Franchise Permit: MFP18003011
IVR Number: 18003011
Permit Informaon
Permit Name:Puget Sound Energy - Electric
Address/Locaon :06/06/2018Application Date:7224000580Parcel Number:332 PARK AVE N
Permit Type:07/05/2018Issue Date:Franchise
Permit Work Class:07/05/2019Expiration Date:Minor Utility
Job Number:101112247Franchise Type:Electric
Description:Remove 2 submersible transformers, install two padmount transformers, install two concrete secondary handholds,
re plumb and re route existing primary and secondary to new transformers and handholds. Pothole all existing
utilities. Restoration per City of Renton Standards.
Contacts
Name Address PhoneTypeBilling
ANISH KUMAR
PUGET SOUND ENERGY - ELECTRIC
6905 S 228th St
Kent, WA 98032
B: (253) 208-2183Applicant
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: BL.005109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
ANISH KUMAR
PUGET SOUND ENERGY - ELECTRIC
6905 S 228th St
Kent, WA 98032
B: (253) 208-2183Specialized
Billing
X
General Condions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
This permit and plans must be posted at the job site at all times.
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Call (425) 430-7203 or go to: www.MyBuildingPermit.com one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 206.510.0575) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Page 1 | Published: 3/30/2017
Planning Division | 1055 South Grady Way, 6th Floor | Renton, WA 98057 | 425-430-7200
Email: franchisepermits@rentonwa.gov Website: rentonwa.gov
FRANCHISE PERMIT APPLICATION
Published: 3/30/2017
TO THE APPLICANT: Submit an electronic copy of the plans with the Franchise Permit Application and the
Traffic Control Application to franchisepermits@rentonwa.gov. Permit cost is $360.50. Inspection fee for
trenching more than 60 lineal feet or installation of 6 or more poles will be billed at $60.00 per hour.
Franchise Agency:
Franchise Job Number: Phone:
Contact Name: Email:
Job Site Address: Project Name:
Description of Work:
Please check all that apply:
☐ New Construction ☐ Repair/Relocate ☐ Underground ☐ Overhead ☐ Sidewalk ☐ Street
☐ Open Trench ☐ Bore # of feet:
Contractor Name: Phone:
State Contractors License #: City of Renton Business License #:
“I certify that I am the owner or applicant’s authorized agent and do hereby agree to abide to the terms and conditions set forth under this permit and shall comply with the City of Renton’s Trench Restoration and Street Overlay Requirements. ”
Signature Date
INSPECTIONS SHALL BE REQUESTED 24 HOURS PRIOR TO COMMENCEMENT OF ALL WORK BY CALLING THE
INSPECTION LINE AT 425-430-7203 OR BY GOING TO MYBUILDINGPERMIT.COM
Jobs are required to be called in for job start, re-inspection and project final. Re-inspection fees are billed at $75/hour.
All Pre-Construction meetings shall be scheduled at a maximum of 14 days prior to the job start date.
Plan Review/Development Engineering Date Approved as submitted
Pre-Construction Meeting required
Site Construction Inspector Date Approved with comments or redlines
Camera inspection of utilities required
Development Engineering Manager Date
Puget Sound Energy - Electric
101112247
Anish Kumar
253-208-2183
anish.kumar@pse.com
332 Park Ave N 98056 101112247
Remove 2 submersible transformers, install two padmount transformers, install
two concrete secondary handholes, re-plumb and re-route existing primary and secondary to
new transformers and handholes. No pavement cuts. Restoration per City of Renton standards.
Potelco Inc.253-208-2183
BL005109 Poteli*227PL
5/31/2018
Scott Warlick 6/6/2018
MFP18003011
Justin Johnson 7-5-2018
pothole all existing utilities.
