HomeMy WebLinkAboutS-347353STRUCTURAL CONCRETE MASONRY UNIT GENERAL NOTES
1. CONCRETE MASONRY UNITS: BLOCKS SHALL HAVE A LIGHTWEIGHT CLASSIFICATION AND
CONFORM TO ASTM C90, LATEST EDITION. MINIMUM COMPRESSIVE STRENGTH OF UNITS
OF 1,900 PSI WHEN AIR CURED FOR 28 -DAYS. MINIMUM COMPRESSIVE STRENGTH OF
1,500 PSI OF MASONRY WALL ASSEMBLAGE AT 28 -DAYS.
2. MORTAR: PROPORTION MORTAR TO CONFORM TO THE REQUIREMENTS OF ASTM C270
FOR TYPE S MORTAR. DO NOT USE MASONRY CEMENT. RETEMPER MORTAR ONLY BY
ADDING WATER INTO THE MORTAR AND THEN WORKING WATER INTO THE MORTAR.
RETEMPERING MORTAR BY DASHING WATER OVER THE MORTAR IS NOT PERMITTED.
ANY MORTAR UNUSED WITHIN 2 1/2 HOURS OR GROUT THAT IS UNUSED WITHIN 1
1/2 HOURS AFTER INITIAL MIXING SHALL BE REMOVED FROM THE WORK.
3. GROUT: MINIMUM GROUT STRENGTH OF 2,500 PSI. INCREASE CEMENT CONTENT OF
THE GROUT, AS NECESSARY TO ACHIEVE THE SPECIFIED MASONRY ASSEMBLY
STRENGTH (fm) AND ADEQUATE WORKABILITY. GROUT COMPRESSIVE STRENGTH WHEN
TESTED PER ASTM C1019 SHALL BE EQUAL OR EXCEED THE CONCRETE MASONRY
UNIT STRENGTH. GROUT SHALL HAVE A SLUMP BETWEEN 9 AND 10- INCHES AT THE
TIME OF PLACEMENT. ALL CELLS SHALL BE FILLED SOLIDLY WITH GROUT. ALL GROUT
SHALL BE CONSOLIDATED BY MECHANICAL VIBRATION.
4. ADMIXTURES: ADMIXTURES ARE NOT PERMITTED IN MORTAR OR GROUT UNLESS
FAVORABLY REVIEWED BY THE ENGINEER.
5. AGGREGATES: SAND FOR MORTAR SHALL CONFORM TO ASTM C144 EXCEPT NOT LESS
THAN 3% OF THE SAND SHALL PASS THE NUMBER 100 SIEVE. SAND AND PEA
GRAVEL FOR GROUT SHALL CONFORM TO ASTM C404, TABLE 1, COARSE AGGREGATE,
EXCEPT WHEN OTHER GRADINGS ARE SPECIFICALLY APPROVED BY THE ENGINEER.
6. WATER: WATER USED FOR MORTAR AND GROUT SHALL BE CLEAN AND FREE FROM
DELETERIOUS AMOUNTS OF ACIDS, SALTS, ALKALI, AND ORGANIC MATERIALS.
7. REINFORCEMENT: REINFORCING SHALL BE ASTM A615 -GRADE 60. REINFORCEMENT
SHALL BE FULLY EMBEDDED IN GROUT. EMBEDDED ITEMS SHALL BE SECURED IN
PLACE PRIOR TO GROUTING. PROVIDE A MINIMUM OF 1 -INCH GROUT AROUND BOLTS
IN MASONRY. PLACE HORIZONTAL REINFORCING IN BOND BEAM UNITS. VERTICAL
REINFORCING SHALL BE HELD IN PLACE AT TOP AND BOTTOM AND AT INTERVALS NOT
EXCEEDING 200 BAR DIAMETERS. UTILIZE REBAR POSITIONERS TO ACHIEVE VERTICAL
REINFORCING PLACEMENT. HORIZONTAL REINFORCING SHALL BE PLACED IN BOND BEAM
UNITS, EXCEPT LINTEL UNITS SHALL BE USED OVER OPENINGS.
