Franchise Permit: MFP17000131
Permit Name:
Address/Location:
Permit Type:
Permit Work Class
Franchise Type:
Description:
Bil
PSE -Electric
154 BLAINE AVE NE
Franchise
Minor Utility
Electric
IVR Number: 17000131
Parcel Number
Job Number:
lace distribution pole P01 and stub pole PO2 in Blaine Ave NE.
Name
X Contact Carli Bunkelman
PSE/POTELCO - Billin_g _
Contractor VICKI HENSON
POTELCO INC
Electrical Contractor: POTELI*34404
Construction Contractor: POTELI*227PL
Owner Kari Roller
Citv of Rer
1723059125
101103202
Address
6905 S 228th St
Kent, WA 98032
8001 212th St S
Application Date
Issue Date:
Expiration Date:
Est. Completion:
01/09/2017
01/09/2017
01/09/2018
01/15/2017
Phone
6:
3)437-6708
B: (253) 863-0484
Kent, WA 98032
Business License Number: BL.005109
1055 S Grady Way
B: (425) 430-6851
C:
5)430-6931
• Permission is hereby given for the work described on this permit according to the conditions hereon and according to the approved
plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton .
• This permit and plans must be posted at the job site at all times.
• 1 hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to Renton
Trench Restoration and Street Overlay Requirements .
• Call (425) 430-7203 or go to: www.MyBuildingPermit.com one working day in advance to schedule an inspections and for ANY work in
the Right of Way.
• Call 8 11 to locate underground utilities at least two full business days prior to any excavation .
• In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010) (Olympic
Pipeline at 206.510.0575)(Puget Sound Energy at 425.457.5816) to request a consultation with the transmission pipeline company prior
to performing any construction or excavation activities . This requirement to consult with the transmission pipeline company is in
addition to the requirement to Call before You Dig as required in RCW 19.122.
(Signature)
(Date)
THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES Page 1 of 2
DEPARTMENT OF COMMUNITY
CITY OF
AND ECONOMIC DEVELOPMENT Renton
0
Franchise Permit: MFP17000131
IVR Number: 1/uuun1
nspections
- Call (425) 430-7203 or go to: www.MyBuildingPermit.com to - Do not cover until approved.
schedule an inspection. - Do not occupy until final inspection is complete.
- Call before work is concealed or concrete poured. - Final inspection is required.
- Do not pour concrete until approved.
Number Description Date Inspector j Comments
918 Traffic Control Plan Inspection
928 ENG -Job Start
914 Restoration Inspection
906 Final Walkthrough Inspection
THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES Page 2 of 2
(� itt- of �•� `�
QLKARTM MI OF COMMUNITYAND ECONOMIC.DVELQPMtNT
DC r.L%JPIVIENT 3rr% Mca DIVISION
MASTER USE/FRANCHISE UTILITY PERMIT APPLICATION
Phone: (425) 430-7266 Fax: (425) 430-7231 franchise@rentonwa_eov
TO THE APPLICANT: Submit 3 copies of plans with application. Permit cost is $360.50. Inspection fee for
trenching more than 60 lineal feet or installation of 6 or more poles will be billed at $60.00 per hour.
For Citv Use On
CITY PERMIT NO: MFP � ? Cr'D-d / 3 /
Date of Application:
12/23/2016
WORK ORDER NO.: 87029
Franchise Agency:
KentWA
Puget Sound Ener9�
Mailing Address for Permit: 6905 S 228th St, ,
Contact Carpi Bunkelman
Name:
Job Number: 101103202
Job site Address: 154 Blaine Ave NE
zip: 98032
Phones 253-4'37-6708
e-mail: Carfi.Bunkefman@pse.com
Project -Name:
Description of work: Crew to replace distribution -pole P01 � stub pole P02 in Blaine Ave NE.
Please Check ail that
❑ New Construction ®Repair/Relocate
❑ Open trench El Bore El# of feet:
Estimated Job completion date:
Contractor name: Potelco Inc.
0'1 /15/17
❑ Underground ❑Overhead
❑ Gas ®' Electric ❑; Other:
❑ Sidewalk ®Street
Phone: 253-437-6708
City of Renton Business License Number: BLO05109 State Contractors License Number: Poteli*227PL
"I certify that I am the applicant's owner or authorized agent and do hereby agree to abide oto -the terms
and conditions set forth
under this permJLarrd shall comply with the City of Renton's Trench Restoration and Street Civerlay Requirements. "
Signature
D
ate 12/23/2016
CITY INSPECTOR SHALL BE NOT1fiED 24 HOURS PRIDR TO COMMENCEMENT OF ALL l/VORK
RY CALLIN!G THE INSPECTION LINE AT-425-430-72t►3
Jobs are required to be called in for job start, re -inspection and project final.