CITY OF RENTON
TRAFFIC CONTROL PLAN
PROJECT NAME: PERMIT#
CONSTRUCTION COMPANY: PHONE#:
CONTACT NAME: PHONE#:
ADDRESS: CELL#:
E-MAIL ADDRESS: FAX#:
PROJECT LOCATION: N/E/S/W OF:
WORK TIME: APPROVED BY:
WORK DATE: APPROVAL DATE:
OFFICE COPY T-
CONTRACTOR
DEV. SERVICE, INSPECTION P. MILLER
DEV. SERVICE, PLAN REVIEW B. BANNWARTH
POLICE CHARLES KARLEWICZ
FIRE FIRE MARSHALL FS #13
Permit Holder agrees to all the following:
• Comply with all traffic regulations of the City of Renton and the State of Washington.
• Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for
all street and lane closures, and the plan shall be performed in compliance with the Manual on
Uniform Traffic Control Devices.
• Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
• Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200
through 47.36.220, 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
• Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments,
including all costs of defense and attorney’s fees incurred in defending against same, arising from and
related to implementation of the approved traffic control plans including claims arising from towing of
private vehicles and the acts of the Permit Holder’s agents and employees.
• The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or
judgment, and in such event shall indemnify and hold harmless the City for any such claims paid,
including the City’s reasonable attorney’s fees and litigation costs incurred resulting from such claim.
• In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder
will pay for legal counsel chosen by the City to defend against same.
• Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address
traffic or pedestrian safety or travel.
• By my signature herein, I acknowledge all the above requirements.
PRINT NAME: DATE:
SIGNATURE:
Reset FormPrint Form
101112247
PSE/Potelco Inc.
Marc Bayley 253-234-6432
6905 S 228th St, Kent, WA 98032
marcus.bayley@pse.com
332 Park Ave N
TBD
6/24/2018
Anish Kumar 5/31/2018
MFP18003011
8:00 am to 3:00 pm
Monday through Friday
Justin Johnson
7-5-2018
SKETCH
I
-- NORTH --
I
NOTES:
• Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by sketch or reference to WSDOT.
• The plan must be submitted to the City’s PW/Transportation Division for review and/or approval at least three
working days prior to work.
• Approved Temporary Traffic Control Plan must be at the work site during work hours.
• Contractor or entity must call Renton School District (425-204-4455) or any public/private agency to be affected
by a temporary lane or road closure.
• Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded.
• Total road closure lasting more than 24 hours is subject to the approval by the City Council.
• Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
• Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
• Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
72 hours in advance of effective date and time.
• The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
• Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop
(3555 NE 2nd Street).
12121212121211111111111111777710200'
200'100'100'100'100'100'100'MATCHLINE SEE ABOVE 12121212121220202020200'
200'
200'
MATCHLINE SEE BELOW
Job#101112247332 Park Ave N, Renton, WAMay 11, 2018Sheet 1 of 2 gregory.harwood@pse.com(425) 424-6425www.trafficmanagement.com800.763.3999Traffic Control Services - Sales & RentalsPermits & Consulting - Engineering - TrainingPLAN PREPARED BY:DATE: 5/11/18PLAN ORDER: 36953TMI CONTACT PERSON: Michael FlanaganTCS CERT #: 301872CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040LANEWIDTHSPOSTED SPEED LIMITS20253035404510111255 +60/6545/5535/403025SIGN SPACING"X"800500'350'200'100'MFP18003011
