HomeMy WebLinkAboutS-347353STRUCTURAL CONCRETE MASONRY UNIT GENERAL NOTES 1. CONCRETE MASONRY UNITS: BLOCKS SHALL HAVE A LIGHTWEIGHT CLASSIFICATION AND CONFORM TO ASTM C90, LATEST EDITION. MINIMUM COMPRESSIVE STRENGTH OF UNITS OF 1,900 PSI WHEN AIR CURED FOR 28 -DAYS. MINIMUM COMPRESSIVE STRENGTH OF 1,500 PSI OF MASONRY WALL ASSEMBLAGE AT 28 -DAYS. 2. MORTAR: PROPORTION MORTAR TO CONFORM TO THE REQUIREMENTS OF ASTM C270 FOR TYPE S MORTAR. DO NOT USE MASONRY CEMENT. RETEMPER MORTAR ONLY BY ADDING WATER INTO THE MORTAR AND THEN WORKING WATER INTO THE MORTAR. RETEMPERING MORTAR BY DASHING WATER OVER THE MORTAR IS NOT PERMITTED. ANY MORTAR UNUSED WITHIN 2 1/2 HOURS OR GROUT THAT IS UNUSED WITHIN 1 1/2 HOURS AFTER INITIAL MIXING SHALL BE REMOVED FROM THE WORK. 3. GROUT: MINIMUM GROUT STRENGTH OF 2,500 PSI. INCREASE CEMENT CONTENT OF THE GROUT, AS NECESSARY TO ACHIEVE THE SPECIFIED MASONRY ASSEMBLY STRENGTH (fm) AND ADEQUATE WORKABILITY. GROUT COMPRESSIVE STRENGTH WHEN TESTED PER ASTM C1019 SHALL BE EQUAL OR EXCEED THE CONCRETE MASONRY UNIT STRENGTH. GROUT SHALL HAVE A SLUMP BETWEEN 9 AND 10- INCHES AT THE TIME OF PLACEMENT. ALL CELLS SHALL BE FILLED SOLIDLY WITH GROUT. ALL GROUT SHALL BE CONSOLIDATED BY MECHANICAL VIBRATION. 4. ADMIXTURES: ADMIXTURES ARE NOT PERMITTED IN MORTAR OR GROUT UNLESS FAVORABLY REVIEWED BY THE ENGINEER. 5. AGGREGATES: SAND FOR MORTAR SHALL CONFORM TO ASTM C144 EXCEPT NOT LESS THAN 3% OF THE SAND SHALL PASS THE NUMBER 100 SIEVE. SAND AND PEA GRAVEL FOR GROUT SHALL CONFORM TO ASTM C404, TABLE 1, COARSE AGGREGATE, EXCEPT WHEN OTHER GRADINGS ARE SPECIFICALLY APPROVED BY THE ENGINEER. 6. WATER: WATER USED FOR MORTAR AND GROUT SHALL BE CLEAN AND FREE FROM DELETERIOUS AMOUNTS OF ACIDS, SALTS, ALKALI, AND ORGANIC MATERIALS. 7. REINFORCEMENT: REINFORCING SHALL BE ASTM A615 -GRADE 60. REINFORCEMENT SHALL BE FULLY EMBEDDED IN GROUT. EMBEDDED ITEMS SHALL BE SECURED IN PLACE PRIOR TO GROUTING. PROVIDE A MINIMUM OF 1 -INCH GROUT AROUND BOLTS IN MASONRY. PLACE HORIZONTAL REINFORCING IN BOND BEAM UNITS. VERTICAL REINFORCING SHALL BE HELD IN PLACE AT TOP AND BOTTOM AND AT INTERVALS NOT EXCEEDING 200 BAR DIAMETERS. UTILIZE REBAR POSITIONERS TO ACHIEVE VERTICAL REINFORCING PLACEMENT. HORIZONTAL REINFORCING SHALL BE PLACED IN BOND BEAM UNITS, EXCEPT LINTEL UNITS SHALL BE USED OVER OPENINGS. 