HomeMy WebLinkAboutMFP19000210DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Franchise Permit: MFP19000210
IVR Number: 19000210
Permit Informaon
Permit Name:Puget Sound Energy - Electric
Address/Locaon :01/11/2019Application Date:7224000235Parcel Number:212 PARK AVE N
Permit Type:01/22/2019Issue Date:Franchise
Permit Work Class:01/22/2020Expiration Date:Minor Utility
Job Number:101116670Franchise Type:Electric
Description:Install overhead Bridal Service. Overhead work on Pole P01 and Pole P02. Install guy wire and Bridal Service.
Contacts
Name Address PhoneTypeBilling
ANISH KUMAR
PUGET SOUND ENERGY - ELECTRIC
6905 S 228th St
Kent, WA 98032
B: (253) 208-2183Applicant
Vicki Henson
Potelco Inc
8001 212th St S
Kent, WA 98032
B: (253) 863-0484Contractor
Business License Number: 5109Electrical Contractor: POTELI*344O4
Construction Contractor: POTELI*227PL
CITY OF RENTON ROW 1055 S Grady Way
Renton, WA 98057-3232
Owner
ANISH KUMAR
PUGET SOUND ENERGY - ELECTRIC
6905 S 228th St
Kent, WA 98032
B: (253) 208-2183Specialized
Billing
X
General Condions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
This permit and plans must be posted at the job site at all times.
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Call (425) 430-7203 or go to: www.MyBuildingPermit.com one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 206.510.0575) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Page 1 | Published: 3/30/2017
Planning Division | 1055 South Grady Way, 6th Floor | Renton, WA 98057 | 425-430-7200
Email: franchisepermits@rentonwa.gov Website: rentonwa.gov
FRANCHISE PERMIT APPLICATION
Published: 3/30/2017
TO THE APPLICANT: Submit an electronic copy of the plans with the Franchise Permit Application and the
Traffic Control Application to franchisepermits@rentonwa.gov. Permit cost is $360.50. Inspection fee for
trenching more than 60 lineal feet or installation of 6 or more poles will be billed at $60.00 per hour.
Franchise Agency:
Franchise Job Number: Phone:
Contact Name: Email:
Job Site Address: Project Name:
Description of Work:
Please check all that apply:
☐ New Construction ☐ Repair/Relocate ☐ Underground ☐ Overhead ☐ Sidewalk ☐ Street
☐ Open Trench ☐ Bore # of feet:
Contractor Name: Phone:
State Contractors License #: City of Renton Business License #:
“I certify that I am the owner or applicant’s authorized agent and do hereby agree to abide to the terms and conditions set forth under this permit and shall comply with the City of Renton’s Trench Restoration and Street Overlay Requirements. ”
Signature Date
INSPECTIONS SHALL BE REQUESTED 24 HOURS PRIOR TO COMMENCEMENT OF ALL WORK BY CALLING THE
INSPECTION LINE AT 425-430-7203 OR BY GOING TO MYBUILDINGPERMIT.COM
Jobs are required to be called in for job start, re-inspection and project final. Re-inspection fees are billed at $75/hour.
All Pre-Construction meetings shall be scheduled at a maximum of 14 days prior to the job start date.
Plan Review/Development Engineering Date Approved as submitted
Pre-Construction Meeting required
Site Construction Inspector Date Approved with comments or redlines
Camera inspection of utilities required
Development Engineering Manager Date
Puget Sound Energy - Electric
101116670
Anish Kumar
253-208-2183
anish.kumar@pse.com
212 Park Ave N 98057 101116670
Crew will be installing OH bridal service. Crew will do overhead work on P01
(318013-166178) and P02 (317994-166177) which is on private property to install guy wire and
bridal service to '212'. City of Renton has approved overhead exemption for ***continued below
Potelco Inc.253-208-2183
BL005109 Poteli*227PL
1/3/2019
MFP19000210
Holly Powers
Scott Warlick 1/22/2019
1/22/2019
CITY OF RENTON
TRAFFIC CONTROL PLAN
PROJECT NAME: PERMIT#
CONSTRUCTION COMPANY: PHONE#:
CONTACT NAME: PHONE#:
ADDRESS: CELL#:
E-MAIL ADDRESS: FAX#:
PROJECT LOCATION: N/E/S/W OF:
WORK TIME: APPROVED BY:
WORK DATE: APPROVAL DATE:
OFFICE COPY T-
CONTRACTOR
DEV. SERVICE, INSPECTION P. MILLER
DEV. SERVICE, PLAN REVIEW B. BANNWARTH
POLICE CHARLES KARLEWICZ
FIRE FIRE MARSHALL FS #13
Permit Holder agrees to all the following:
• Comply with all traffic regulations of the City of Renton and the State of Washington.