I
b � � ,Approved as Submitted
Plan R v' w/Development Services Date ❑ On -Site Pre -Con Required
El Approved with Comments or Redlines
7 [Z Traffic Control Plant Attached
❑ Camera Inspection of Utilftie-s-Required
Utility Inspector Date
Issue
Date:
Public Works Permit Supervisor Date Permit expires 6 months from issue date
CITY OF RENTON
TRAFFIC CONTROL PLAN
PROJECT NAME: 101 103202
CONSTRUCTION COMPANY: POteICO Inc.
CONTACT NAME: Carle B -UH �GelC11011
ADDRESS: 6905 S 228th St, Kent, WA 98032
E-MAILADDRESS: CarfT,Bl�rlketrxlan a�pse.Com
PROJECT LOCATION: X54 Blaine AVe NE
woR�c TIN9E0 TBD
WORK DATE: TBD
PERMIT#
PHONE#:
PHONE#:
CELL#:
FAX#:
N/E/S/W OF:
APPROVED BY:
2534137-6708
APPROVAL DATE: � � � Cn ` Ze I
Permit Holder agrees to all the following:
• Comply with all traffic regulations. of the City of Renton and the State of Washington.
• Prepare a traffic control plan and obtain City approval of that plan. That pian shall be implemented for
all street and lane closures, and the plan shall be performed in compliance with the Manual on
Uniform Traffic Control Devices.
• Notify emergency services (253-852-2121) twenty-four (24) hours before any street or lane closures.
• Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of R.C.W. 47.36.200
through 47.36.220, 9A.36.050 Reckless Endangerment, and other applicable State and City codes.
Indemnify and 'hold'harmless the City of Renton from any and all claims, actions, and judgments,
including all costs of defense and attorney's fees incurred in defending against same, arising from and
related to implementation of the approved traffic control plans including claims arising from towing of
private vehicles and the acts of the Permit Holder's agents and employees.
• The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or
judgment, and in such event shall indemnify and hold harmless the City for any such claims paid,
including the City's reasonable attorney's, fees and litigation costs incurred: resulting from such claim.
In the event any claim or suit is brought against City within the scope of this Agreement, Permit Holder
will pay for legal counsel chosen by the City to defend against same.
• Flagger and sign placement aresubject to revision by the City Inspector>on5ite, Lif needed to .address
traffic or pedestrian safety or travel.
• By my signature herein, I acknowledge all the above requirements.
PRINT NAME: CaW'li 8un'kelman DATE: I 2123/2n'I a
SIGN'ATU'RE:
OFFICE COPY
T -
CONTRACTOR
DEV. SERVICE, INSPECTION
P. MILLER
DEV, SERVICE, PLAN REVIEW
8, BANNWARTH
POLICE
CHARLES KARLEWICZ
FIRE
FIRE MARSHALL FS#13
NOTES:
• Work Zone Traffic Control shall be in accordance with the Manual on Uniform Traffic Control Devices (MUTCD)
and shown by sketch or reference to WSDOT.
• The plan must be submitted to the City's PW/Transportation Division for review and/or approval at least three
working days prior to work.
Approved Temporary Traffic Control Plan must be at the work site during work hours.
Contractor or entity must cail Rentan School District (425-204-4455) ,or any public/private agency to be affected
by a temporary lane or road closure.
Complete assistance and accomrrrodation shalt #�e _p°rovicled to all kinds of pedestrian traffic when sidewalk or
walkway is impeded.
• Total road closure lasting more than 24 hours is subject to the approval by the City Council.
Any vehicle, equipment, barricade, or portable tow -away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary Ntt Barking. Zones; ali` the following, apply in addition to previous:
• Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations for
vacate parking or curb lane usage.
• Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
72 hours in advance of effective date and time.
- The cover sheet of this Traffic Control Plan form must be attached to each Temporary No Parking Sign on the
project site.
• Temporary traffic control devices must be removed immediately when work is done or no construction activities
are going on. If deemed abandoned, City crews will remove and store them at the City's maintenance shop
(3555 NE 2"d Street).
SKETCH
--
AHEAD
LANE
CLOSED
AHEAD
(W 20-5L)
FLOGGER
AHEAD
(W 20-5L)
TABLE A
TAPER LENGTH TRUCK WITH
SPEED
CONE SPACING FLASHING
FT BEACON
(MPH) ALONG TAPER
OFFSET WIDTH (FT)
10' 12'
25 105 125 10-20
30. 150 180 10-20 T
35 205 245 10-20 IT
40 270 320 10-20 BUFFER SPACE: 425' (50MPH)
45 450 540 10-20 O
50 500 600 10-20 O
O° TAPER LENGTH: SEE TABLE A
NOTE: O O 6 DEVICE MINIMUM
1. DISTANCE BETWEEN SIGNS SHALL
BE 100' FOR RESIDENTIAL
STREETS (25 MPH), AND STo
200' FOR ARTERIAL ROADWAYS O
J
2. FLASHING BEACON SHALL BE I U
INSTALLED AT EACH SIGN FOR d
NIGHT—TIME USE.
