / J02 318503 RX 9997158 506 Cover Grate Vent and Anti-skid Doors BP X1503 166714 ' O.p� ' �� �� �� �� 0 318502 SAFEWAY REPLACEMENT COVER X4'8" X 6`) @ J01 / 166713 u'� R` o ROW 70 / \ BP -8 / NEW 575 965 EOP 40' J -BOX CONSTRUCTION NO ES a I� oI M ' N W TOP VIEW :.DETAIL @ P01, PO2 & P03 NOT TO SCALE OPEN TRENCH 30' Pol J06 318501 RX BP 11 166661 � � a tiFs� ✓ �� 318496 BP -17 Q ROW 100 J05 RX / B� �EOP 60' 166681 Lp BP -1 PL J\0 INTERCEPT & BP -15 BP -14 PVED) RETRAIN CABLES gUNSET BwD (P BP -9 / 20458-460 FROM i NE V03 TO J02A , BORE r120 / P a BP -13 PL 7 PX 318488 J03 ` 2 960 I 166687 O ❑ ` 00 1 QX 1667318 4 88 V03 m 2 I TOP VIEW Cables should enter the vault so that all of the cables will la in the same direction. Y J- BOX CABLE ENTRY DETAIL Not to scale o I SITE PLAN SCALE: 1:50 -CUT OFF & CAP OLD CABLES AT T P OF RISER -ATTACH OLD CABLE # TO CABLE TUB -REMOVE OLD C/O & TERM O -INST �OLB C/O TERM F:40T STD 604 .1000 (TS3C1F) -� -INST 1-4" RISER ON STAND-OFF BR S STD 6042.1000 (RIS4CSS) ON -INST SW# X1502 O P02 00 -CUT OFF & CAP OLD CABLES AT TOP OF RISER -ATTACH OLD CABLE # TO CABLE STUB -REMOVE OLD C/O & TERM -INST 30 LI C/O TERM F:65T STD 604-3.1000 (TSU3LIF) -INST 1-4" RISER ON STAND-OFF BRKTS STD 6042.1000 (RIS4CSS) -INST SW# X1504 P03 -CUT OFF & CAP OLD CABLES AT T P OF RISER -ATTACH OLD CABLE # TO CABLE STUB -REMOVE OLD C/O & TERM -INST 30 LB C/O TERM F:40T STD 604:3.1000 (TSU3CIF) I r,�� ` -INST 1-4" RISER ON STAND-OFF BRKIS STD 6042.1000 (RIS4CSS) TO -INST $W# X1503 I Zm r k ,F FOREMAN NOTE: 2621 REAL ESTATE/EASEMENT PERMIT �o P POTHOLING IS REQUIRED PRIOR TO DRILLING AND THE REQ- CITY OF RENTON l Z_ BORE PROFILE SHALL BE PREPARED ON SITE AND � 3 FUNCTION CONTACT PHONE NO DATE t a PROVIDED TO THE INSPECTOR FOR APPROVAL. ! 2 PROJECT MGR C. YLENNI 253-720-9700 09-27-17 I 1 ' I 1 TI�� i; • - New conduit shall be at 36 minimum depth to the top and Maintain 1 ENGR -POWER C. TOBIN 253-548-4516 09-20-17 ROW 70' a minimum 1 -foot vertical clearance between outer surface of existing REV# DATE BY DESCRIPTION ENGR - GAS N/A N/A N/A P ,f =0P 40' structure and minimum 5 -foot horizontal separation of existing COUNTY Emer Sect Gas Wk Ctr POV�/ER WK CTR DRAWN BY F. SHANK 253-234-6114 09-20-17 -- - .... -- I ' INTERCEPT 89 RETRAIN CABLES AFF049-051 FROM VACANT LOT J10 TO J01A � P# 7227500635 500635 BP -12 p.,�.. hb VACANT LOT 104 structure. Call (300) 424-5555 Utility Notification Center 24/7 before beginning any excavation prevents damage to underground facilities, service interruptions & bodil,injuiti . '! r , !r KING N/A N/A OSEPRE CHECKED BY PRE -11 SUNSET HWY 2017 CR 1/4 SEC NW -9-23-5 OP MAP N/A PLAT MAP N/A APPROVED BY - � , FOREMAN #1 N/A 101102076 U-MAPNO (POWER) ) 2305E034 O CKT MAP H 2305E040 U G CKT MAP 2305E034I CIRCUIT NO PRE -11 FOREMAN#2 MAPPING './ it •/ _i ,r ,/ r / �. / /i„O;v Y/ �- 0 6J{JINT FACILITIES ARRANGEMENTS UTILITIES 166701 - _--�---- 318468 01 � I MAPS &RECORDS NOTE: 166701 ' V01 IS LOCATED _ @ 927 HARRINGTON AVE NEW 575 INTERCEPT & I J - BOX RETRAIN CABLES aw BP -26 ' 927 318466 AFF049-051 FROM -^ P# 7227500625 QX V01 4 J01A TO J10 .. 