8. BEFORE PLACING BLOCK ON CONCRETE, CLEAN CONCRETE, ROUGHEN CONCRETE SO THAT AGGREGATE IS EXPOSED TO 1/4 -INCH AMPLITUDE AND APPLY BONDING AGENT. 9. LAY ALL MASONRY WITH COMMON OR RUNNING BOND. CONSTRUCT ALL MASONRY TO MAINTAIN AN UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO BE FILLED. THE VERTICAL ALIGNMENT SHALL BE SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED VERTICAL FLUE IN ACCORDANCE WITH TABLE 7 OF THE SPECIFICATION FOR MASONRY IN ACI 530. 10. CONSTRUCTION JOINTS: WHEN GROUTING IS STOPPED FOR A PERIOD OF 1 HOUR OR LONGER, FORM HORIZONTAL CONSTRUCTION JOINTS BY STOPPING THE GROUT POUR 1 1/2 INCHES MINIMUM BELOW THE UPPER -MOST UNIT, EXCEPT AT THE TOP OF WALLS. 11. CONTROL JOINTS: LOCATE CONTROL JOINTS AS SHOWN ON PLANS OR AT 20' -0" MAXIMUM SPACING WHERE NOT SHOWN BUT NOT LESS THAN 2' -0" FROM A JAMB OR OPENING. PLACE LEDGER, LINTEL, OR TOP OF WALL BEAM REINFORCING CONTINUOUS THROUGH EXPANSION AND CONTROL JOINTS, WRAPPING BARS WITH 1/8 -INCH THICK BOND BREAKING TAPE 2' -0" BOTH SIDES OF JOINT. DO NOT SPLICE BOND BEAM REINFORCING WITHIN 6' -0" OF AN EXPANSION OR CONTROL JOINT. 12. SPECIAL INSPECTION: WHERE THE BUILDING, STRUCTURE OR STRUCTURAL ELEMENT REQUIRES SPECIAL INSPECTION AS NOTED ON THE PLANS AND THE REINFORCING SCHEDULE BELOW, PROVIDE SPECIAL INSPECTION IN ACCORDANCE WITH IBC CHAPTER 17. 13. INSPECTION: ALL WORK SHALL BE INSPECTED BY THE OWNER'S REPRESENTATIVE OR THE BUILDING OFFICIAL. THE CONTRACTOR SHALL MAINTAIN ALL WORK ACCESSIBLE AND EXPOSED FOR INSPECTION. INSPECTION SHALL INCLUDE BUT NOT BE LIMITED TO CHECKING CELLS FOR DEBRIS PRIOR TO GROUTING AND SIZE AND PLACEMENT OF REINFORCEMENT, ANCHORS, AND OTHER EMBEDDED ITEMS. SCHEDULE REINF SHALL APPLY IN ALL CASES UNLESS NOTED OTHERWISE ON SPECIFIC DETAILS OR SECTIONS. RECORD DRAWING T m Roca I Dmaipn hm been prepared band w infarrnation provided by the mftdor and otlrera. KanedylIwim CaaJOnb ba not mWed the amt to aonrrmy a�miple of them iiaxard Dma Wan of Oise Rwwd Dmrige aeeune all risk of I= molting fmm fhdr ae. PHILL Roth Hill, LLC Tel 425.869.9448 www.rothhill.com 11130 NE 33rd Place, Suite 200 Bellevue, WA 98004 ADD'L #5 BAR VERT z PROVIDE 24" HOOK IN TO BOND BEAM ALONG TOP o OF WALL N OPEN END BLOCKS THROUGHOUT (TYP) NOTES: 1. PLACE VERTICAL REBAR AT (� OF WALL. 2. SEE SCHEDULE BELOW FOR TYPICAL WALL REINFORCING. 