• Prepare a traffic control plan and obtain City approval of that plan. That plan shall be implemented for
all street and lane closures, and the plan shall be performed in compliance with the Manual on
Uniform Traffic Control Devices.
• Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
• Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200
through 47.36.220, 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
• Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments,
including all costs of defense and attorney’s fees incurred in defending against same, arising from and
related to implementation of the approved traffic control plans including claims arising from towing of
private vehicles and the acts of the Permit Holder’s agents and employees.
• The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or
judgment, and in such event shall indemnify and hold harmless the City for any such claims paid,
including the City’s reasonable attorney’s fees and litigation costs incurred resulting from such claim.
• In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder
will pay for legal counsel chosen by the City to defend against same.
• Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address
traffic or pedestrian safety or travel.
• By my signature herein, I acknowledge all the above requirements.
PRINT NAME: DATE:
SIGNATURE:
Reset FormPrint Form
101116670
PSE/Potelco Inc.
Timothy LoPresto 425-393-4185
6905 S 228th St, Kent, WA 98032
timothy.lopresto@pse.com
212 Park Ave N
TBD
1/21/2019
Anish Kumar 1/3/2019
MFP19000210
Scott Warlick
1/22/2019Monday - Friday
8:00AM - 3:30PM
SKETCH
I
-- NORTH --
I
NOTES:
• Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by sketch or reference to WSDOT.
• The plan must be submitted to the City’s PW/Transportation Division for review and/or approval at least three
working days prior to work.
• Approved Temporary Traffic Control Plan must be at the work site during work hours.
• Contractor or entity must call Renton School District (425-204-4455) or any public/private agency to be affected
by a temporary lane or road closure.
• Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded.
• Total road closure lasting more than 24 hours is subject to the approval by the City Council.
• Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
• Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
• Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
72 hours in advance of effective date and time.
• The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
• Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance shop
(3555 NE 2nd Street).
the OH service modification to 212 Park Ave N. There will be one lane closed for installation of service.
No pavement cuts anticipated. Restoration per City of Renton standards.
212 Park Ave N
Renton
WA 98057
USABUSSTOPMOVE BUS
STOP
TEMPORARILY
125' NORTH
RIGHT LANE
CLOSED
AHEAD W20-5RW4-2LROAD
WORK
AHEAD W20-1200'200'200'ROADWORKAHEADW20-1ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1 200'W20-7A
N 2ND STPARK AVE NM6-2P01
P02
11 11 11 111515 1414CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
N PSE PUGET
SOUND
ENERGY
JOB#101116670
212 PARK AVE N, RENTON, WA
12/21/2018
ryan.perkins@pse.com
425-424-6621
SHEET 1 of 1
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 008997
Card Exp. 08/13/2019
gregory.harwood@pse.com
(425)424-6425
TEMPORARY TRAFFIC CONTROL PLAN
Notes:
1. All signs and spacing to conform to the
MUTCD and City of Renton standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
28" TRAFFIC CONE
LEGEND
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
STOP
POLE
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