166700 CONTACT PHONE# PIJGEl. INCIDENT MAOP PRE -11 SUNSET HWY 2017 CR N/A N/A SOUND Gas Order Elect Order CABLE REMEDIATION PROGRAM ENERGY N/A 101102076 2800 NE SUNSET BLVD., RENTON, WA 98056 DESIGNED BY Poteico, Inc. SCALE PAGE � AS NOTED 2/5 EH0071 - A0 AFF049 - AO 1-4" - L \� LINK -A0 1-4"-L I 20458 - AO vo3 EXISTING v 1-4" - L ' 20459 - 130 TO REMAIN @ J01A EH0035 - AO 20460 - CO )��/ 14 - L EH0036 - B0 EXISTING Q J❑ 1-411 - L EH0037 - CO x T 502 45° 2t� P01 INTERCEPT Jog EH0068 - AO BO Poi 45° EH0069 - BO - 1 409 @ J02A o EH0070 - CO so° EH0036 Q 2ct� EH0063 N F 0)), J 200 X 2 w - 1 389 506 r 245 40T EH0033 EH0034 O J J02A �o 9 1-4" - L 2-4" - L ' EH0067 - A0 EH0064 - A0 Jos 45° EH0065 - BO EH0061 - 130 EH0062 - CO 14" - L ' E H 0057 - AO EH0058 - BO EH0059 - CO AG1225 - AO AG 1226 - 130 AG 1227 - CO EXISTING TO REMAIN EH0048 - AO 2-4 - L 90° E02 14" - L ' 35T EH0032 - AO K1504 EH0033 - 130 EH0034 - CO 42148 - AO 42149-80 42150 - CO EXISTING TO REMAIN AFF049 - AO 1-4" - L \� 90° 1-4"-L I 20458 - AO vo3 / v EH0066 - CO 20459 - 130 REMARKS @ J01A EH0044 - CO 20460 - CO )��/ 14 - L O EXISTING BENDS 45 22 EH0045 - AO EH0038 - AO TO REMAIN DESIGN ACTUAL LENGTH LENGTH (ft) (ft) 2t� P01 INTERCEPT 4 EH0039 - BO RETRAIN Jot N� - 1 409 @ J02A Poi EH0040 - CO EH0036 EH0037 2ct� EH0063 - AO J 200 X 2 - - - 1 389 506 1/0 AL JKT 245 40T EH0033 EH0034 O J J02A �o 1 14" L�o X1503 2 1-2" - L - 2 - 1 293 �" Al 1/0 AL JKT REI v EH0039 - J02A J02 EH0041 -A0 1 5 ��� - Co - 20 20 1/0 AL JKT EH0054 - AO 2 - J02A J03 4 1 EH0053 - A0 1 EH0055 - B0 �� J02 420 �J �w EH0043 VO4 J07 EH0052 - AO EH0056 - CO 2� O X 22° - - - 413 527 1/0 AL JKT 420 EH0045 EH0046 318502 0 J03 J03 - - 90° X - 22° 166713 - - 4414 - CO 1/0 AL JKT 25 EH0048 - - C NEW 575 4 EXISTINGJ-Box 120 X 1 - - - 203 22' 1/0 AL JKT 135 TO REMAIN 1-411 - L Job J ❑ J05 22° 4 1 270 E 006 - AO 1 - - Jos 321 , 315 EH0054 EH0055 EH0061 - 130 EH0062 - CO 14" - L ' E H 0057 - AO EH0058 - BO EH0059 - CO AG1225 - AO AG 1226 - 130 AG 1227 - CO EXISTING TO REMAIN EH0048 - AO 2-4 - L 90° E02 14" - L ' 35T EH0032 - AO K1504 EH0033 - 130 EH0034 - CO 42148 - AO 42149-80 42150 - CO EXISTING TO REMAIN 1-4 - L EH0049 - AO EH00 0 - 13 5 0 EH0051 - CO PRIMARY CABLE & CONDUIT DIAGRAM NOT TO SCALE PRIMARY CABLE &CONDUIT TABLE 318468 01 166701 NEW 575 AFF049 - AO 1-4" - L \� 90° AFF051 - CO EXISTING EH0042 - AO 20458 - AO vo3 INTERCEPT EH0043 - 130 20459 - 130 REMARKS @ J01A EH0044 - CO 20460 - CO ❑ J03 14 - L ACTUAL TYPE LENGTH D6120 POLY SCH 80 (ft) EXISTING BENDS 45 22 EH0045 - AO PULL REV (lbs) TO REMAIN DESIGN ACTUAL LENGTH LENGTH (ft) (ft) EH0046 - BO P01 INTERCEPT 4 EH0047 - COC0 230 RETRAIN m - - - 1 409 @ J02A m 275 EH0035 EH0036 EH0037 P02 J01 4 J 200 X 2 1-4 - L EH0049 - AO EH00 0 - 13 5 0 EH0051 - CO PRIMARY CABLE & CONDUIT DIAGRAM NOT TO SCALE PRIMARY CABLE &CONDUIT TABLE 318468 01 166701 NEW 575 AFF049 - AO J -Box AFF050 - 130 90° AFF051 - CO EXISTING FUNCTION CONTACT PHONE NO DATE TO REMAIN INTERCEPT PROJECT MGR C. YLENNI 253-720-9700 09 27 17 & RETRAIN REMARKS @ J01A LOCATION REAL ESTATE/EASEMENT PERMIT REQ- CITY OF RENTON 3 CONDUIT FUNCTION CONTACT PHONE NO DATE 2 PROJECT MGR C. YLENNI 253-720-9700 09 27 17 PRIMARY CABLE REMARKS FROM TO SIZE (In) QTY DESIGN LENGTH (ft) ACTUAL TYPE LENGTH D6120 POLY SCH 80 (ft) 90 BENDS 45 22 PULL I 11 (lbs) PULL REV (lbs) CABLE SIZE DESIGN ACTUAL LENGTH LENGTH (ft) (ft) CABLE NUMBERS PLEASE RECORD