GENERAL CONSTRUCTION NOTES:
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE NTH THE CITY OF RENTON
CONSTRUCTION STANDARD DETAILS, MATERIALS UST AND THE MOST CURRENT COPY
OF THE STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD, BRIDGE, AND MUNICIPAL
CONSTRUCTION ( WSDOT /APWA).
2. ALL APPROVALS AND PERMITS REQUIRED BY CITY OF RENTON SHALL BE OBTAINED BY
THE CONTRACTOR PRIOR TO THE START OF CONSTRUCTION INCLUDING WAC 332 -120. ABSENCE
OF THE PERMIT MAY RESULT IN AN IMMEDIATE SHUT DOWN OF WORK AND POSSIBLE REMOVAL
OF THOSE ITEMS CONSTRUCTED WITHOUT THE PERMIT.
3. THIS PLAN MAY NOT SHOW ALL EXISTING UTILITIES. EXISTING UTILITY LOCATIONS SHOWN ARE
APPROXIMATE. PRIOR TO CONSTRUCTION, THE CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL
UNDERGROUND UTIUTIES. CALL THE UNDERGROUND UTIUTY LOCATION SERVICE AT
(800) 424 -5555 A MINIMUM OF 2 BUSINESS DAYS PRIOR TO EXCAVATION BEFORE YOU DIG.
ANY CONFLICTING UTIUTIES SHALL BE RELOCATED PRIOR TO CONSTRUCTION.
4. ALL FINISHED GRADING ELEVATIONS SHALL MATCH EXISTING ELEVATIONS AT THE SITE'S
BOUNDARY, EXCEPT AS SHOWN OTHERWISE IN THE GRADING PLAN. WHERE CONFLICTS EXIST, THE
CONTRACTOR SHALL NOTIFY OWNER TO RESOLVE THE ISSUE PRIOR TO PROCEEDING.
5. GRADING: ALL GRADING SHALL BE LIMITED TO THE AREAS IDENTIFIED IN THE GRADING PLAN AND
SHALL NOT INFRINGE ON ADJACENT OWNERSHIPS.
6. THE CONTRACTOR SHALL HAVE A RESPONSIBLE PARTY WHO SHALL HAVE THE AUTHORITY TO
REPRESENT AND ACT FOR THE CONTRACTOR AT THE JOB SITE DURING ALL WORKING HOURS
7. CUT SLOPES IN SOLID ROCK SHALL NOT EXCEED %:1 (HORIZONTAL VERTICAL), AND SOIL CUT
SLOPES SHALL NOT EXCEED 2:1 (HORIZONTAL- VERTICAL), EXCEPT AS SHOWN OTHERWISE IN THE
PLANS.
B. FILL SLOPES ACROSS THE PROPERTY SHOULD BE DESIGNED FOR A MAXIMUM SLOPE OF 2:1
(HORIZONTAL VERTICAL), EXCEPT AS SHOWN OTHERWISE IN THE PLANS.
9. CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR AND EQUIPMENT TO CONSTRUCT AND
INSTALL IN PROPER WORKING ORDER, THE DESIGN SHOWN, AS DETAILED OR CALLED OUT IN
THESE PLANS AND SPECIFICATIONS. THE CONTRACTOR SHALL BE FULLY RESPONSIBLE FOR BEING
FAMILIAR NTH THE PROVISIONS AND REQUIREMENTS CONTAINED IN THE CITY OF RENTON
CONSTRUCTION STANDARD SPECIFICATIONS.
10. CONTRACTOR SHALL PROVIDE TRAFFIC CONTROL PLAN(S) IN ACCORDANCE WITH THE MANUAL ON
UNIFORM TRAFFIC CONTROL DEVICES (MUTCD) AS REQUIRED. PRIOR TO DISRUPTION OF ANY
TRAFFIC, A TRAFFIC PLAN SHALL BE PREPARED AND SUBMITTED TO THE ENGINEER FOR
APPROVAL. NO WORK SHALL COMMENCE UNTIL ALL APPROVED TRAFFIC CONTROL ISIN PLACE.
11. ALL CURB AND GUTTER, STREET GRADES, SIDEWALK GRADES, AND ANY OTHER VERTICAL AND /OR
HORIZONTAL ALIGNMENT SHALL BE STAKED BY AN ENGINEERING OR SURVEYING FIRM CAPABLE
OF PERFORMING SUCH WORK.
12. WHERE NEW ASPHALT JOINS EXISTING, THE EXISTING ASPHALT SHALL BE CUT TO A NEAT
VERTICAL EDGE AND TACKED NTH ASPHALT EMULSION TYPE CSS -11N ACCORDANCE NTH THE
CITY OF RENTON STANDARD SPECIFICATIONS. THE NEW ASPHALT SHALL BE FEATHERED
BACK OVER EXISTING TO PROVIDE FOR A SEAL AT THE SAW CUT LOCATION AND THE JOINT
SEALED WITH GRADE AR -4000W PAVING ASPHALT.