121212121212121212121212202020201111201111111110100'100'100'200'200'100'100'100'Job#101112247332 Park Ave N, Renton, WAMay 11, 2018Sheet 2 of 2 gregory.harwood@pse.com(425) 424-6425www.trafficmanagement.com800.763.3999Traffic Control Services - Sales & RentalsPermits & Consulting - Engineering - TrainingPLAN PREPARED BY:DATE: 5/11/18PLAN ORDER: 36953TMI CONTACT PERSON: Michael FlanaganTCS CERT #: 301872CHANNELIZATIONDEVICE SPACINGMPH55/7035/4525/30TAPER403020TANGENT806040LANEWIDTHSPOSTED SPEED LIMITS20253035404510111255 +60/6545/5535/403025SIGN SPACING"X"800500'350'200'100'MFP18003011
318
310
304
300
1304
248
240
238
230
235
238 326
247
1211
1207
1201250
248
240
236
232235
247
301
315
249
J
J
J318061-166207
37.5 kVA 120/240V (C)
318061-166191
50 kVA 120/240V (C)
318061-166203
50 kVA 120/240V (C)
318061-166217
37.5 kVA 120/240V (C)
N 3RD STPARK AVE NGARDEN AVE N318057-166223 318061-166233
50 kVA 120/240V (C)
318064-166224
X3470
X3470
SLAG7883
318073-166224
10 kVA 120/240V (A)
SLAG7884
SLAG7885
318044-166223
UNK
SLAG7882
318049-166178
UNK
318069-166179
25 kVA 120/240V (C)
318074-166174
318049-166178
UNK
318073-166214
500 kVA 120/208V
60'PCR
14
PCR
14
PCR
14
318064-166224
X3470
X3470
SLAG7883
J
J
J PROPOSED
10' EASEMENT
PROPOSED
10' EASEMENT
(3) 750KCMIL(1) 1/0 AL SOL 336.4KCMIL ACSRABC336.4KCMIL ACSRABC
00 1"2"
00 50'100'
SITE PLAN
N
Vicinity Map
N/A
Owner / Developer Contact Info
officeATTN:
Renton School District #409
7812 S 124th ST
Seattle, wA 98178
Matt Feldmeyer (425) 204-4475
SITE SPECIFIC NOTES
OVERHEAD CIRCUIT MAP
SCALE: 6" = 1 MILE
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
108106462
584043027
594120879
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
Perm. Service
Relocation
Removal
POWER GENERAL NOTES - COMMERCIAL PROJECT
8.
EXCAVATION: The customer is to provide all trenching, backfill, vault excavations, compaction and
restoration per this sketch and per PSE standards. A minimum protective cover of 36" is required over
PSE's primary voltage equipment and 24" is required of PSE's secondary voltage equipment. The customer
will provide any and all shoring or they will side slope the trench to 1:1.
All materials to be installed in accordance with Puget Sound Energy's (PSE) standards. Any deviation from
this work sketch must be AUTHORIZED by PSE's Project Manager and NOTED on the Foremans' Copy.
All switching arrangements and/or outage arrangements are to be made with the Project Manager at least
three (3) working days in advance.
Contact the Utilities Underground Location Center (1-800-424-5555) at least 48 hours prior to commencing
work to get the underground facilities located.
STAKING: The customer will provide all staking (transformer, handhole, trench, grade, lot, pole, sidewalk,
etc.). See sketch and details for locations. Equipment locations must be approved by the Project Manager.
SITE PREPARATION: The work area will be at or near finished grade, clear of trench spoils or construction
materials which would restrict construction and/or equipment access, before work can begin.
Roads shall be paved or have a compacted , crushed rock base in place.
CLEARANCES: Transformers require a minimum of 6 feet from fire fighting equipment, 10 feet from
combustible walls, overhangs, doors, and windows, and a minimum of 5 feet from the back of curb (or guard
posts will be required per PSE standards). All conduits and vaults are to be at least 5 feet away from water,
storm and sewer lines when paralleling them in the right of way, and at least 1 foot when crossing them.
All work is to be done in accordance with local municipal and county permit requirements as applicable.
Customer/Developer is responsible to provide, install and maintain all secondary service cables, conduits
and crossings from the individual unit's meter base to the designated connection point.
Inclement weather conditions may cause delays in construction times and dates.
1.
2.
3.
4.
5.
6.
7.
9.
11.
10.