FOREMAN - COMPLETE A B C MANUFACTURER YEAR P01 J01 4 1 230 X 2 - - - 1 409 534 1/0 AL JKT 275 EH0035 EH0036 EH0037 P02 J01 4 1 200 X 2 - - - 1 389 506 1/0 AL JKT 245 EH0032 EH0033 EH0034 J01 J02A 4 1 210 X - - 2 - 1 293 277 1/0 AL JKT 230 EH0038 EH0039 EH0040 J02A J02 2 1 5 X - - - - 20 20 1/0 AL JKT 25 EH0041 - - J02A J03 4 1 400 X 1 - 2 - 409 364 1/0 AL JKT 420 EH0042 EH0043 EH0043 J03 J01AI 4 1 400 X 2 - - - 413 527 1/0 AL JKT 420 EH0045 EH0046 EH0047 J03 J03 - - - X - - - - - - 1/0 AL JKT 25 EH0048 - - J01A V01 4 1 120 X 1 - - - 203 195 1/0 AL JKT 135 EH0049 EH0050 EH0051 J05 P03 4 1 270 X 1 - - - 431 321 1/0 AL JKT 315 EH0054 EH0055 EH0056 J05 J05 - - - X - - - - - - 1/0 AL JKT 25 EH0052 - - J05 J06 4 1 180 X - - - - 170 170 1/0 AL JKT 200 EH0057 EH0058 EH0059 J06 J06 - - - X - - - - - - 1/0 AL JKT 25 EH0053 - - J06 J07 4 1 230 X - - - - 192 192 1/0 AL JKT 250 EH0060 EH0061 EH0062 J07 J07 - - - X - - - - - - 1/0 AL JKT 25 EH0063 - - J07 J08 4 1 1 250 X - - - - 201 201 1/0 AL JKT 270 EH0064 EH0065 EH0066 J08 J08 - - - X - - - - - - 1/0 AL JKT 25 EH0067 - - J08 J09 4 1 650 X - 3 - - 555 547 1 1/0 AL JKT 670 EH0068 EH0069 EH0070 J09 1 J09 - - - X - - - - - - 1/0 AL JKT 25 EH0071 - - TOTAL 4" 4,745' 14 3 6 - TOTAL 30 5,420' TOTAL 2" 5 - - - - TOTAL 10 25' QTS OF GLUE I 14.2 I GALS OF LUBE I 29.7 CIVIL CREW NOTE: ALL 2" - 900 BENDS MIN 48" RADIUS SCH-80 PVC ALL 2" - 450 BENDS SCH-80 PVC ALL 4" - 900 BENDS MIN 60" RADIUS SCH-80 PVC ALL 4" - 450 BENDS SCH-80 PVC - ALL CONDUITS SHALL BE CAPPED AT EACH END UNTIL CABLE IS INTALLED Crew to provide all property owner's that are impacted by project prior notice and make an effort to work with property owner's to maintain their access to their property, as well as, reduce the impact of our work on their use of their property. FOREMAN NOTE: Call (800) 424-555 Utility Notification Center 24/7 before beginning any excavation prevents damage to underground facilities, service interruptions &� bodily injury. //y% iiry/ , �, '�." i� „,.✓.,l fir /i„ D//F ✓ „ h _. / /; _ / ry/i..,,.. //. //���,is,' i ,/r CIVIL CREW FOREMAN NOTC: Maintain on site, in good condition, a complete file of all work drawings. These drawings shall be available a all times to a Puget Sound Energy representative. Corrections and changes ma a during the job shall be recorded continuously on these drawings. Mark all underground utilities encountered during construction on these drawings. Furnish Puget Sound Energy a complete set of as -built prints (foreman's copies) at the end of the job. WIRE CREW FOREMAN NOTE: ALL FAULT INDICATORS WILL BE MAINTAINED IN THEIR CURRENT LOCATION ON 1/0 CABLES AFTER NBW CABLE IS INSTALLED UNLESS OTHERWISE SPECIFIED. PLEASE RED -MARK ALL FAULT INDICATORS ON "CABLE DIAGRAM" FOR MAPPING. I REAL ESTATE/EASEMENT PERMIT REQ- CITY OF RENTON 3 FUNCTION CONTACT PHONE NO DATE 2 PROJECT MGR C. YLENNI 253-720-9700 09 27 17 1 ENGR - POWER C. TOBIN 253-548-4516 09-20-17 REV# DATE BY DESCRIPTION ENGR - GAS N/A N/A N/A COUNTY KING Emer Sect Gas Wk Ctr N/A N/A POWER WK CTR QSEPRE DRAWN BY F. SHANK 253-234-6114 09-20-17 CHECKED BY �- 1/4 SEC NW -9-23-5 OP MAP N/A PLAT MAP N/A APPROVED BY ° FOREMAN #1 U -MAP NO (POWER) 2305EO34 OH CKT MAP 2305EQ40 UG CKT IVAP 2305E 34 CIRCUIT NO PRE -11 FOREMAN #2 IMAPPING JOINT FACILITIES ARRANGEMENTS UTILITIES CONTACT PHONE# PUGEr PRE -11 SOUC ENERGY 2800 DESIGNED BY Potelco, Inc. INCIDENT MAOP SUNSET HWY 2017 CRR N/A N/A Elect Order .ND BLE REMEDIATION PROGRAM GaNOrder 101102076 NE SUNSET BLVD., RENTON, WA 98056 SCALE PAGE I AS NOTED 3/5 I O / REMOVE / REPLACED CABLE 0018113 PERMIT CITY OF RENTON CABLE NE 10TH ST LOCATIONS CABLE FUNCTION EXISTING CABLE 5 RUNS, 500 CABLE CABLE EZ B\ -VD NO. KCNi FROM TO ovo EST B020459 318488 MFG. DATE REPLACED? ENGR - POWER 18102 03 TLXA023201 J01 BY DESCRIPTION 260 CO20460 166713 5J AOUNK COUNTY KING 18103 10511652 P01 o MAPS & RECORDS NOTE: f260 09-20-17 CHECKED BY O// it J09 IS A COMBO J-BOX/TUT 80324,0 8032411 18104 10511662 J ❑ J 0032412 COAG1227 FOREMAN #1 J09 318580 NX YES OH CKT MAP 2305EO40 18105 10511680 166620 W AOUN0 IMAPPING Z YES FACILITIES ARRANGEMENTS NE 9TH PLAO18114 10511690 ui ¢ J01 UTILITIES 180 - Z o AO,s4,6 21 z 318575-166698 0018116 J01 BO,a41s 180 300kVA 1201208v PHONE# YES 18108 10511714 J01 J02 SUNSET HWY 2017 CRP i LE REMEDIATION PROGRAM I SUNSET BLVD., RENTON, WA 98056 255 INCIDENT N/A Gas Order N/A SCALE AS NOTED MAOP N/A Elect Order 101102076 PAGE 4/5 YES 18109 10511726 101 J02 255 YES 5J - 18110 z J01 J02 CO25923 2� YES 318571-166766 4 318570-166767 Z Fj, 10511747 J02 J03 112.6kVA 1201208v d 25kVA 1201240v �o A016889 YES B016890 10511758 J02 �4�1 C016891 YES 18113 10511768 J02 J03 NF 10 YES ST 18114 10511784 J03 J04 1360 YES P01 318538 \ B013642 10511794 J03 J04 166721 360 G(EN 4,00D IFN I 40T 18116 F - X1502 360 318536-166771 NO A018102 J� AOEHE500 AOUNK 8018103 �� - BOEHE501I 25kVA 1201240v1 �AOAGG2 C018104 �� COEHE502 BHABH66, J ❑ 318536-166710 L__ BOAGG258 �� J COAGGI20AGG2 ��� 3'.8 34-166740 ✓. BOAGG260 ; BOAGG26 OAGG2 3 45kVA 1201208v C _ p 318541 318535-166709 4 p JOU SX / `✓�_ A042151 B018674 166633 s B042, 52 318544-166723 j X18533-166739 0042153 CII18675 J sG 3■60kVA 1201208v A042148 '..8042149 = 3 E Go 54 C042150 m 76kVA w?240v A018129 2 z �� 318529-'66767 T U G - 112.6kVA 1201208v m B018130 rm 0018131 X22 m �J01 318521 J o 166730 A018105 J= m J07 318515 B018106 �'�� m 166647 C018107 Ao AHUNK 318519 �o P02166739 A018108 65T 318510-166637 109 B018 167kVA 1201240v A018126 X 1504 [3��G�s B018127 01812° 0018110 F� C018128 C018122 C04414 ��o J02 318503 PX - N�c�oTysT 318510 AOUNK J ❑ AOUNK 166714 V04166637 ULX o A018123 318496 �o ' 6018124 J05 166681 RX J�S���� J06 318501 RX C018125 ��`' A018111 A023204 166661 AHUN 6018112 6023205 0023206 318494-166774 3%37.5kVA 120/208v 318572-166803 J AHUNK BOUNK COUNK A013906 6013907 C013908 3'&H --'H792 1=76kVA 120V240v 1x10MA 1201240v Open -Wye.,Ope n -Delta AHA3=44^ W z IDLE Q 0 Z Y LL Y A04338 ;B0433940 318506-166795 225kVA 120/208v 318467 J04 166701 3184 - A032855 J J AIIA==037 6032856 a AOAFF049 BOA =F038 LCA,=Fa39 0032857 BOAFF050 V01>18466 C0AFF051 1 66700 QX EXISTING 318458-166729 750kVA 1201208V v ,i 318445-166691 100kVA 1201240v 0 -,.. AOA.