13. FORM AND SUBGRADE INSPECTION BY THE INSPECTOR IS REQUIRED BEFORE POURING CONCRETE.
TWENTY -FOUR HOURS NOTICE IS REQUIRED FOR FORM INSPECTION.
14. ALL TESTING TO BE IN ACCORDANCE NTH THE CITY OF RENTON CONSTRUCTION
STANDARDS AND WSDOT STANDARD SPECIFICATIONS.
15. THE CONTRACTOR SHALL PROVIDE THE DESIGN ENGINEER NTH RECORD DRAWINGS PRIOR TO
FINAL APPROVAL. ALL DEVIATIONS FROM THE ORIGINAL PLANS MADE DURING THE COURSE OF
THE CONSTRUCTION INCLUDING LOCATIONS, INVERTS, AND DEPTHS OF UTILITIES SHOULD BE
CLEARLY MARKED ON THE RECORD DRAWINGS.
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CLEANING DIRT, MUD, AND OTHER CONSTRUCTION
DEBRIS, WHICH MAY ACCUMULATE ON PAVED STREETS ADJACENT TO THE SITE AS A RESULT OF
THE CONSTRUCTION ACTIVITY. CLEANING SHALL BE ON AN "AS NEEDED" BASIS.
17. THE ENGINEER HAS ATTEMPTED TO SHOW ALL EXISTING UNDERGROUND UTUTES
STRUCTURES. APPEARANCE ON THESE PLANS, HOWEVER, DOES NOT GUARANTEE THE ACCURACY
AND COMPLETENESS OF THE LOCATION OR EXISTENCE OF THESE UTILITIES AND /OR
SUBSTRUCTURES. THE CONTRACTOR IS REQUIRED TO TAKE ALL REQUIRED PRECAUTIONARY
MEANS TO LOCATE AND PROTECT ALL EXISTING UTILITIES AND SUBSTRUCTURES WHETHER SHOWN
OR NOT, PRIOR TO EXCAVATION IN ANY AREA. THE CONTRACTOR SHALL MEET AT THE JOB SITE
WITH REPRESENTATIVES OF THE UTIUTY DISTRICTS OR COMPANIES AND OTHER OWNERS WHICH
MAY HAVE EXISTING FACILITIES AND TO DISCUSS THEIR PROTECTION.
18. EXCAVATION AND EMBANKMENT SHALL BE IN ACCORDANCE WITH APPLICABLE REQUIREMENTS OF
THE CITY OF RENTON STANDARD SPECIFICATIONS. ALL COMPACTION OF SUBGRADE, ROCK,
AND ASPHALT SHALL BE IN ACCORDANCE WITH CITY OF RENTON CONSTRUCTION
STANDARD SPECIFICATIONS.
19. IF CONSTRUCTION IS TO TAKE PLACE IN THE CITY RIGHT -OF -WAY, THE CONTRACTOR SHALL
NOTIFY THE CITY AND OBTAIN ALL THE REQUIRED APPROVALS AND PERMITS. LANDSCAPE
UNIMPROVED PORTIONS OF THE CITY RIGHT -OF -WAY PER THE CITY OF RENTON
CONSTRUCTION STANDARD SPECIFICATIONS.
20.A PRECONSTRUCTON MEETING SHALL BE HELD WITH THE CITY OF RENTON CONSTRUCTION
INSPECTOR PRIOR TO THE START OF CONSTRUCTION.
21. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO HAVE A COPY OF THESE APPROVED PLANS
ON THE CONSTRUCTION SITE AT ALL TIMES.
22. ANY CHANGES TO THE DESIGN SHALL FIRST BE REVIEWED AND APPROVED BY THE PROJECT
ENGINEER AND CITY OF RENTON'S ENGINEERING DEPARTMENT.
23, PRIOR TO BACKFILL ALL MAINS AND APPURTENANCES SHALL BE INSPECTED AND APPROVED BY
THE CITY OF RENTON CONSTRUCTION INSPECTOR. APPROVAL SHALL NOT RELIEVE THE
CONTRACTOR FOR CORRECTION OF ANY DEFICIENCIES AND /OR FAILURES AS DETERMINED BY
SUBSEQUENT TESTING AND INSPECTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY THE CITY OF RENTON FOR THE REQUIRED INSPECTIONS.
24. THE CIVIL DRAWNGS SHALL NOT BE USED TO LOCATE THE BUILDING. BUILDING SHALL BE
LOCATED USING ARCHITECTURAL PLANS.
