HomeMy WebLinkAboutS-343603PACKAGE W/ SRA - 125 -CV LIFTOUT
CONCRETE BASIN, COMPONENTS AS AVAILABLE FROM
BECKWITH & KUFFEL, (206) 767 -6700
CONTACT: JAMES BURKHART
CONTROL PANEL - MYERS MODEL CGNC- 30 -43DW
COORDINATE LOCATION ON EXTERIOR WALL WITH ARCHITECT.
COORDINATE WITH ELECTRICAL TO ENSURE THAT HIGH WATER
ALARM AND PUMP FAIL ALARM ARE ROUTED TO EMCS.
MODEL THS 24" X 36" ACCESS HATCH W/ ODOR
REDUCTION GASKET, ALUM W/ BIT PAINT, H -20 FOR
OCCASSIONAL TRAFFIC AS AVAILABLE FROM
B. L. WILCOX & ASSOC. 562- 693 -2787
CONTACT: HANK FLEISCHER
VI \11 tlVLI\ i LJIVII , L I 1 \L%X V
MYERS MODEL W 20 -43 -15 2HP 3/60/460v PUMP,, EXPLOSION PROOF
I EL W/ GRADING
NEC TO ACHIEVE
ON PAVEMENT
VE EXTENSION HANDLE
✓�'4 'PV CN 2 RI Q� D N )
F RAIL KIT, (2) REQ'D
=RS SRAX -1 25 NON- SPARKING
26.50 0 PIPE CENTERLINE
DISCHARGE LEVEL
LIFTOUT CHAIN, 1/4 $$ $ SST (2) REQ'D
LIFT BAIL, SST (2) REQ'D
1 1/4 " DI CHARgE PIPE, PVC
SCH.801 (2 ) REQ D
MYERS "SRA -1 25 -CV" LIFTOUT
(W /CHECK VALVE) (2) REQ'D
PUMP STATION DETAILS
NOT TO SCALE
SYM I REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE
BOEING 10 -080 HUB RECORD DRAWING J# 140898 -01 RFA RF 06.29.07
mo
ACCEPTABILITY
THIS DESIGN AND /OR
SPECIFICATION IS APPROVED
APPROVED BY I DEPT. I DATE
,LVE, PVC
OCKED TYPE
16UNC X 2 LG.
DR , STU D
EQD.
SUBTITLE
SANITARY SEWER PUMP STATION DETAILS
TITLE 10 -080 HUB SHELL & UTILITY SEPARATION
BUILDING 10 -080 HUB
CIVIL MASTER
RENTON, WA
J# 140898 -01
C505
J# 140898 -01 c
10- 080 —0505