=F040 J A04207 B-IIAF-041 LL] COAF=042 z o Lu t 318443-166691 ¢ 100kVA 1201240v Z 0 0 x 318431-166728 7 760kVA 1201208v AOAFF043 AOA::=F1046 BOAFF044 30AFF047 COAFF045 COAFF048 318424-166730 NF 97 Sr SCALE: 1:100 NE 9TH ST 'ABANDONED / REMOVE / REPLACED CABLE 0018113 PERMIT CITY OF RENTON CABLE NE 10TH ST LOCATIONS CABLE FUNCTION EXISTING CABLE EXISTING CABLE CABLE EZ B\ -VD NO. A020458 FROM TO leslo EST B020459 318488 MFG. DATE REPLACED? ENGR - POWER 18102 03 TLXA023201 J01 BY DESCRIPTION 260 CO20460 166713 tL 8023203A0A%2 COUNTY KING 18103 10511652 P01 41 F. SHANK f260 09-20-17 CHECKED BY O// it YES EXISTING 18104 10511662 ❑ J j yfL COAG1227 FOREMAN #1 YES OH CKT MAP 2305EO40 18105 10511680 318478-166720 J01 AOUN0 IMAPPING 112.5kVA 1201208v YES FACILITIES ARRANGEMENTS NE 9TH PLAO18114 10511690 P02 J01 UTILITIES 180 J03 318488 PX 6018115 AO,s4,6 21 166687 0018116 J01 BO,a41s 180 PHONE# YES 18108 10511714 J01 J02 SUNSET HWY 2017 CRP i LE REMEDIATION PROGRAM I SUNSET BLVD., RENTON, WA 98056 255 INCIDENT N/A Gas Order N/A SCALE AS NOTED 318467 J04 166701 3184 - A032855 J J AIIA==037 6032856 a AOAFF049 BOA =F038 LCA,=Fa39 0032857 BOAFF050 V01>18466 C0AFF051 1 66700 QX EXISTING 318458-166729 750kVA 1201208V v ,i 318445-166691 100kVA 1201240v 0 -,.. AOA.=F040 J A04207 B-IIAF-041 LL] COAF=042 z o Lu t 318443-166691 ¢ 100kVA 1201240v Z 0 0 x 318431-166728 7 760kVA 1201208v AOAFF043 AOA::=F1046 BOAFF044 30AFF047 COAFF045 COAFF048 318424-166730 NF 97 Sr SCALE: 1:100 NE 9TH ST 'ABANDONED / REMOVE / REPLACED CABLE I SCHEDULE PERMIT CITY OF RENTON CABLE SAP LOCATIONS CABLE FUNCTION EXISTING CABLE EXISTING CABLE CABLE NO. EQUIP FROM TO NF) EST MFG. NAME MFG. DATE REPLACED? ENGR - POWER 18102 10511642 P01 J01 BY DESCRIPTION 260 ENGR - GAS N/A N/A YES COUNTY KING 18103 10511652 P01 41 F. SHANK f260 09-20-17 CHECKED BY O// it YES OP MAP N/A 18104 10511662 P01 101 j yfL 1260 FOREMAN #1 YES OH CKT MAP 2305EO40 18105 10511680 P02 J01 11bu IMAPPING YES FACILITIES ARRANGEMENTS 18106 10511690 P02 J01 UTILITIES 180 i YES 18107 10511704 P02 J01 180 PHONE# YES 18108 10511714 J01 J02 SUNSET HWY 2017 CRP i LE REMEDIATION PROGRAM I SUNSET BLVD., RENTON, WA 98056 255 INCIDENT N/A Gas Order N/A SCALE AS NOTED MAOP N/A Elect Order 101102076 PAGE 4/5 YES 18109 10511726 101 J02 255 YES 18110 10511737 J01 J02 255 YES 18111 10511747 J02 J03 340 YES 18112 10511758 J02 J03 1340 YES 18113 10511768 J02 J03 340 YES 18114 10511784 J03 J04 1360 YES 18115 10511794 J03 J04 360 I YES 18116 10511804 J03 J04 360 YES 18120 10511847 J05 P03 315 YES 18121 10511862 J05 P03 315 YES 18122 10511877 J05 P03 315 YES 18123 10511888 J05 J06 1210 YES 18124 10511898 J05 J06 210 YES 18125 10511910 J05 J06 210 YES 18126 10511925 J06 J07 180 YES 18127 10511936 J06 J07 180 YES 18128 10511950 J06 J07 180 YES 18129 10511960 J07 J08 265 YES 18130 10511969 J07 J08 265 YES 18131 10511979 J07 J08 265 YES 16889 14098385 J08 49 265 YES 16890 14098386 J08 49 1265 YES 16891 UNK J08 49 265 YES 32855 10527517 J04 Vol 70 YES 32856 10527527 J04 Vol 70 YES 32857 10527537 J04 Vol 70 YES UNK UNK J02 J02 25 YES UNK UNK J03 J03 25 YES UNK UNK J05 J05 25 YES UNK UNK J06 J06 25 YES UNK UNK J07 J07 25 YES UNK UNK J08 J08 25 YES UNK UNK J09 J09 25 YES TOTAL CIRCUIT FEET ,875- I I j i O O IV 11 O REAL ESTATE/EASEMENT REQ- PERMIT CITY OF RENTON 3 FUNCTION CONTACT PHONE NO DATE 2 PROJECT MGR C. YLENNI 253-720-9700 09-27-17 1 ENGR - POWER C. TOBIN 253-548-4516 09-20-17 REV# DATE BY DESCRIPTION ENGR - GAS N/A N/A N/A COUNTY KING Emer Sect Gas Wk Ctr N/A N/A PO ER WK CTR QSEPRE DRAWN BY F. SHANK 253-234-6114 