ROW ROW
MFP19000210
224
1200
1206
223
221
217
220
216
214
212
210
204
200
215
211
1010
1/0 OH TPLX
L=75'
318013-166178
25 kVA 120/240V (C)
2ND ST PARK AVE N317994-166177
65T
X4009
WORKSITE
GAS
PHONE
CABLE TV
N/A 108110410
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A
N/A N/A
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
OH Removal
Relocation
Removal
Temporary
Job Order
Distribution
HP Svc/MSA
Owner / Developer Contact Info
officeATTN:
FLORENCE WONG-HODGKIN
212 PARK AVE N
RENTON, AW 98057
RYAN HUGHES 206-423-5064
Vicinity Map
TG PG 656-D2
SITE SPECIFIC NOTES
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
SITE PLAN
SCALE: 6" = 1 MILE
OVERHEAD CIRCUIT MAP
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:TIMOTHY LOPRESTO
425-393-4185
timothy.lopresto@pse.com
PSE
No
No
No
Yes
Yes
Yes
No
YesDeveloper
"Flagging Required"
"Outages Required"
"Locates Required"
X
X
X
X
SCALE: 1" = 50'
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
Service Stubs
101116670
N/A
N/A
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT
Gas Order
SCALE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO
OH CKT MAP CIRCUIT NOUG CKT MAP
T. LoPRESTO 425-748-6367
T. LoPRESTO 425-748-6367
N/A N/A
QC. NGUYEN 425-748-6369
N/A RENTON
RYAN HUGHS-WEST SEATTLE ELEC
OH MODIFIED SVC
212 PARK AVE N, RENTON, WA
N/A
N/A
AS NOTED
KING N/A N/A QCNOKE
NW17 T23N R05E N/A N/A
2305E066 2305E066NE 2305E088 GRA-17
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
506612108
N/A
P01 GRID #318013-166178
-EXISTING POLE WILL REMAIN
P02 GRID #317994-166177
- EXISTING POLE WILL REMAIN
P01 TO P02
- EXISTING 4/0 NEUTRAL TO REMAIN
P01 TO "212"
- INSTALL OH BRIDAL SERVICE 1/0 [BSTPX] PER STD 6024.1000 35' FROM P01
- INSTALL 1/0 OH TPLX, L≈75'(___')
CUSTOMER NOTES:
**CUSTOMER PAYS ONLY FOR OH MODIFIED SERVICE**
6. TREAT ALL FIELD-DRILLED POLES WITH COPPER NAPHTHENATE WOOD PRESERVATIVE.
1. POLES, CONDUCTORS, DEVICES TO BE INSTALLED PER PSE STANDARDS & SPECIFICATIONS.
2. POLES ARE TO BE INSTALLED OR RELOCATED AS STAKED.
3. ALL NEW POLES SET SHALL BE THE CLASS INDICATED ON THE SKETCH OR BETTER.
4. INSTALL GROUND PLATE ASSEMBLY ON ALL NEW POLES.
5. INSTALL GRID NUMBERS ON ALL NEW AND EXISTING POLES AS SHOWN ON SKETCH.
GENERAL OVERHEAD NOTES:
NOTE: If the common neutral wire is 2/0 ACSR or larger, the
mid span clamp may be attached to the common neutral and
the span guy eliminated. Do not use the mid span clamp on
any size of copper neutrals (see application statement).
#2 ACSR may be substituted for 3/8 steel guy wire as an
alternate method to support the bridle service wire.
Ñ
Automatic Guy Grip
or
Automatic Deadend
#2 ACSR
Preformed
Guy Grip
or
6
Alum “H”
Conn#2 ACSR
13 10
Secure service wire to
span guy with plastic
zip ties as needed to
prevent it from sagging
into communications
safety space.
Mid-Span
Tap Clamp 3
4
7 Service Wedge
1 2 8
Rigid Clevis
7 7
Service Wedge
Common Neutral
Typically up to 125 maximum
for #2 or 1/0, 75 maximum
for 4/0.
3/8 Span Guy
#2 ACSR
or
Attach the service
wedge deadend
bail to the mid span
tap clamp.
5
11
1 9
5/8 Eye Bolt
with Curved
Washer
12
4
To supporting structure or house
Top View
Service Wedge Bail
Service Line Neutral
Service Wedge Bail
Mid span tap clamp fits steel
guy and #4 4/0 ACSR common
neutral conductor.
Mid Span Clamp
Detail
Figure 1 Overhead bridle service, triplex or quadraplex wire
OVERHEAD BRIDLE SERVICE
@XFMR (P01)
Load: 37.58 kW
LRC: 65 A
% V. Drop: 3.1%
% Flicker: 1.5%
LRC:
Length:
% Flicker:
Sq. Footage:
Panel Size:
Heat Type:
Est. Demand:
% V. Drop:
Size:
800 SQ.FT.
200 AMPS
GAS
8 KW
65 AMPS
75'
2.3%
3.5%
1/0 OH TPLX
P01 - MTR "212"
MFP19000210