3, DISTANCES MAY VARY AS APPROVED 500'
BY THE ENGINEER. FLACCER
AHEAD
4, FLAGGERS REQUIRED TO CONTROL
(W 20-5L)
TRAFFIC WHENEVER THE CONTRACTOR 500'
MUST INTERRUPT TRAFFIC FLOW
TO ACCESS THE WORK SITE WITH LANE
MATERIALS OR EQUIPMENT. CLOSED AHEAD
HEAD
5. SIGN SIZE PER MUTCD. (w 20-5L)
500'
LEGEND: ROAD
CONSTRUCTION
R CONE OR CHANNELIZING DEVICE AHEAD
(SEE STD 702) (W20-1)
TRAFFIC CONTROL PLAN REwsES.REED 4-28-2014
PUGET 2 LANE ROADWAY: ONE LANE CLOSED WITH APPROVED: DATE:
SOUND
ENERGY ALTERNATING ONE-WAY TRAFFIC AND FLAGGERS
PLANNING AND ENGINEERING DEPARTMENT DRAWNGNUMBER:
2A -90C
N
SCALER: 1 0
a
164
UO2
TRANSFORMER TRANSFER
New pole at site: P0 1
Grid Number: 317959-166495
kVA Rating: 25 —
Foreman to redline the following information
Company ID#:
Primary phase connected to:
Tested Secondary Voltage
158
317955-166466 � /
152
121 Ar"" \� �'-
317945-166475
50kVA 1201240v
115
SITE PLAN- 6-.._.
..
SCALE: 1`-501
(fg)
317961-166490
120
317978-166504
I x25kVA 120/240V
lxlOkVA 120/240v
317959-166495
25kVA 1201240V
317945-166492
16T
UNK
151
150
146
142
SITE SPECIFIC NOTES
154 BLAINE AVE NE, RENTON P02 317961 -1
POLE RETIREMENT TABLE
TEMP TRANSFERS
ST. LIGHT TRANSFERS
SITE
#
POLE DATA
POLE
TEL
TV
FIBER
TRAN
RMVD
ID NUMBER
GRID #
HEIGHT
CLASS
YEAR
TOPPED
RMVD
P01
317959-166495
40
ENGR -GAS
1953
El
El
El
El
❑
❑
❑
Todd Zumwalt
82-6405
66490
30
1977
El
El
El
0
El
El
El
FOREMAN #1
P01: 317969-166495 (Avg. Span =185; < 18*)
- EX. 40 " ,f 1953 POLE TO BE REPLACED
-REPL W/ 40' CL 4 POLE (PD40 ) PER STD 6010-1000 I -1A x I
= INST 1 * DBL PTP (ANG112) PER STD 6031.1020
- INST (2) RIGID CLEVISI (INDNRC)
- TRANSFER 26kVA TRF & L.B. C/O, RETAP (0
M TRANSFER OH SEC (S) & SVCS (E, SE)
- INST (2) 3/819 SPAN GUYS (GYD30W) (W) TO P02, PER STD 6013.0170
- TRANSFER STLT
- TRANSFER AMR '50511'
TOP POLE 1' ABOVE COMM 2429 x I
COMM TO TRANSFER
INST GRID #
P02: 317961-166490 (EX STUB POLE)
EX. 30, 1977 POLE TO BE REPLACED
REPL Wi 30, CL 4 POLE (PS304) PER STD 6010-1100 14A x 1
CONNECT (2) 31891 SPAN GUYS FROM POI (E)
INST 711611 PRI DOWN GUY (GYD7SA) TO EX. ANC (W)
INST GRID #
Scope
REPLACE (2) POLES, LINE & STUB POLE
Please replace b/o 40' single phase line pole set 1953 at grid number
317959-166495, U -map 2305EO65.
Lat/Lon = 47.4842, -122.1894
Budget
Pole replacement will fall under the planned OH Capital Budget. Estimated cost
for this work is:
WBS Element P 10012.06.01.01 - $8,900 CAP
WBS Element P10012.06.02.01-$570 EXP
Chad Hoover, 10/27/16.
1►1
SCALE. -6 "aw"o 1 MILE
POLE TABLE (NEW)
Site
#
Pole Data
Grid #
Height
Class
Year
Remarks /Location Ref.