09-20-17 CHECKED BY O// it 1/4 SEC NW -9-23-5 OP MAP N/A PL T MAP N/A APPROVED BY j yfL FOREMAN #1 U -MAP NO (POWER) 2305EO34 OH CKT MAP 2305EO40 JUG CKTM (P 2305E03 CIRCUIT NO PRE -11 FOREMAN #2 IMAPPING ,JOINT FACILITIES ARRANGEMENTS UTILITIES i CONTACT PHONE# PUG S PRE -11 SOUNDCABLE CA ENERGY 2800 NE DESIGNED BY Potelco, Inc. SUNSET HWY 2017 CRP i LE REMEDIATION PROGRAM I SUNSET BLVD., RENTON, WA 98056 INCIDENT N/A Gas Order N/A SCALE AS NOTED MAOP N/A Elect Order 101102076 PAGE 4/5 MATCHLINE "B" SEE BELOW � BP -22 V250 fL P# 0923059058 O co N o 2502 m a I I P# 0923059058 L I P� ir P� � a L SX 31854 J08 2 166633 BP121p! � P� \ G2 � 'Q► cn� \ v a t,P-20 11 11 / \A riJ ff 10 Jai; 39 MATCHLINE B ' y� �, ROW 65' v1o5'00\� SEE ABOVE' ag \ EOP30' BORE PIT DETAIL o BORE PT \ o� �/ o�� B . 3, \ 2801 NOT TO SCALE EOP 60 2 \moo �� \ ® POT HOLE *NOTE:BORE PITS, TRENCH HATCHING & POTHOLES ARE NOT SHOWN TO SCALE FOR VISUAL PURPOSE'S. PLEASE SEE BORE \ \ /0 \� \ PIT DETAIL F R TYP. BORE PIT & TRENCH DIMENSIONS. Z �µ l0 1 all,,' B/-6 318 2101 166730 \ f \ \ Cr t provide 1 r own that are O Crew o ro eal i w property owner's impacted by N r \ \ p � l� p Y p ,,,,� � � `, � / REPLACE ESTIMATED QUANTITIES OF GRADING AND TESC WORK ITEM DESCRIPTION APPROX QUANTITY CLEAR AND GRADE 1) NON -USABLE CUT 99.2 CY 2) REQUIRED GRAVEL FILL 86.9 CY 11 SURFACE IMPROVEMENT AND RESTORATION 1) FOLLOWING FINAL GRADING ACTIVITY, SOD SHALL BE PLACED ON EXPOSED SOIL TO PROVIDE PERMANENT AND IMMEDIATE EROSION PROTECTION. 2) TEMPORARY COLD MIX SHALL BE PLACED ON EXPOSED GRAVEL IN HARD SURFACE FOR IMMEDIATE EROSION PROTECTION AND HOT MIX ASPHALT WILL BE APPLIED AT FINAL RESTORATION TO PROVIDE PERMANENT EROSION PROTECTION. \ ,P� ROW 70' � 2800 P 30' 40T B X1502 \ �' \, \ P01 318538 \ 166721 a. > ✓ �'� �` \ ' % ~ fIl / 318534-166740 45kVA 1201208v 318535-166709 fi BP -2 Will maintain 36" Min. depth while directional drilling 24" Typical VOLUME OF DISTURBANCE TABLE CITY OF RENTON NUM DESC SIZE (ft) REM YD (APPX) GRAVEL FILL YD (APPX) TYPE OF SURFACE REMARKS BP -1 BORE PIT 2 X 14 3.1 3.1 SIDEWALK BP -2 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -3 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -4 BORE PIT 2 X 14 3.1 3.1 SIDEWALK BP -5 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -6 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -7 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -8 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -9 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -10 BORE PIT 2 X 8 1.8 1.8 ASPHALT BP -11 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -12 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -13 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -14 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -15 BORE PIT 2 X 14 3.1 3.1 SIDEWALK BP -16 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -17 BORE PIT 2 X 14 3.1 3.1 SIDEWALK BP -18 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -19 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -20 BORE PIT 2 X 8 1.8 1.8 SIDEWALK BP -21 BORE PIT 2 X 14 3.1 3.1 GRAVEL BP -22 BORE PIT 2 X 8 1.8 1.8 GRAVEL BP -23 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -24 BORE PIT 2 X 14 3.1 3.1 ASPHALT BP -25 BORE PIT 2 X 8 1.8 