HomeMy WebLinkAboutS-347352SPUCE LENGTH FOR REINFORCING BARS IN WALLS & SLABS (INCHES) 1'2.3,5 BAR SIZE CONC COVER =1.00 IN. CONC COVER =1.50 IN. CONIC COVER =2.00 IN. SOFT INCH TOP OTHER TOP OTHER TOP OTHER METRIC POUND #10 #3 17 16 17 16 17 16 #13 #4 23 17 23 17 23 17 #16 #5 33 26 28 22 28 22 #19 #6 46 35 34 26 34 26 #22 #7 74 57 55 43 49 38 #25 1 #8 1 93 1 72 1 70 1 54 56 43 #29 #9 113 87 86 66 69 53 #32 #10 137 106 105 81 85 66 #36 #11 162 125 125 97 102 79 NOTES: 1. LAP SPLICE LENGTHS ARE DEPENDENT ON THE FOLLOWING CRITERIA AND ARE IN CONFORMANCE WITH ACI 318 -05. NOTIFY THE DESIGN ENGINEER IF THERE ARE ANY DIFFERENCES THAN THE FOLLOWING CRITERIA FOR APPLICABLE CHANGES IN LAP SPLICE LENGTH. 2. LAP SPLICE LENGTHS ARE IN INCHES FOR GRADE 60 REINFORCING IN NORMAL - WEIGHT CONCRETE WITH f'c GREATER THAN OR EQUAL TO 3,000 PSI. 3. CENTER -TO- CENTER SPACING OF REINFORCING SHALL BE GREATER THAN TWICE THE CONCRETE COVER PLUS ONE BAR DIAMETER. 4. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 IN. OF CONCRETE CAST BELOW BARS. 5. FOR EPDXY - COATED REINFORCING OR LIGHTWEIGHT AGGREGATE CONCRETE CONSULT THE DESIGN ENGINEER FOR LAP SPLICE LENGTHS. TOP LAYER 3/4" BELOW TOP OF SLAB INTERIOR CORNERS SAND BLAST AND CLEAN SEE SPECIFICATION - OTHERWISE PROVIDE KEY WHEN CJ IS LOCATED WITHIN 113 SPAN FROM FACE OF SUPPORT 4'-0" 5 -#4 F_ WALL -WALL 0 4" CC, TOP JOINT SEALANT A" ADD #4x4' -0" STANDARD 12" (T &B WHEN NO KEY SEE VIV�SIDE OTHER HORIZONTAL / OF SL B DETAIL 7 REINF IS INDICATED) BACKER ROD- _. - S2 XTRA #4 X PRE- FORMED JOINT ONT AT EACH FILLER CJ EDGE OF SLAB WALL -SLAB SLAB -SLAB NOTES: EXTERIOR CORNERS 1. REINFORCING STEEL IS CONTINUOUS THROUGH CONSTRUCTION JOINTS. 2. SEE SPECIFICATION FOR CONCRETE SURFACE PREPARATION. ADJ WALL CONC 7Z OR SLAB SLAB ON GRADE D o D a u a a u a u a u u u u a Q a TYPICAL ADDITIONAL I CONSTRUCTION JOINT CONCRETE REINFORCEMENT SPLICE TABLE 1 REINFORCING FOR SLAB CORNERS WITHOUT WATERSTOP EXPANSION JOINT SCALE: NTS SCALE: NTS \ J SCALE: NTS M—SCALE: NTS IN— #3012- EW, H LESS THAN 8" #4012" EW, H BETWEEN 8" & 16" #5®12" EW, H MORE THAN 16" #3 ®12" EW, H LESS THAN 8" I�72' 3/4" CHAMFER VERTICAL EDGES #4 ®12" EW, H BETWEEN 8" & 1 /(TYP) - - - - - - — \' 112 "1 #5 ®12" EW, H MORE THAN 16" ROUGH CJ v _ _ °�-!° ROUGH CJ (N) CONC SLAB (E) CONC ° d (TYP.) SLAB a #4 n AT 12 ", H MORE THAN #5 DOWEL IN ADHESIVE #4 012" H LESS THAN 16" CAPSULE ® 12" CC STANDARD HO #5012" H 16" OR MORE ON EXISTING CONCRETE SLAB ON NEW CONCRETE SLAB Nom( I� 0 1. PLACE ALL EQUIPMENT ON CONCRETE BASES. co 2. SEPARATE ALL STEEL SURFACES BEARING ON CONC BY A GROUT LAYER. 3. FOR INSTALLATION AT EXISTING SLABS, THE CONTRACTOR ^I SHALL LOCATE AND AVOID DRILLING THIRD EXISTING REINFORCING STEEL. TYPICAL EQUIPMENT PAD SCALE: NTS W s a z 0 0 N Z O N K W V W 3 c ILL z Roth Hill, LLC Te1425.869.9448 www.rothhill.com 0 11130 NE 33rd Place, Suite 200 Bellevue, WA 98004 a Kennedy /Jenks Consultants 32001 32nd Avenue South, Suite 100 Federal Way, WA 98001 Ph. 253- 835-8400 Fax 253- 952 -3435 SAWED JOINT (1/8 "- 1/16 ") W/ CAULK IF SPECIFICALLY NOTED ON DRAWINGS a L d r p NO WATERSTOP OR DOWELS AT JOINT NOTES: 1. IF SINGLE LAYER REINFORCEMENT, EVERY OTHER BAR IS DISCONTINUOUS AT JOINT. 2. IF 2 LAYER REINFORCEMENT, TOP LAYER IS COMPLETELY DISCONTINUOUS AT JOINT. 3. JOINT FORMED WITH TOOL OR INSERT STRIP MAY BE SUBSTITUTED FOR SAWED TYPE ONLY WITH PRIOR ACCEPTANCE BY THE ENGINEER. 4. SAWED JOINT MUST BE CONSTRUCTED WITHIN 12 HOURS OF CONCRETE PLACEMENT. TYPICAL CONTROL JOINTS SCALE: NTS NO. REVISION } u w Yo CONSTRUCTION JOINT \Jn NOTES: 1. KEYS ARE REQUIRED FOR HORIZONTAL CONSTRUCTION JOINTS. 2. FOR SUSPENDED SLABS, PROVIDE A KEY FOR AT LEAST 50% OF THE CONSTRUCTION JOINT LENGTH. THICKNESS OF SLAB OR WALL "A" NOMINAL KEY SIZE D x W LESS THAN 8" 2x3 9" TO 12" 2x4 13" TO 18" 2x6 19" TO 24" 2x8 MORE THAN 24" 2x12 TYPICAL LONGITUDINAL KEY SCALE: NTS va vex: ET 1/2 " =1' -0" AT ML SWf a rar aec lets $GVE KCLflgMiT wmru: w,w ,vas xamamw x+a ,aaai,aa, DATUM EL R CITY OF �D RENTON Planning /Building /Public Works Dept. RECORD DRAWING Then Record Dmwhga haw bean prepared band w infamadion provided by the M*Octor and other. Kmndy /Jnb Cam has not verified the awrocy or mrgWbwm of kdomxxw provided to th m and don not wa"fft the ommaq or c 06ts of then RewN Draeiy. Ue of then Record Drawings aname all risk of Ion mulUng fmm than ass. STONEGATE LIFT STATION REPLACEMENT TYPICAL CONCRETE NOTES AND DETAILS aQ. 5- __3''73 3 06 -11 -2010 PP S2 23