MONSTER RD SW
ILLUMiNATION MRING DIAGRAM
{
ILLUMINATION CONSTRUCTION NOTES:
C""11
CONSTRUCT FOUNDATION PER CITY OF RENTON STANDARD PLAN 117.1. FURNISH AND INSTALL NEW POLE, LUMINAIRE, AND CONDUIT PER
ILLUMINATION POLE SCHEDULE, THIS SHEET, AND CITY OF RENTON STANDARD PLANS 7 r7.1, 120, 124, AND 125.
2 CONSTRUCT FOUNDATION PER CITY OF RENTON .STANDARD PLAN 117.2. FURNISH ,AND INSTALL NEW POLE, LUMINAIRE, AND CONDUIT PER
ILLUA41NATION POLE SCHEDULE, THIS SHEET, AND CITY OF RENTON STANDARD PLANS II .2, 120, 124, AND 125.
REMOVE EXISTING STREET LIGRT POLE AND FOUNDATION. FILL AND COMPACT VOID.
RELOCATE EXISTING JUNCTION BOX OUTSIDE OF NEW RAMP LOCATION. EXTEND CONDUITICONDUCTORS TO NEW JUNCTION BOX LOCATION.
LL�T11 IF SUFFICIENT SLACK IS NOT PRESENT, CONTRACTOR SHALL POLL NEW WIRES BACK TO NEAREST SPLICE POINT AND OR SERVICE
CABINET.
f POWER SOURCE UNKNOWN AT TIME OF PLAN PREPRATION. THE CONTRACTOR SHALL COORDINATE WITH P E TO CONFIRM A LOCATION
ll FOR 120 240 VOLT SINGLE PHASE POWER SOURCE CONNECTION INCLUDING COMPLETING ALL FORMS APPLICATIONS AND PAYMENT OF
ALL ASSOCIATED FEES. THE CONTRACTOR SHALL INSTALL CONDUIT AND CONDUCTORS TO TIME POWER SOURCE. PEE ,SHALL MAKE THE
FINAL CONNECTION TO THE POWER SOURCE.
RELOCATE EXISTING LIGHT POLE TO LOCATION SHOWN. CONSTRUCT FOUNDATION PER CITY OF RENTON STANDARD PLAN 115. REMOVE
EXISTING FOUNDATION. FILL AND COMPACT VOID.
ILLLIA41NATION GENERAL NOTES
r. THE LOCATION OF ALL CONDUIT, JUNCTION BOXES, AND CABINETS SHOWN ON TINS PLAN ARE APPROXIMATE ONLY. FINAL
LOCATION SHALL DE DETERMINED 8Y THE CONTRACTOR ,AND CONFIRMED N THE FIELD BY THE ENGINEER.
2. ALL WORD( SHALL BE IN ACCORDANCE WITH THESE PLANS CITY OF RENTON ,STANDARDS AND WSDOT STANDARDS ARID
SPECIFICATIONS, CURRENT EDITION.
J. THE LOCATIONS OF FEATURES SHOWN ARE APPROXIMATE AND SMALL BE VERIFIED IN THE FIELD BY THE CONTRACTOR AS
NECESSARY.
4. THE CONTRACTOR SHALL SUBMIT A REQUEST TO THE CITY OF RENTON FOR MATERIALS APPROVAL AT THE EARLIEST
POSSIBLE DATE.
5. ALL WORK SHALL BE CONSISTENT WITH UTILITY AGENCY REQUIREMENTS. THE CONTRACTOR SHALL CONTACT ALL
PERTINENT UTILITY AGENCIES 48 HOURS BEFORE COMMENCING WORK, AND SHALL COORDINATE WITH AFFECTED UTILITY
AGENCIES THROUGHOUT THE PROJECT.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES. THE CONTRACTOR SHALL NOTIFY
THE AFFECTED UTILITY COMPANY AND THE CITY OF RENTON IMMEDIATELY UPON DAMAGE.
7. POLE FOUNDATIONS SMALL NOT BE EXCAVATED AND POURED BEFORE POLE LOCATIONS ARE APPROVED BY THE ENGINEER.
S. ELECTRICAL CONTRACTOR TO CONTACT CITY CONSTRICTION INSPECTOR FOR INSPECTION OF POLE FOUNDATIONS, BASE
BOLTS, AND CABINET FOUNDATION.
9. CONTRACTOR TO CONTACT CITY ELECTRICAL INSPECTOR FOR UNDERGROUND ROUGR-IN INSPECTION.
10. CONTRACTOR TO CONTACT TRANSPORTATION MAINTENANCE MANAGER FOR STREET LIGHTING COMPLIANCE TO .STANDARDS
INSPECTION PRIOR TO ENERGIZING.
11. FOLLOWING THE TRANSPORTATION MAINTENANCE INSPECTION, THE CONTRACTOR SHOULD CONTACT THE CITY ELECTRICAL
INSPECTOR FOR SERVICE INSPECTION.
12. FOLLOWING THE SERVICE INSPECTION FROM CITY ELECTRICAL INSPECTOR, ELECTRICAL CONTRACTOR SHALL SUBMIT
APPLICATION TO PSE TO ENERGIZE TIDE STREET LIGHTING.