WATER UTILITY NOTES & SPECIFICATIONS
1. THESE NOTES SHALL APPEAR FOR PROJECTS FOR THE WATER UTILITY.
2. ALL WORK MATERIAL SHALL BE IN CONFORMANCE NTH THE STANDARDS AND SPECIFICATIONS OF THE CITY
OF RENTON PLANNING /BUILDING /PUBUC.WORKS. DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA
STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON
STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES
DURING CONSTRUCTION.
3, THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 'AM TO 3:30 PM ON
WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE DEPARTMENT OF PUBLIC WORKS AT
(425)..430 -7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE N01IFlED 24 HOURS IN
ADVANCE OF ANY WORK IN THE RIGHT OF WAY.
4. ALL LOCATIONS OF EXISTING UTILITIES. SHOWN ARE APPROXIMATE: AND IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE.
FOR UTILITY LOCATES CALL 48 -HOURS LOCATORS, 1- 800 - 424 -5555. - -
5.
AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE - CONSTRUCTION MEETING.
6.
ALL WATER MAIN PIPE TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO -AWWA C110 AND C111 OR
LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO
AWWA C104 OR LATEST REVISION. PIPE JOINTS TO. BE .PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE
CLASS C. ALL DUCTILE IRON PIPE AND FITTINGS. SHALL BE POLYETHYLENE WRAPPED : PER ANSI /AWWA
7. C105/A21.5 -93 STANDARDS. - -
CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS,
AND IN ACCORDANCE WITH ANSI /AWWA C110/A21.10- 87. CEMENT LINING SHALL BE IN ACCORDANCE NTH -
ANSI/AWWA C104/421/4 -90. IF FITTINGS ARE 3 INCHES TO 12 INCHES IN DIAMETER AND HAVE
MECHANICAL JOINTS, THE FITTINGS SHALL BE IN ACCORDANCE WITH EITHER ANSI /AWWA C110- A21.10 -87
OR ANSI /AWWA C153/A21.53 -94. THREE (3) INCH TO 12 INCH DIAMETER FITTINGS WHICH HAVE MECHANICAL
JOINTS AND /OR FLANGED JOINTS SHALL BE IN ACCORDANCE WITH ANSI /AWWA C110/A21.10.87 OR A :
COMBINATION OF ANSI/AWWA C110 /A21.10.87 AND ANSf /AWWA C153/A21.53-94 SUCH THAT THE PORTION
OF THE FITTING NTH A MECHANICAL JOINT(S) AND /OR FLANGED JOINT(S), MAY BE IN ACCORDANCE 'NTH
ANSI /AWWA C153/A21.53 -94 AND THAT PORTION OF THE FITTING WITH FLANGED JOINT(S) SHALL BE IN
ACCORDANCE WITH ANSI /AWWA C110/A21.10 -87. ACCEPTANCE TESTING IN ACCORDANCE NTH SECTION.
B. 53.53 OF ANSI /AWWA SECTION 10 -4.3 OF ANSI /AWWA C110/A21.10 -87 SHALL BE OBTAINED BY THE
CONTRACTOR AND TRANSMITTED TO THE OWNER.
GATE VALVES SHALL BE IRON BODY, BRONZED - MOUNTED, DOUBLE DISC .WITH BRONZE WEDGING DEVICE AND
0 -RING STUFFING BOX (AWWA C500) OR OF RESILIENT SEAS TYPE (AWWA C509). VALVES SHALL BE
9. DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI GATE VALVES SHALL BE CLOW LIST
14, MUELLER COMPANY NO A2380, OR M & H.
FIRE HYDRANTS SHALL BE COREY TYPE (OPENING NTH THE PRESSURE) OR COMPRESSION TYPE (OPENING
AGAINST PRESSURE) CONFORMING TO AWWA -C- 502 -85 WITH A 6 INCH MECHANICAL JOINT INLET AND A'
MAIN VALVE OPENING (M.V.O.) OF 5 -1/4 INCHES, TWO 2 -1/2 INCH HOSE NOZZLES NTH NATIONAL
STANDARD THREADS 7 -1/2 THREADS PER INCH AND ONE 4INCH PUMPER NOZZLE NTH THE NEW SEATTLE
10. PATTERN 6 THREADS PER INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875
AND ROOT DIAMETER 4.6263. HYDRANTS SHALL HAVE A 1 -1/4 INCH PENTAGON OPERATING NUT OPENED BY
TURNING COUNTER CLOCKWISE (LEFT).
11. THE TWO 2 -1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS NTH OPERATING
NUT OF THE SAME DESIGN AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED NTH
SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS UNDER TEST PRESSURES:
THE 4 INCH PUMPER NOZZLE SHALL BE FITTED NTH A STORZ ADAPTER, 4 INCH SEATTLE THREAD X 5 INCH
STORZ. STORZ ADAPTER SHALL BE FORGED AND /OR EXTRUDED 6061 -T6 ALUMINUM ALLOY, HARDCOAT
12. ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND 2 SET SCREWS 180 DEGREES APART.