8. BEFORE PLACING BLOCK ON CONCRETE, CLEAN CONCRETE, ROUGHEN CONCRETE SO
THAT AGGREGATE IS EXPOSED TO 1/4 -INCH AMPLITUDE AND APPLY BONDING AGENT.
9. LAY ALL MASONRY WITH COMMON OR RUNNING BOND. CONSTRUCT ALL MASONRY TO
MAINTAIN AN UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO BE FILLED. THE
VERTICAL ALIGNMENT SHALL BE SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED VERTICAL
FLUE IN ACCORDANCE WITH TABLE 7 OF THE SPECIFICATION FOR MASONRY IN ACI 530.
10. CONSTRUCTION JOINTS: WHEN GROUTING IS STOPPED FOR A PERIOD OF 1 HOUR OR
LONGER, FORM HORIZONTAL CONSTRUCTION JOINTS BY STOPPING THE GROUT POUR 1 1/2
INCHES MINIMUM BELOW THE UPPER -MOST UNIT, EXCEPT AT THE TOP OF WALLS.
11. CONTROL JOINTS: LOCATE CONTROL JOINTS AS SHOWN ON PLANS OR AT 20' -0"
MAXIMUM SPACING WHERE NOT SHOWN BUT NOT LESS THAN 2' -0" FROM A JAMB
OR OPENING. PLACE LEDGER, LINTEL, OR TOP OF WALL BEAM REINFORCING
CONTINUOUS THROUGH EXPANSION AND CONTROL JOINTS, WRAPPING BARS WITH
1/8 -INCH THICK BOND BREAKING TAPE 2' -0" BOTH SIDES OF JOINT. DO NOT SPLICE
BOND BEAM REINFORCING WITHIN 6' -0" OF AN EXPANSION OR CONTROL JOINT.
12. SPECIAL INSPECTION: WHERE THE BUILDING, STRUCTURE OR STRUCTURAL ELEMENT
REQUIRES SPECIAL INSPECTION AS NOTED ON THE PLANS AND THE REINFORCING
SCHEDULE BELOW, PROVIDE SPECIAL INSPECTION IN ACCORDANCE WITH IBC CHAPTER 17.
13. INSPECTION: ALL WORK SHALL BE INSPECTED BY THE OWNER'S REPRESENTATIVE OR
THE BUILDING OFFICIAL. THE CONTRACTOR SHALL MAINTAIN ALL WORK ACCESSIBLE
AND EXPOSED FOR INSPECTION. INSPECTION SHALL INCLUDE BUT NOT BE LIMITED TO
CHECKING CELLS FOR DEBRIS PRIOR TO GROUTING AND SIZE AND PLACEMENT OF
REINFORCEMENT, ANCHORS, AND OTHER EMBEDDED ITEMS.
SCHEDULE REINF SHALL APPLY IN ALL CASES UNLESS NOTED OTHERWISE ON SPECIFIC
DETAILS OR SECTIONS.
RECORD DRAWING
T m Roca I Dmaipn hm been prepared band w infarrnation provided
by the mftdor and otlrera. KanedylIwim CaaJOnb ba not mWed the
amt to aonrrmy a�miple of them iiaxard Dma Wan of
Oise Rwwd Dmrige aeeune all risk of I= molting fmm fhdr ae.
PHILL
Roth Hill, LLC Tel 425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
ADD'L #5 BAR VERT
z PROVIDE 24" HOOK IN TO
BOND BEAM ALONG TOP
o OF WALL
N OPEN END BLOCKS
THROUGHOUT (TYP)
NOTES:
1. PLACE VERTICAL REBAR
AT (� OF WALL.
2. SEE SCHEDULE BELOW
FOR TYPICAL WALL
REINFORCING.