P01
317959-166495
40
4
N/A
PSE Equip#
P02
317961-166490
30
4
PSE Equip #
rA8 I =3,ARa
23 Sr ***sees 898*20661
ftft oo*% 90 0 0 - ft
Ir .1101%,?4 **A 0008 1 X1 74
100 : No
B 3 0: coo) JVo1'8101
'Sao o* 6
*as
so:
100T 30-
•
AvB :18 30 aon, go 94
X• % X471 0
%lbo •0" 6%swasoor, •oy
to 0 a 03 $11splo•a %
SY a
b *8
OOT ST40T 100T
pose
.. � 3
X•
65 131 G 013
1 10,•1s,
65T "mao a
1 131 M a 6-..,
tX55 2 a "ek : a
65T 11 Be I OOT:: 0* A :A
65T dqd
OOT CO2=5 % T 6002 a 3001
9 @0 28 00*00 0
0 goes 00
X• 30 346 a *609 JOB S1TEe!!o.%
0 so V_ -0 a,
0 ok 5T Wo
045 x769 0 0
•
65T •100T ee* V1 0 030 loans 65T
a
*030
%
30 '030 • 0
rPCR**N coo
V 0 a �J
91
Q4
tOR�A � � �
a
93 •
M04249 •
as
a *a*0
X1 2085 30 %4 %00 U3216
10,
3 %a a
; '�
30 0
3009
% •...,r.,..........
a %A
6 4*
9 J
• tee %
�30 44 *0 00 o4c
a *a % o C
U %
0
0 a so
10
o ga 0
a 060
a A9C 1# B
a
ao
r X11315' . �1- �`30
so a 46 799C
?• VC
4
a 40 400w�
tGRA
8 T
5F 7
lose's
U4641 Nee
131 ***a_
OVERHEAD CIRCUIT MAP (2)305E088
SCALE: 6" = 1 MILE
FOREMAN (CHECK BOX WHEN COMPLETED)
0 PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
0 Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
0 Field Changes RED -LINED on As -built.
0 Material VERIFIED and CHANGES noted on Paperwork.
0 Total PRIMARY Cable noted on As -built.
0 Company IDWs RECORDED in correct location on As -built.
0 Indicate correct FUSE SIZE on As -built & VERIFY, proper PHASE.
0 Deviations noted on the As -built and their reason.
0 1 certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
Foreman's Signature
Print Name Date
PROJECT PHASE
NOTIF#
I
ORDER#
PWR Superior
OH Expense
UG Expense
OH Expense
UG Expense
Removal
11270087
101103202
N/A
583055651
N/A
584....
N/A
593177372
N/A
594....
N/A
108099008
REV# DATE
BY
DESCRIPTION
ENGR -GAS
CABLE TV
N/A
N/A
PHONE
_17
Gas Wk Ctr
IN/A
Project Manager Contact on:
Jeremy Tuntland
(425) 516-3033 Cog Phone
"Locates Required" (SD No
"Outages Requited" Yes (ZD
"Flagging Required" e No
Owner/ Developer Contact Info
PSE I
ATTN: Chad Hoover 81-3279 office
For contacts below dial 1 -888 -CALL PSE (225-5773)
CALL (800) 424-5566
2 BUSINESS DAYS BEFORE YOU DIG
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
REAL
REAL ESTATE/EASEMENT PERMIT
N/A I City Of Rp-ntnn
3
2
FUNCTION
PROJECT MGR
CONTACT
Jeremy Tuntland
PHONE NO
425-516-3033
DATE
12/14/16
1
ENGR -POWER
Carl Buher
425-457-9536
12/14/16
REV# DATE
BY
DESCRIPTION
ENGR -GAS
N/A
N/A
N/A
COUNTY
KING
Emer Sect
NIA
Gas Wk Ctr
IN/A
POWER WK CTR
QCSOKE
DRAWN BY
Todd Zumwalt
82-6405
12/14/16
CHECKED BY .lot
1/4 SEC
NE17 T23N R05E
OP MAP
N/A
PLAT MAP
N/A
APPROVED BY
C___
01.395.64(t
m(Ni/15
FOREMAN #1
U -MAP NO (POWER)
2305E065
OH CKT MAP
2305E088
UG CKT MAP
NIA
ICIRCUIT NO
PRE -12
FOREMAN #2
MAPPING
JOINT FACILITIES ARRANGEMENTS
UTILITIES
CONTACT
PHONE#
COMCAST CENTURYLINK/QWEST
303-992-0935
PUGU
SOUND
ENERV T
DESIGNED BY PSE
PRE -12 REPLACE 1 DISTRIBUTION POLE
REPLACE BAD ORDER POLES
154 BLAINE AVE NE, RENTON, WA 98056
INCIDENT MAOP
NIA N/A
Gas Order Elect Order
NIA 101103202
SCALE PAGE
1##=50' 1/1