HomeMy WebLinkAboutS-226314PROPOSED ELECTRICAL
B
MOl
EQUIPMENT. SEE DWG LE4.
-
INTAKE LOUVER -�
j\
i
TRAILER WHEEL GUIDES. 2"
36" MIN
x 1/4" STAINLESS STEEL
BOLTED TO FLOOR WITH
LEVELING
112" x 4" ANCHOR BOLTS.
_
JACK
f
PROPOSED ELECTRICAL
BUILDING CEILING
EQUIPMENT. SEE DWG LE4.
-
HOSE CLEAR OF ENGINE GENERATOR
j\
i
TRAILER WHEEL GUIDES. 2"
x 2"
x 1/4" STAINLESS STEEL
BOLTED TO FLOOR WITH
ANGLE
(9)
112" x 4" ANCHOR BOLTS.
TYPICAL BOTH SIDES. LOCATE
2" AWAY FROM TIRES
AFTER
GENERATOR IS IN PLACE.
i
4" YELLOW GUIDANCE STRIPS
20
PAINTED ON FLOOR. PAINT
BE INSTALLED AFTER ENGINE
GENERATOR IS IN PLACE.
TO _
FIRE EXTINGUISHER AND FIRST
AID KIT TO BE MOUNTED ON
WALL, CLEARLY VISIBLE.
RAIN CAP SHALL BE A
MINIMUM OF 12" ABOVE ROOF \
AT THE MOUNTING BRACKET.
STAINLESS STEEL MOUNTING
BRACKET. EXHAUST PIPE
SHALL BE A MINIMUM OF 6"
FROM EAVE.
EXISTING TR
MOUNTED El
GENERATOR 1
DELIVERED TO SI1
THE CITY OF REI
LEVELING JACK
EXHAUST �-
ASSEMBLY
LING JACK
rmurUxu L nv,U
ACCESS DOOR.
EXHAUST SLIP FIT BELL
AND HANG 6' STEP
X IADOFR ON WALL
ED ELECTRICAL
NT. SEE DWG LE4.
48 "w x 60 "h MOTOR OPERATED
DAMPER. LOUVERS AND
DAMPERS, INC. MODEL AF4 -P
OR APPROVED EQUAL.
ROOF
EXHAUST ASSEMBLY. SEE
3/8° RIGHT ANC
PIPE CLAN
w x 60 "h x 8 "d MOTOR
=RATED ACOUSTICAL INTAKE
1VFR. LOUVERS AND
APERS, INC. MODEL ACF -C1
APPROVED EQUAL. INCLUDE
D SCREEN. LOUVER TO
-N ON STARTUP OF EXHAUST
J.
PROVIDE EYEBOLT SECURED IN RAFTER
BUILDING CEILING
AND WIRE TO HOLD FLEXIBLE EXHAUST
-
HOSE CLEAR OF ENGINE GENERATOR
BUILDING WALL
WHILE BEING REMOVED_
\
EXHAUST FAN
'\ G
\�
STAINLESS STEEL FLEXIBLE EXHAUST
HOSE EQUAL TO MICROFLEX AF -SSDE
HOSE WITH INSULATION JACKET. 'WELD 4
1
BOLT FLANGE TO EACH END OF FLEXIBLE
HOSE. LENGTH AS NECESSARY.
20
EXHAUST ASSEMBLY
EXHAUST FAN ASSEMBLY
WHEEL GUIDES �\
(2) TIRE BLOCKS DOTH SIDES
ENGINE GENERATOR ELEVATION Mot
SCALE 1" = 2' -0"
3/16 STAINLESS HANGER
CABLE. LAG BOLT TO
RAFTERS. (TYP.)
MAX. SPAN 54" (TYP.)
TYPICAL 4 BOLT FLANGE
WELDED TO EXHAUST PIPE.
1" FIBERGLASS EXHAUST
INSULATION BLANKET. BLANKET
SHALL RATED TO WITHSTAND A
MINIMUM TEMPERATURE OF
1200'F. WRAP ENTIRE INTERIOR
EXHAUST SYSTEM WITH
4 BOLT FLANGE (TYP.) INSULATION BLANKET.
ENGINE EXHAUST DETAIL
SCALE 1" = 1' -0"
EXHAUST HANGERS (TYP.)