911
ADD'L #5
BAR VERT
VERT REBAR
AT 4" HIGH UNITS
ONLY 2 SYD BOND
BEAM BLOCKS
HORIZ WALL REBAR
1/2" MIN CLR
INTERSECTION BOND BEAM BLOCK
(AT ALL HORIZ REBAI
TYPICAL REINFORCEMENT AT CONCRETE MASONRY UNIT WALLS
SCALE: NTS
AT DOOR
OPENING
EXTEND
DOWELS
TO
GROUT EVERY
CELL (TYP) ,
TYP WALL REBAR
U#3 HAIRPIN TIES
0 8" CC
2 - #5 BARS TYP
(OR AS NOTED) -
LINTEL
DO NOT CONTINUE
SOLID BEAM BLOCK
BEYOND JAMB
LINTEL
48 BAR DIAMETERS WALL REINFORCING WITH
OR 2' -0" MIN (TYP) LINTEL REINFORCING PER LINTEL STANDARD HOOK ALT HOOK
SECTION, WHERE EXTENSION IS
NOT POSSIBLE, EXTEND BARS AS JAMB REINF SEE
FAR AS POSSIBLE AND PROVIDE SCHEDULE
STANDARD HOOK. DO NOT SPLICE
BARS OVER OPENING (TYP)
wZ
D 2 - #5 (TYP) UNLESS OTHERWISE
o _ NOTED
o DOOR U
m N SEE JAMB REINFORCING
o SCHEDULE (TYP)
I I I I F� 1 1111 1111 N STOP OF CONCRETE
NOTES:
1. FOR WALL REINFORCING, SEE "TYPICAL WALL
REINFORCING SCHEDULE" THIS SHEET. SEE RELATED
SECTIONS AND DETAILS THIS SHEET.
2. EXTEND JAMB BARS FROM THE FLOOR TO ROOF WHERE
OPENING EXCEEDS 4' -0" IN WIDTH; OTHERWISE EXTEND 48
BAR DIAMETERS OR 2' -0" MIN.
3. DOWELS FOR JAMB BARS SHALL MATCH JAMB REINFORCING
SCHEDULE.
JAMB REINF SCHEDULE
TYPICAL WALL REINFORCING
SCHEDULE
LESS THAN 5' -0"
2 -#6
5' -0" TO 7' -0"
2 - #7
BUILDING
WALL
THICKNESS
VERT
REINF
HORIZ
REINF
REMARKS
INSPECTION
CONTROL BUILDING
NORTH WALL
8"
#4
0 24"
#4
0
24"
2 - #5
0
TOP
OF
WALL
SPECIAL
INSP
REQ'D
SOUTH WALL
8"
#4
024-
#4
0
24"
2 - #5
0
TOP
OF
WALL
SPECIAL
INSP
REQ'D
EAST WALL
8"
#4
0 24"
#4
0
24"
2 - #5
0
TOP
OF
WALL
SPECIAL
INSP
REQ'D
WEST WALL
8"
#4
0 24"
#4
0
24"
2 - #5
0
TOP
OF
WALL
SPECIAL
INSP
REQ'D
SCREEN WALL
8"
#5
0 16"
1 #5
0
16"
NONE
SPECIAL
INSP
REQ'D
PILASTER
16"
#5 0
CORNERS
#4 0
8"
HOOPS
NONE
SPECIAL
INSP
REQ'D
SCHEDULE REINF SHALL APPLY IN ALL CASES UNLESS NOTED OTHERWISE ON SPECIFIC
DETAILS OR SECTIONS.
RECORD DRAWING
T m Roca I Dmaipn hm been prepared band w infarrnation provided
by the mftdor and otlrera. KanedylIwim CaaJOnb ba not mWed the
amt to aonrrmy a�miple of them iiaxard Dma Wan of
Oise Rwwd Dmrige aeeune all risk of I= molting fmm fhdr ae.
PHILL
Roth Hill, LLC Tel 425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
ADD'L #5 BAR VERT
z PROVIDE 24" HOOK IN TO
BOND BEAM ALONG TOP
o OF WALL
N OPEN END BLOCKS
THROUGHOUT (TYP)
NOTES:
1. PLACE VERTICAL REBAR
AT (� OF WALL.
2. SEE SCHEDULE BELOW
FOR TYPICAL WALL
REINFORCING.