911 ADD'L #5 BAR VERT VERT REBAR AT 4" HIGH UNITS ONLY 2 SYD BOND BEAM BLOCKS HORIZ WALL REBAR 1/2" MIN CLR INTERSECTION BOND BEAM BLOCK (AT ALL HORIZ REBAI TYPICAL REINFORCEMENT AT CONCRETE MASONRY UNIT WALLS SCALE: NTS AT DOOR OPENING EXTEND DOWELS TO GROUT EVERY CELL (TYP) , TYP WALL REBAR U#3 HAIRPIN TIES 0 8" CC 2 - #5 BARS TYP (OR AS NOTED) - LINTEL DO NOT CONTINUE SOLID BEAM BLOCK BEYOND JAMB LINTEL 48 BAR DIAMETERS WALL REINFORCING WITH OR 2' -0" MIN (TYP) LINTEL REINFORCING PER LINTEL STANDARD HOOK ALT HOOK SECTION, WHERE EXTENSION IS NOT POSSIBLE, EXTEND BARS AS JAMB REINF SEE FAR AS POSSIBLE AND PROVIDE SCHEDULE STANDARD HOOK. DO NOT SPLICE BARS OVER OPENING (TYP) wZ D 2 - #5 (TYP) UNLESS OTHERWISE o _ NOTED o DOOR U m N SEE JAMB REINFORCING o SCHEDULE (TYP) I I I I F� 1 1111 1111 N STOP OF CONCRETE NOTES: 1. FOR WALL REINFORCING, SEE "TYPICAL WALL REINFORCING SCHEDULE" THIS SHEET. SEE RELATED SECTIONS AND DETAILS THIS SHEET. 2. EXTEND JAMB BARS FROM THE FLOOR TO ROOF WHERE OPENING EXCEEDS 4' -0" IN WIDTH; OTHERWISE EXTEND 48 BAR DIAMETERS OR 2' -0" MIN. 3. DOWELS FOR JAMB BARS SHALL MATCH JAMB REINFORCING SCHEDULE. JAMB REINF SCHEDULE TYPICAL WALL REINFORCING SCHEDULE LESS THAN 5' -0" 2 -#6 5' -0" TO 7' -0" 2 - #7 BUILDING WALL THICKNESS VERT REINF HORIZ REINF REMARKS INSPECTION CONTROL BUILDING NORTH WALL 8" #4 0 24" #4 0 24" 2 - #5 0 TOP OF WALL SPECIAL INSP REQ'D SOUTH WALL 8" #4 024- #4 0 24" 2 - #5 0 TOP OF WALL SPECIAL INSP REQ'D EAST WALL 8" #4 0 24" #4 0 24" 2 - #5 0 TOP OF WALL SPECIAL INSP REQ'D WEST WALL 8" #4 0 24" #4 0 24" 2 - #5 0 TOP OF WALL SPECIAL INSP REQ'D SCREEN WALL 8" #5 0 16" 1 #5 0 16" NONE SPECIAL INSP REQ'D PILASTER 16" #5 0 CORNERS #4 0 8" HOOPS NONE SPECIAL INSP REQ'D SCHEDULE REINF SHALL APPLY IN ALL CASES UNLESS NOTED OTHERWISE ON SPECIFIC DETAILS OR SECTIONS. RECORD DRAWING T m Roca I Dmaipn hm been prepared band w infarrnation provided by the mftdor and otlrera. KanedylIwim CaaJOnb ba not mWed the amt to aonrrmy a�miple of them iiaxard Dma Wan of Oise Rwwd Dmrige aeeune all risk of I= molting fmm fhdr ae. PHILL Roth Hill, LLC Tel 425.869.9448 www.rothhill.com 11130 NE 33rd Place, Suite 200 Bellevue, WA 98004 ADD'L #5 BAR VERT z PROVIDE 24" HOOK IN TO BOND BEAM ALONG TOP o OF WALL N OPEN END BLOCKS THROUGHOUT (TYP) NOTES: 1. PLACE VERTICAL REBAR AT (� OF WALL. 2. SEE SCHEDULE BELOW FOR TYPICAL WALL REINFORCING. 