1.8 ASPHALT J02A-NORTH OPEN TRENCH 1X3X30 3.3 3.3 GRAVEL/SIDEWALK J02A-SOUTH OPEN TRENCH 1X3X30 3.3 3.3 GRAVEL/SIDEWALK J01A VAULT EXCAVATION 11X9X5.5 14.5 8.3 GRAVEL/SIDEWALK J02A VAULT EXCAVATION 11X9X5.5 14.5 8.3 GRAVEL TOTALS 96.1 83.8 ESTIMATED QUANTITIES OF GRADING AND TESC WORK ITEM DESCRIPTION APPROX QUANTITY CLEAR AND GRADE 1) NON -USABLE CUT 99.2 CY 2) REQUIRED GRAVEL FILL 86.9 CY 11 SURFACE IMPROVEMENT AND RESTORATION 1) FOLLOWING FINAL GRADING ACTIVITY, SOD SHALL BE PLACED ON EXPOSED SOIL TO PROVIDE PERMANENT AND IMMEDIATE EROSION PROTECTION. 2) TEMPORARY COLD MIX SHALL BE PLACED ON EXPOSED GRAVEL IN HARD SURFACE FOR IMMEDIATE EROSION PROTECTION AND HOT MIX ASPHALT WILL BE APPLIED AT FINAL RESTORATION TO PROVIDE PERMANENT EROSION PROTECTION. \ ,P� ROW 70' � 2800 P 30' 40T B X1502 \ �' \, \ P01 318538 \ 166721 a. > ✓ �'� �` \ ' % ~ fIl / 318534-166740 45kVA 1201208v 318535-166709 fi BP -2 Will maintain 36" Min. depth while directional drilling 24" Typical 2621 CITY OF RENTON (6" Min) Final Grade DATE C. YLENNI M1 , " y I P1,I , a I 3 2 1 REAL ESTATE/E) REQ- 09-20-17 FUNCTION £ PROJECT MGR F. SHANK i ., IE¢ G G G 36" Min ........... Depth r ROW 70' J ENGR -GAS P SD ' £ EXISTING POWER EXISTING SEWER EXISTING STORM DRAIN ec P# 7227500635 i 7€ ' ) µ " ! P EOP 40' NTERCEPT & \RETRAIN CABLES ' AFF049-051 FROM \ J10 TO J01A OREV# COUNTY Emer Sect Gas Wk Ctr POWER KING N/A N/A 1/4 SEC OP MAP PLA NW -9-23-5 N/A U -MAP NO (POWER) OH CKT MAPUG CKT MAP £ I DRAWN BY TYPICAL BORE C VER MAP N/A APPROVED BY FOREMAN #1 ;PLAN VIEW 24' Typical MAPPING ( Min) Bore Pits will be excavated EXISTING TELEPHONE EXISTING FIBER OPTIC "' I I using Vac Truck method. Final Grade { -4�.....� J 1 0 I 2305EO34 2305EO40 2305EO34 JOINT UTILITIES CONTACT PRE -11 FACILITIES ARRANGEMENTS 36" Min BORE PIT POT HOLE I Backfill w/I NEW 575 J -Box Cover �\ crushed rock 5/8minus , Backfill shall not damage a the conduit. PHONE# PUGET PRE -11 SUNSET HWY 2017 C ._::; ... I - 927 aN P# 7227500625 0.y -N QX 318466 166700 V01 B P-26 4 INTERCEPT & RETRAIN CABLES AFF049-051 FROM J01A TO J10 i REMEDIATION PROGRAM SUNSET BLVD., RENTON, WA 98056 Electric Service Cable in Conduit 4" POLY A an \ \ \d °-., d b project prior notice and make an effort to work with I All OV .pro ert owner's to maintain their access to their property, � x P-4 \ 318519\ as well as reduce the impact of our work on their use of \ 3P-19 moi' their , -`` , / ROW 100 39 1� `eir property." PO2 1667 \ w , <, / F 0 BP 18 -.. P 60'X150 a J07 318515 s� \ / b5 ' ° f S - s� �� yF,' o �� • v EOEXPOSED SOIL PROTECTION NOTES: \ 166647 ,.\ \ >'Qj / f.' ---_ SD b P��� d SD -- SII _---._. sD --- -_ BO AREAS WHERE THE GRADING ACTIVITIES,RE PIT EXCAVATION OR UTILITY POT HOLING, WILL BE TEMPORARILY STABILIZED BY ONE OF THE FOLLOWING \ P03 318507 a 318510 �,� \ 0� / BP -7 METHODS WHICH ARE BASED ON PERIOD OF EXPOSED SOLS ARE LEFT VO4 ULX 'L�` \ %.880 �; 166696 �.; \ 2 166637 s , 2 \ TRENCH 30 D. ,,,,,,,,,,; , \ \ a OPEN T UNWORKE ❑ �8+ G'�s� c� �\� G X15o3 - OSE OILS ON SITE DURING CONSTRUCTION. . ____..... a� �`, BP 40T / 318503 RX . FEWA V d� _ 2�1��R� \` ,\ OC 6714 SA Y ALL SPOILS FROMEXCAVATIONWILL BE VAC EXCAVATED INTO THE TRUCK. 