STORZ FACE TO BE METAL, NO GASKET TO. WEATHER. STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER
GASKET, AND SHALL BE ATTACHED TO HYDRANT ADAPTER NTH 1/8 INCH COATED, STAINLESS STEEL,
13. AIRCRAFT CABLE.
14• FIRE HYDRANTS SHALL BE PAINTED WITH. TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43 -655
15. SAFETY YELLOW OR APPROVED EQUAL
PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, LATEST
16. REVISION.
ALL WATERMAIN 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH
GRADE. ALL WATERMAIN 12 INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH
17. GRADE. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS ARE TO BE LOWERED TO CLEAR.
ALL WATER MAINS 6 INCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING "PIGS"
18. PRIOR TO DISINFECTION. THE "POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVE)
EQUAL, 2 LB /CU. FT. DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER COATING ON THE REAR OF
"PIG" ONLY.
"PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM
THE CLEANING OPERATION.
19. ALL WATERMAINS AND SERVICES SHALL BE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING
PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON
STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A
REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT
EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS AND
SPECIFICATIONS 7- 11.3(11). THE LOSS IN PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST
PERIOD.
ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM (MINIMUM
CONCENTRATION) CHLORINE /WATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE
PIPE AS LAID. CHLORINE SHALL BE METERED /INJECTED IN ACCORDANCE NTH SECTION 7- 11.3(12)E OR
7- 11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED ABOVE.
13 A. g�
CO,
CITY COMMENTS
CITY COMMENTS
y�0028g0 CITY COMMENTS
ZONAL'1 AS BUILT
EXPIRES 9/27/2008 N0. REVISION
ROLE 207 0
20. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A
MINIMUM OF 5 (FIVE) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING.
21. TWENTY -FOUR HOUR NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
22 IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS
PRIOR TO STARTING - CONSTRUCTION. - 23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES; LINES AND METERS SHALL NOT
- BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS, CONSTRUCTION PERMITS,
AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON. -
24. ALL CONNECTION TO EXISTING MAINS TO BE ACCOMPLISHED BY THE CITY OF RENTON,
EXCEPT WET TAPS WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS WITH
PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION
AND MATERIALS TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY
NOTIFICATIONS.
25.
INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT
SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES
TWENTY- FOUR (24) HOURS IN ADVANCE OF BACKFIWNG ALL CONSTRUCTION. THE
26, CONTRACTOR, AS WELL AS THE ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS.
CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING
27. AND PURITY ACCEPTANCE PRIOR TO FINAL TIE -IN.
ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS
28_ MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO OR EQUAL
APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT.
ASPHALT AND CONCRETE STREET PAVING SHALL BE SAVICUT TO A MINIMUM DEPTH OF
TWO (2) INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE CONCRETE,
29, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT
TO A MINIMUM DEPTH OF TWO (2) INCHES OR REMOVED TQ AN EXISTING EXPANSION JOINT.
A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL
30. EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO CITY OF RENTON
POLICY, WITHIN TEN DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF
FINAL PATCH.
FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED FOR ALL
CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE. SCHEDULE 40 IN
UNIMPROVED AREAS AND SCHEDULE 80 PVC UNDER IMPROVED AREAS.
DAS
OO" JJS-
OARR IF NOT ONE 'ICI
a
SANITARY SEWER NOTES & SPECIFICATIONS
1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE NTH THE STANDARDS AND SPECIFICATIONS
OF THE CITY OF RENTON UTILITY DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA
STANDARDS AND SPECIFICATIONS.
2. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR
MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE CHAPTER
AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON
STANDARD SPECIFICATIONS.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTORS RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID
DAMAGE OR DISTURBANCE.
4. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE.
5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER
RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
6. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT, SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS.
7. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS
IN PROGRESS.
8. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWANG OF THE
SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED
PROFESSIONAL ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
9. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE M LAYERS NTH A LOOSE
AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THORCUGHLY TAMPING EACH
LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR
ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS
TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED.
10. OPEN CUT ROAD CROSSINGS FOR UTIUTY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE
BACKFILLED NTH CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING
ASPHALT SHALL BE NEATLINE CUT WITH SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH
MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX
PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT
STANDARDS.
11. DATUM SHALL BE CITY OF RENTON, 1988 NAVD.
12. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE
SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION AFTER THE
COMPLETION OF CONSTRUCTION.
13. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE NTH SECTION 7 OF THE CURRENT STATE OF WASHINGTON STANDARD
SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY
LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS
PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL, TO UNIFORM GRADE SO THAT
THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING
BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6 INCHES ABOVE AND BELOW THE PIPE.
14. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034,
SDR 35, OR DUCTILE IRON CLASS 50.
15. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES
ABOVE FINISHED GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH
PAVING.