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
X
X
X
X
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:Marc Bayley
(253) 259-4494
Marcus.Bayley@PSE.com
SCALE: 1" = 50'
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
V01
318061-166217
37.5kVA
6247050
101112247THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Marc Bayley (253) 234-6432 5/4/18
Nate Linville (253) 970-7284 5/4/18
Nate Linville (253) 970-7284
Required City of Renton
Sartori Elementary Relocation
Remove (2) TUT, Install (2) PM Transformers
332 Park AVE N, Renton, WA 98056
101112247
As Noted 1 of 3
King CSPSKEPM
NW-17-23N-05E
2305E066 2305E088 2305E066 GRA-17
101112247505910446
Installed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER INSTALLATION
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
Material ID#:
V03
318061-166203
50kVA
6247100
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
V02
318061-166207
37.5kVA
Removed at site:
Grid Number:
kVA Rating:
Foreman to redline the following information
TRANSFORMER REMOVAL
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
V04
318061-166191
50kVA
AT J01: EXISTING 318057-166223
EXISTING VAULT TO REMAIN
REMOVE EXISTING B/O 4POS JBUS ON (S) WALL [594120879 2-45]
-INSTALL (1) NEW 4POS JBUS ON (S) WALL
AT V01: NEW 318061-166217 - 101112242
-INSTALL (1) 36" X 42" X 38" UNI-STRUT MINI-PAD HAND HOLE PER STD 6045.1010 (MINU15S) [2-60]
-INSTALL (1) 37.5kVA 120/240V 1Ø PM TRANSFORMER (MID: 6247050) [2-45]
-INSTALL (2) LB ELBOWS PER STD 6041.1000 (ELB10J) [2-57 X2]
-INSTALL (3) 5/8" STUD #6-350KCMIL 6POS SECONDARY CONNECTION BARS (MID: 4842001)
-INSTALL GRID 318061-166217
TRANSFER CABLE #CØ-10159 FROM V02
-INSTALL CABLE #CØ-EHX807
AT HH1: NEW
-INSTALL (1) 2'6" X 2'6" X 2' CONCRETE SECONDARY HAND HOLE W/ ANTI-SKID DOOR PER STD 6050.2000 (HH14350AS) [2-34]
-INSTALL (3) #10-350KCMIL SECONDARY CONNECTION BLOCKS
TRANSFER CABLE #CØ-10159 TO V01
AT V02: REMOVE 318061-166207
REMOVE EXISTING 37.5kVA 120/240V TUT AND RETURN TO PSE YARD [2-45]
REMOVE EXISTING 4'8" X 4'8" X 6' VAULT [2-60]
AT V03: NEW 318061-166203
-INSTALL (1) 36" X 42" X 38" UNI-STRUT MINI-PAD HAND HOLE PER STD 6045.1010 (MINU15S) [2-60]
-INSTALL (1) 50kVA 120/240V 1Ø PM TRANSFORMER (MID: 6247100) [2-45]
-INSTALL (1) LB ELBOW & (1) DUST CAP PER STD 6041.1000 (ELB10J) [2-57]
-INSTALL (3) 5/8" STUD #6-350KCMIL 6POS SECONDARY CONNECTION BARS (MID: 4842001)
-INSTALL GRID 318061-166203
AT HH3: NEW
-INSTALL (1) 2'6" X 2'6" X 2' CONCRETE SECONDARY HAND HOLE W/ ANTI-SKID DOOR PER STD 6050.2000 (HH14350AS) [2-34]