1 \ / 6 ROW 70 c' .k Vol, 166 111 A p i • A `\ 965 NEW 575 Q \ �6, \� \ \ J -Box EROSION &SEDIMENT ONTROL REQUIREMENTS J06 318501 RX ` ` BP -11 , �% ° ON TRENCH -- 30' EROSION &SEDIMENT CONTROLS ALL BE PER PSE STANDARD PRACTICE 166661 J \ r�, 0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL & ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS. �s A ��-� \ 4 Pi LOCAL JURISDICTIONS MAY HAVEADDITIONAL REQUIREMENTS INCLUDING �318499-161111,1301183, ;" \ s ( Q S NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES 41& L/ O BP- 16'� ROW 100' J05 318496 RX -'��/y5o �� \ Q &° 2725 ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION 166681 \ �ti \� STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE A EAS.) \`\ EOP 60 P _OP 40 ¢s P BP -15 BP -14 / F. e `E. \� _ _ �_ - �� % Q� �O� \ o INTERCEPT & ,P -� P 7 RETRAIN CABLESwo 180, q -- - P P cis \$ `� d� j 20458-460 FROM FOREMAN NOTE: as vo3 To Jo2A ----- ss �` / \ \ POTHOLING IS REQUIRED PRIOR TO DRILLING AND THE „< BORE PROFILE SHALL BE PREPARED ON SITE AND s d / �s �-_ __ NE S�NSE� B as B X56 PROVIDED TO THE INSPECTOR FOR APPROVAL. % �� as as - - us 0, a ��" P y� CIVIL SITE PLAN as -~_-- - as as S \ `` L a New conduit shall be at 36" minimum depth to the to and Maintain 01> SCALE: 1:50 `�;' ; Bo �� �o:. a �� p a minimum 1 -foot vertical clearance between outer surface of existing 'i '�� \ structure and minimum 5 -foot horizontal separation of existing \ a� a A� structure. i PX 318488 k 960 L Call (800) 424-5555 Utility Notification Center 24/7 before beginning any ' `� 2 �, excavation prevents damage to un er round facilities service interrupt ons & 166687 J03 co 'D+ Gam' 318488 V03P g g P LEGEND ❑ p \ QX 166713 o injury. o `` bodily t } ,a/ / i s, / -,, c� i `. � I ATH I ,., I ,, �, � � ;; , r ,✓,i �i . , / /, �, OSED BORE P �'� ,/ , , � �� ���,, - - - W - -PROP - - /'� T - W W RIGHT OF WAY04 STREET CENTER LINE EXISTING WATER 2621 CITY OF RENTON I I I DATE C. YLENNI M1 , " y I P1,I , a I 3 2 1 REAL ESTATE/E) REQ- 09-20-17 FUNCTION N/A PROJECT MGR F. SHANK ENGR-POWER G G G EXISTING GAS ........... r ROW 70' DATE BY DESCRIPTION ENGR -GAS P SD P $$ SD EXISTING POWER EXISTING SEWER EXISTING STORM DRAIN P# 7227500635 ' ) µ " ! P EOP 40' NTERCEPT & \RETRAIN CABLES ' AFF049-051 FROM \ J10 TO J01A OREV# COUNTY Emer Sect Gas Wk Ctr POWER KING N/A N/A 1/4 SEC OP MAP PLA NW -9-23-5 N/A U -MAP NO (POWER) OH CKT MAPUG CKT MAP WK CTR QSEPRE DRAWN BY CHECKED BY gib_\ MAP N/A APPROVED BY FOREMAN #1 CIRCUIT NO FOREMAN #2 MAPPING TEL FO EXISTING TELEPHONE EXISTING FIBER OPTIC "' I I VACANT LOT --b VACANT LOT 318467 J04 BP-12 166701 { -4�.....� J 1 0 I 2305EO34 2305EO40 2305EO34 JOINT UTILITIES CONTACT PRE -11 FACILITIES ARRANGEMENTS %- O BORE PIT POT HOLE I NEW 575 J -Box 318468 0l 166701 PHONE# PUGET PRE -11 SUNSET HWY 2017 C ._::; ... I - 927 aN P# 7227500625 0.y -N QX 318466 166700 V01 B P-26 4 INTERCEPT & RETRAIN CABLES AFF049-051 FROM J01A TO J10 SOUND CABLE p �/ ENE/CG! 2800 NE DESIGNED BY Potelco, Inc. REMEDIATION PROGRAM SUNSET BLVD., RENTON, WA 98056 O O O O ENT PERMIT Gas Order N/A Elect Order 101102076 CITY OF RENTON CONTACT PHONE NO DATE C. YLENNI 253-720-9700 09-27-17 C. TOBIN 253-548-4516 09-20-17 N/A N/A N/A F. SHANK 253-234-6114 09-20-17 INCIDENT N/A MAOP N/A Gas Order N/A Elect Order 101102076 CALE AS NOTED PAGE 5/5