13. ELECTRICAL CONTRACTOR SHOULD CONTACT THE CITY ELECTRICAL INSPECTOR FOR FINAL INSPECTION AFTER ,STREET
LIGHTING HAS BEEN ENERGIZED.
14. PROTECT AND MAINTAIN EXISTING ILLUMINATION CONDUCTORS ALONG PROJECT FRONTAGE.
15. CONTRACTOR SHALL POTHOLE ALL POLE LOCATIONS TO CONFIRM T"AT THEME ARE NO UNDERGROUND CONFLICTS. IF A
CONFLICT IS DISCOVERED. THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO FOUNDATION INSTALLATION.
16. TI4E CONTRACTOR SHALL CONFIRM THAT 10 FEET MINIMUM CIRCUMFERENTIAL CLEARANCE IS PROVIDED BETWEEN
LUMINAIRE POLES AND OVERHEAD POWER LINES. IF A CONFLICT IS DISCOVERED. THE CONTRACTOR SHALL NOTIFY THE
ENGINEER PRIOR TO FOUNDATION INSTALLATION.
r
hlt=a.
CONSTRUCTED
REVISION
BY I DATE I APPR
5UR ETEP;
OESI6NEOc
T. Takara
OMKN;
T. Takara
CHECKS;
C. Bicket
C. Bicket
5DL :
SEE SHEET IL-01 FOR.
i POLE SCHEDULE
SEE SHEET IL-03 & IL-04 FOR:
• CITY STANDARD DETAILS
ILLUMINATION WIRING SCHFDULF
RACEWAY
CONNo. S17E UIT
ILLUM.
r�
SV
POWER
EQt1IP.
ORO* ND
TRACER
4VII2E
1
2" SCH40 PVC
2
r
2
2" EXISTING *
2
1
2" SCH40 PVC
2
r
2" SCH40 PVC SPARS
I
2" ,SCNSO PVC
2
I
4
2" S H80 PVC SPARS
I
5
2" SCH40 PVC SPARS
I
6
2" ,SCH80 PVC
3
7
2" ,SC1480 PVC
4
1
* EOUIPMENT GROUND SIZE SHALL BE EQUAL TO OR LARGER
THAN THE LARGEST WIRE SIZE IN THE CONDUIT.
** OTHER EXISTING CONDUCTORS MAY BE PRESENT.
TAB (ACTUAL
CALCULATION SUMMARY
DESIGN CRITEAA
MIN. AVG.
MAX.
AdAiNTAINED
UNIFORMITY
(FC)
RATIO
CALCULATION AREA
WONSTER RD SW &
1.50
4.00:I
MONSTER IUD SW
(W TERSECTION)
1.56
.60:1
MONSTER RD SW
T.30
4.00:1
(WAJOR ARTERIAL)
1.3
3.30:7
9ONSTER RD SW
0 90
4.00: I
(COLLECTOR ARTERIAL)
3,33:1
SE VICE I 13REAKER SCHEDULE
(NEW SERVICE ON MONSTER IUD SW)
CIRCUIT
BREAKER
CONTACTOR
MAIN
2P- f 00 AMP
---
ILLUM A
2P-20 AMP
30 .AMP
ILLON B
2P-20 AMP
30 AAUP
ILLUMINATION LEGEND
EX NEW
DESCRIPTION
z r
JUNCTION BOX TYPE 2
LUMINAIRE POLE (COR STD
7 r )
LUMINAIRE POLE (COR STD
117.1)
LUMINAIRE POLE (COR STD
117.2)
------
CONOUITCO DUCTOR
®
SERVICE CABINET
0
CONSTRICTION NOTE
0
LU44I AIRE POLE NUMBER
O WAL F+9 u.D 7B HOR3 Ml
1 "=30'
ONE NCH IQATU M
AT FULL SCALE
IF NOT ONE INCH
gfb E ACCORUNCLx
TY rl F
-R %PENT`--!
(D
Planning/Building/Public Work's 1.)�: k
loHSL �
RECORD DRAWING
03-15-2021
RECORD DRAWING NOTE:
THIS CONSTRUCTION RECORD DRAWING IS A COPY
OF THE APPROVED CONSTRUCTION DRAWINGS
PREPARED BY INNOVA ARCHITECTS AND HAS BEEN
EDITED TO REFLECT ASBUILT CONDITIONS. THE
INFORMATION PROVIDED ON THESE RECORD
DRAWINGS IS A COMBINATION OF FIELD SURVEYED
75 60
0 .30 90
CALL
IPTENW
Iran SpQ Fli OT io ri Lrig111E .rinig. I'wQnri %ti aQ 1
rarss arrtrtiorn P€aruxng 1 be grt 1 7rafk rmpa-cr &op
11400 5E &M 5[fee h SOre 2W. Be&� vuo. WA %COd
Offioa (4251 8894u7
?"OCr C.onro& ltavd RAffo. P.E.
Maw; �25 2S»�865
ient
f y
PROLOGIS
12720 Gateway Dr., Suite 110
Tukwila, WA 98168
206- 14-7825
INFORMATION AND DOCUMENTED FIELD REVISIONS. T-404202
IN COMPLIANCE WITH CITY OF RENTON N T ND f D
TRANSPORTATION OPERATION 4 �.
cbarnes 07/31/2019 ;:
DEVELOPMENT ENGINEERING