-INSTALL (3) #10-350KCMIL SECONDARY CONNECTION BLOCKS
INTERCEPT EXISTING 3" CONDUIT, PLUMB FROM V03 TO NEW HAND HOLE
INTERCEPT EXISTING UG SECONDARY TRPLEX TO HH4
AT V04: REMOVE 318061-166191
REMOVE EXISTING 37.5kVA 120/240V TUT AND RETURN TO PSE YARD [2-45]
REMOVE EXISTING 4'8" X 4'8" X 6' VAULT [2-60]
AT J02: EXISTING 318049-166178
EXISTING JBOX TO REMAIN
REMOVE NEUTRAL TIE FROM V04 TO J02
SPAN NOTES
IP1 & IP2 TO V01
INTERCEPT EXISTING 2" CONDUIT, PLUMB INTO V01 [2-36]
STRIP BACK CABLE #CØ-10159 FROM V02 AND ROUTE TO V01
IP3 TO V01
INTERCEPT EXISTING 2" CONDUIT, PLUMB INTO V02 [2-36]
IP4 TO HH2
INTERCEPT EXISTING 3" SECONDARY CONDUIT [2-36]
REMOVE EXISTING 350KCMIL SECONDARY TPLX CABLE
V01 TO HH1
-INSTALL (1) RUN 350KCMIL SEC TPLX ±70' _____' ACTUAL [2-54A]
HH1 TO HH2
INSTALL (1) RUN 350KCMIL SEC TPLX ±80' _____' ACTUAL [2-54A]
V02 TO HH1
REMOVE EXISTING (1) 350KCMIL SEC TPLX ±10' [2-54A]
V03 TO HH2
-INSTALL (1) RUN 350KCMIL SEC TPLX ±50' _____' ACTUAL [2-54A]
V04 TO HH2
REMOVE EXISTING (1) 350KCMIL SEC TPLX ±10' [2-54A]
DEVELOPER & CUSTOMER NOTES:
THE CUSTOMER IS RESPONSIBLE FOR PROVIDING ALL TRENCHING, SELECT BACKFILL,
COMPACTION & RESTORATION PER PUGET SOUND ENERGY STANDARDS 6750.6500
-REQUIRED TO PROVIDE 6' X 6' WORK PIT & 1 CUBIC YARD OF 5/8" MINUS AT V01 & V03
-REQUIRED TO PROVIDE 6' X 6' WORK PIT FOR IP1& IP2, IP3, AND IP4
-REQUIRED TO FOLLOW ALL TRENCH DETAILS ON SELECT BACKFILL
-REQUIRED TO PROVIDE EQUIPMENT TO PUMP OUT WATER FOR WORK PITS & TRENCH AT ALL
TIMES
-EXCAVATE & EXPOSE EXISTING PSE UG FACILITIES 48 HOURS PRIOR TO CONSTRUCTION
-PSE INSPECTION IS REQUIRED PRIOR TO FINAL BACKFILL
-PSE WILL NOT ENERGIZE FACILITIES UNTIL BACKFILL IS COMPLETE
-L&I INSPECTION & APPROVAL IS REQUIRED 72 HOURS PRIOR TO CONNECTION
-RESPONSIBLE FOR ALL TREE TRIMMING AND BRUSH CLEARING
UNDERGROUND CIRCUIT MAP
SCALE: NONE
JOB
SITE
JOB
SITE
CIRCUIT FEET ADDED: 180
CIRCUIT FEET REMOVED: 200'
MFP18003011
318061-166217
37.5kVA 120/240V
318061-166203
50kVA 120/240V
EXISTING
2" CONDUIT
EXISTING
2" CONDUIT
6' X 6' WORK PIT
CUSTOMER PROVIDED
9' X 10' WORK PIT
CUSTOMER PROVIDED
6' X 6' WORK PIT
CUSTOMER PROVIDED
6' X 6' WORK PIT
±20'90°
R=48"±20'90°
R=48"
90°
R=48"±20'318061-166217
37.5kVA 120/240V
318061-166203
50kVA 120/240V CØ-EHX803
318061-166217
37.5kVA 120/240V
318061-166203
50kVA 120/240V
PSE PROVIDED & INSTALLED
(1) NEW 1/0 AL SOL
CØ-EHX803
EXISTING 1/0 AL SOL
CØ-10159
PRIMARY CABLE ONE-LINE DIAGRAM
SCALE: NONE