6' STEP LADDER
GUIDANCE STRIPES
ENGINE GENERATOR VIEW
INTAKE LOUVER
`\ BUILDING FLOOR AND
l STEM WALLS
WALL THIMBLE WITH
BUGSCREEN. PER NFPA
STANDARDS.`
t
R\
STAINLESS STEEL EXHAUST PIPE_
MINIMUM DIAMETER = 4 ". SEE
SIZING NOTE BELOW.
,�- ENGINE GENERATOR
ENGINE GENERATOR NOTES,
1. ALL EXHAUST COMPONENTS SHALL BE
STAINLESS STEEL EXHAUST COMPONENT SIZES
SHALL BE NO SMALLER THAN PRESENT IN THE
EXISTING ENGINE GENERATOR.
2. CONTRACTOR SHALL VERIFY EXHAUST
LOCATION ON EX(STTNG ENGINE GENERATOR PRIOR
TG C- USFRUCTION Of BUILDING EXHAUST SYSTEM.
CONSTRUCT EXHAUSC SYSTEM! TO, MATCH
LOCATION OF EXISS iimi ----- t GENERATOR
EXHAUST WHILE IN PARKED POSITION.
3. CONTRACTOR SHALL COORDINATE WFIH THE
CITY OF RE14TON TO OBTAIN SPECIFIC ,
INFORMATION REQUIRED FOR THE COMPLETE
INSTALLATION OF THE ENGINE GENERATOR.
J
BUILDING CEILING
-
-
TRAILER MOUNTED HANGERS
BUILDING WALL
ENGINE GENERATOR
EXHAUST FAN
NOT TO SCALE
NOTE: CONTRACTOR SHALL f— 20" --I 8"
PROVIDE ADEQUATE SUPPORT FOR
NOT TO SCALE
REVISED TO CONFORM
TO CONSTRUCTION RECORDS
MARK MILLER 10/24/00
RH2 ENGINEERING INC. DATE
O F�R 2�99
w
I
EXHAUST FAN AND LOUVER
NOT TO SCALE
ASSEMBLY.
ROLL UP DOOR. SEE unG. N0.
20
C06 FOR DOOR DETAILS.
(2) GALVANIZED °C' CHANNELS GRAVITY OPERATED COUNTER
EXHAUST LOUVER
30" LONG_ LAG BOLT TO A BALANCED BACKDRAFT DAMPER.
MINIMUM OF 2 RAFTERS. LOUVERS AND DAMPERS, INC.
MODEL CBC OR APPROVED
EXHAUST FAN ELEVATION
EQUAL. SIZE TO FIT IN
B
M O1
DUCTWORK DIRECTLY ADJACENT
"'- TO FAN.
SCALE 1" = 2' -0"
DOOR
48" x 48" x 12" ACOUSTICAL
��
1
3;16" GALVANIZED STEEL
CABLE HANGERS. ATTACH EYE
LOUVER. LOUVERS AND
DAMPERS, INC. MODEL ACF -C1
f
BOLTS TO EACH END.
OR APPROVED EQUAL.
REVISED TO CONFORM TO CONSTRUCTION RECORDS
DMB
MLM 10
FAN INTAKE SCREEN.
NO.
REVISION
BY
REVIEW1 I
EXHAUST FAN. KANALFLAKT MODEL
KDS26 OR APPROVED EQUAL. FAN
BE RATED TO SUPPLY 6500
RH2 ENGINEERING, INC.
F a H.
s�
Gab °y
CFM AT 0.125 IN OF WATER.
tNG i N E_ R S BOTHELLOFFICE
_
TRANSITION DUCT WORK. SEE
N N E R S
JBBER MAT TO
ACK STAND FLANGE
DETAIL THIS SHEET.
NTISTS EAST WENATCHEE OFFICE
.9, 16727
Rg rstsI -P S.
'8" CARRIAGE BOLTS.
ONAL 01
K BOLTS INTO RUBBER
DRAWING IS NOT i0 SCALE
EXPIRES 8 2 O1
0
VAN SURFACE ON EXHAUST FAN OBLIQUE
F BAR IS NOT 2" LONG
LANGE. (3 TYPICAL)
y-.1.,
„1 �. ,,
NOT TO SCALE
REVISED TO CONFORM
TO CONSTRUCTION RECORDS
MARK MILLER 10/24/00
RH2 ENGINEERING INC. DATE
O F�R 2�99