911
ADD'L #5
BAR VERT
VERT REBAR
AT 4" HIGH UNITS
ONLY 2 SYD BOND
BEAM BLOCKS
HORIZ WALL REBAR
1/2" MIN CLR
INTERSECTION BOND BEAM BLOCK
(AT ALL HORIZ REBAI
TYPICAL REINFORCEMENT AT CONCRETE MASONRY UNIT WALLS
SCALE: NTS
AT DOOR
OPENING
EXTEND
DOWELS
TO
GROUT EVERY
CELL (TYP) ,
TYP WALL REBAR
U#3 HAIRPIN TIES
0 8" CC
2 - #5 BARS TYP
(OR AS NOTED) -
LINTEL
DO NOT CONTINUE
SOLID BEAM BLOCK
BEYOND JAMB
LINTEL
48 BAR DIAMETERS WALL REINFORCING WITH
OR 2' -0" MIN (TYP) LINTEL REINFORCING PER LINTEL STANDARD HOOK ALT HOOK
SECTION, WHERE EXTENSION IS
NOT POSSIBLE, EXTEND BARS AS JAMB REINF SEE
FAR AS POSSIBLE AND PROVIDE SCHEDULE
STANDARD HOOK. DO NOT SPLICE
BARS OVER OPENING (TYP)
wZ
D 2 - #5 (TYP) UNLESS OTHERWISE
o _ NOTED
o DOOR U
m N SEE JAMB REINFORCING
o SCHEDULE (TYP)
I I I I F� 1 1111 1111 N STOP OF CONCRETE
NOTES:
1. FOR WALL REINFORCING, SEE "TYPICAL WALL
REINFORCING SCHEDULE" THIS SHEET. SEE RELATED
SECTIONS AND DETAILS THIS SHEET.
2. EXTEND JAMB BARS FROM THE FLOOR TO ROOF WHERE
OPENING EXCEEDS 4' -0" IN WIDTH; OTHERWISE EXTEND 48
BAR DIAMETERS OR 2' -0" MIN.
3. DOWELS FOR JAMB BARS SHALL MATCH JAMB REINFORCING
SCHEDULE.
JAMB REINF SCHEDULE
OPENING WIDTH
REINFORCEMENT (EACH SIDE)
LESS THAN 5' -0"
2 -#6
5' -0" TO 7' -0"
2 - #7
TYPICAL CMU ELEVATION
SCALE: NTS
ELEVATION
SCALE: 1/4 " =,' -0"
JAMB OR END OF WALL PLAN
SCALE: NTS
SEE TABLE OR AS
SHOWN ON
Z J j D AWING
7
U NMI
BOLT
EMBEDMENT
SCHEDULE
BOLT
SIZE
EMBED
1/2"
4"
5/8"
4"
1"
7"
NOTES:
1. THE MINIMUM BOLT SPACING SHALL BE 12 BOLT
DIAMETERS.
2. THE MINIMUM EDGE DISTANCE SHALL BE 6 BOLT
DIAMETERS WITH A MINIMUM 6" TO END OF WALL.
TYPICAL BOLT EMBEDMENT
SCALE: NTS
Hwhi
IN
CONTROL JOINT AT COLUMN
SCALE: NTS
3/8" T��
MORTAR JOINT
RAKED 1/2" ,
JOINT AT LEDGER OR AT LEDGER OR LIN�L
VERT REINF -
HORIZ REINF
ELWIN
Rolm l'
HORIZ REINF
SEE NOTE #11
TYPICAL JOINT
TYPICAL CONTROL JOINT DETAIL e
SCALE: NTS
Kennedy /Jenks Consultants � . 1/2 " =,' -0" �°"° "°° F? z CITY OF
«���a STONEGATE os— „ —zolo Er RENTON LIFT STATION REPLACEMENT
32001 32nd Avenue South, Suite 100 eJL
Feaefal way, -8 x6401 0� ET «rte DATUM TYPICAL MASONRY NOTES auxwa xa
Ph. 253 -935 -5400 1 RECORD DRAWING RFB 7/20/1 JMF Qa DLB Planning /Building /Public Works Dept. AND DETAILS S3
Fax 253.952.3435 it xor o� exm
NO. REVISION BY DATE APPR APr_—_. eft s.zr: ar:
24 42