911 ADD'L #5 BAR VERT VERT REBAR AT 4" HIGH UNITS ONLY 2 SYD BOND BEAM BLOCKS HORIZ WALL REBAR 1/2" MIN CLR INTERSECTION BOND BEAM BLOCK (AT ALL HORIZ REBAI TYPICAL REINFORCEMENT AT CONCRETE MASONRY UNIT WALLS SCALE: NTS AT DOOR OPENING EXTEND DOWELS TO GROUT EVERY CELL (TYP) , TYP WALL REBAR U#3 HAIRPIN TIES 0 8" CC 2 - #5 BARS TYP (OR AS NOTED) - LINTEL DO NOT CONTINUE SOLID BEAM BLOCK BEYOND JAMB LINTEL 48 BAR DIAMETERS WALL REINFORCING WITH OR 2' -0" MIN (TYP) LINTEL REINFORCING PER LINTEL STANDARD HOOK ALT HOOK SECTION, WHERE EXTENSION IS NOT POSSIBLE, EXTEND BARS AS JAMB REINF SEE FAR AS POSSIBLE AND PROVIDE SCHEDULE STANDARD HOOK. DO NOT SPLICE BARS OVER OPENING (TYP) wZ D 2 - #5 (TYP) UNLESS OTHERWISE o _ NOTED o DOOR U m N SEE JAMB REINFORCING o SCHEDULE (TYP) I I I I F� 1 1111 1111 N STOP OF CONCRETE NOTES: 1. FOR WALL REINFORCING, SEE "TYPICAL WALL REINFORCING SCHEDULE" THIS SHEET. SEE RELATED SECTIONS AND DETAILS THIS SHEET. 2. EXTEND JAMB BARS FROM THE FLOOR TO ROOF WHERE OPENING EXCEEDS 4' -0" IN WIDTH; OTHERWISE EXTEND 48 BAR DIAMETERS OR 2' -0" MIN. 3. DOWELS FOR JAMB BARS SHALL MATCH JAMB REINFORCING SCHEDULE. JAMB REINF SCHEDULE OPENING WIDTH REINFORCEMENT (EACH SIDE) LESS THAN 5' -0" 2 -#6 5' -0" TO 7' -0" 2 - #7 TYPICAL CMU ELEVATION SCALE: NTS ELEVATION SCALE: 1/4 " =,' -0" JAMB OR END OF WALL PLAN SCALE: NTS SEE TABLE OR AS SHOWN ON Z J j D AWING 7 U NMI BOLT EMBEDMENT SCHEDULE BOLT SIZE EMBED 1/2" 4" 5/8" 4" 1" 7" NOTES: 1. THE MINIMUM BOLT SPACING SHALL BE 12 BOLT DIAMETERS. 2. THE MINIMUM EDGE DISTANCE SHALL BE 6 BOLT DIAMETERS WITH A MINIMUM 6" TO END OF WALL. TYPICAL BOLT EMBEDMENT SCALE: NTS Hwhi IN CONTROL JOINT AT COLUMN SCALE: NTS 3/8" T�� MORTAR JOINT RAKED 1/2" , JOINT AT LEDGER OR AT LEDGER OR LIN�L VERT REINF - HORIZ REINF ELWIN Rolm l' HORIZ REINF SEE NOTE #11 TYPICAL JOINT TYPICAL CONTROL JOINT DETAIL e SCALE: NTS Kennedy /Jenks Consultants � . 1/2 " =,' -0" �°"° "°° F? z CITY OF «���a STONEGATE os— „ —zolo Er RENTON LIFT STATION REPLACEMENT 32001 32nd Avenue South, Suite 100 eJL Feaefal way, -8 x6401 0� ET «rte DATUM TYPICAL MASONRY NOTES auxwa xa Ph. 253 -935 -5400 1 RECORD DRAWING RFB 7/20/1 JMF Qa DLB Planning /Building /Public Works Dept. AND DETAILS S3 Fax 253.952.3435 it xor o� exm NO. REVISION BY DATE APPR APr_—_. eft s.zr: ar: 24 42