101112247UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Marc Bayley (253) 234-6432 5/4/18
Nate Linville (253) 970-7284 5/4/18
Nate Linville (253) 970-7284
Required City of Renton
Sartori Elementary Relocation
Remove (2) TUT, Install (2) PM Transformers
332 Park AVE N, Renton, WA 98056
101112247
As Noted 2 of 3
King CSPSKEPM
NW-17-23N-05E
2305E066 2305E088 2305E066 GRA-17
UNDERGROUND CIRCUIT MAP (AFTER)
SCALE: NONE
PRIMARY CONDUIT DIAGRAM
SCALE: NONE
UNDERGROUND CIRCUIT MAP (before)
SCALE: NONE
PRIMARY CABLE & CONDUIT TABLE
LOCATION CONDUIT PRIMARY CABLE
ASBUILT INFORMATION
SIZE Qty LENGTH
Design
(ft)
BENDS PULL PULL Cable LENGTH
Design
(ft)
Cable Numbers Foreman Please Record Foreman - Complete
FROM TO (in)90°45°22°11°(lbs)
Rev
(lbs)Size A B C Manufacturer Compound Year Actual Amount Installed (Conduit & Cable)
J01 V01 2 1 EX 130
NEW 30 2 0 0 0 48 46 PRI 12KV
1/0 UG 160
10159
V01 V03 2 1
30
EXISTING
140'
2 0 0 0 33 33 PRI 12KV
1/0 UG 160
EHX807
ABANDONED / REMOVE / REPLACED CABLE SCHEDULE
CABLE
NO.
SAP
EQUIP
LOCATIONS CABLE
(LF) EST
EXISTING CABLE
MFG. NAME
EXISTING CABLE
MFG. DATE
CABLE
REPLACED?FROM TO
10159 10502898 IP1 V02 30'
10158 10502887 V02 V04 180
TOTAL 180'
GUARD POSTS FOR PADMOUNT EQUIP.
TYPICAL
TRANSFORMER
0700.1600Not to scale
5'
MAX
5'
MAX
5'
MAX
5'
MAX
5'
MAX
5'
MAX
5'
MAX
5'
MAX
3'
MIN
8' x 8' OR 10' x 10'
CONCRETE PAD
GUARD POSTS
ACCESS DOOR SWING
4'
MIN
18'
MIN
3'
MIN
CL
CL
18'
MIN
COOLING
5' MIN
5' MIN
10' MIN
5'
MIN
FINS
ACCESS
CONCRETE PAD
MINIMUM CLEARANCES FOR PSE EQUIPMENT
CURB OR EDGE OF PAVEMENT
CURB OR EDGE OF PAVEMENT
5' MIN
ROAD OR
PARKING AREA
TYP. PAD
& TRANS-
FORMER
3'
MIN
3' MIN
3' MIN
DOOR
ACCESS
DOOR
REQUIRED
WORK SPACE
AREA
6775.0035 Not to scale
Communications
Primary Power
Cables or Conduit
Excavated Dirt Pile
ROADSIDE
Final Grade
24" Min
12" Min
Separation
36"
Min
Cover
48"
Max
Backfill
(No rocks over 10" diameter)
Separation
12" Min
Gas
4" Sand Bedding
32" Typical
(Power, Gas, and
Communications)
JOINT TRENCH DETAIL
Primary-Mainline Gas & Communications (NTS)
Separation
12" Min
6" or 12" Min Sand Shading after Compaction
- A 6" layer of sand is allowed when excavated native material contains rocks no larger than 8" in diameter.
Trench and backfill requirements for primary electric line extension trenches (No PSE gas)
- A 12" layer of sand is required when excavated native material contains rocks up to 10" in diameter.
FLOW DIRECTION
LAY 8" BOTTOM SKIRT ON TOP OF NATIVE SOIL,
SECURE WITH PEA GRAVEL BAGS (MID 9995692).
6'
3'
8"
TECHNIQUES FOR EROSION AND SEDIMENT CONTROL
SILT FENCE DETAIL
Not to Scale 0150.3200 MINIMUM CLEARANCES FOR PSE EQUIPMENT
NOT TO SCALE
OIL-FILLED EQUIPMENT
TRANSFORMER
APPROVED
AREA
COMBUSTIBLE BUILDING WALLS & ROOF10'
10'
10'
MFP18003011
318061-166217
37.5kVA 120/240V
318061-166203
50kVA 120/240V
EXISTING
(1) 3" CONDUIT
CUSTOMER PROVIDED
6' X 6' WORK PIT
CUSTOMER PROVIDED
6' X 6' WORK PIT
CUSTOMER PROVIDED
6' X 6' WORK PIT
90°
R=36"
45°
R=36"±20'±70'±70'EXISTING
(1) 3" CONDUIT
PSE PROVIED
(1) 3" SCH80 PVC CONDUIT
PSE PROVIED
(1) 3" SCH80 PVC CONDUIT
CUSTOMER PROVIDED
6' X 6' WORK PIT
±50'±20'±40'90°
R=36"
318061-166217
37.5kVA 120/240V
318061-166203
50kVA 120/240V
±20'90°
R=36"45°
R=36"±20'±70'±70'EXISTING
(1) 350KCMIL SEC TPLX
NEW
(1) 350KCMIL SEC TPLX
IN EXISTING 3" CONDUIT
±40'
±50'
PSE PROVIDED
(1) 350KCMIL SEC TPLX
PSE PROVIDED NEW
(1) 350KCMIL SEC TPLX
90°
R=36"
SECONDARY CONDUIT DIAGRAM
SCALE: 1" = 50'101112247UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
Marc Bayley (253) 234-6432 5/4/18
Nate Linville (253) 970-7284 5/4/18
Nate Linville (253) 970-7284
Required City of Renton
Sartori Elementary Relocation
Remove (2) TUT, Install (2) PM Transformers
332 Park AVE N, Renton, WA 98056
101112247
As Noted 3 of 3
King CSPSKEPM
NW-17-23N-05E
2305E066 2305E088 2305E066 GRA-17
SECONDARY CABLE DIAGRAM
SCALE: NONE
TOP VIEW
SIDE VIEW
EXCAVATION: 4-2/3 CUBIC YARDS
Rock
Crushed
6"
3'-6"
2"
6'
6'
48"42"
36"
38"
42"
Struts
VAULT & EXCAVATION DETAIL AT V01 & V03
Not to scale 6045.1000
1950 lbs
PROPOSED UG PRIMARY
EXISTING UG PRIMARY
PRIMARY SPLICES
SPLICE PIT DETAIL IP1 & IP2
SCALE: NONE
TO V03FROM J01
TO V01
SINGLE PHASE SECONDARY CONCRETE HANDHOLE AT HH1 & HH3
Not to scale 6050.2020-1
TOP VIEW
SIDE VIEW
2'-4"
EXCAVATION: 5-1/3 CUBIC YARDS
6'-0"
6'-0"
6" Crushed rock
2"
2'-6"
Install PVC bell ends
and grout into wall
2'-6"
Handhole
820 lbs
Conduits and conductors shall enter from
ends of handhole through knockouts provided
Typical customer run
service conductors in duct
Steel Door
Seal conduit
with foam
Customer-installed grounding wires ( the "4th" wire on the single-phase systems and the "5th" wire on
the three-phase systems) shall not be connected to PSE's ground or neutral bus. They shall be
removed by customer or cut off at the vault wall.
PROPOSED UG PRIMARY
EXISTING UG PRIMARY
PRIMARY SPLICES
SPLICE PIT DETAIL IP3
SCALE: NONE
FROM V01
TO V03
MFP18003011