HomeMy WebLinkAboutzS-2832SetSANITARY SEWER UTILITY - GENERAL NOTES 1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON AND THE LATEST EDITION OF WSIiOT /APWA STANDARDS AND SPECIFICATIONS. 2. THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30 A.M. TO 3:30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE TRANSPORTATION DIVISION AT 277- 6222. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE TRANSPORTATION DIVISION 24 HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE. 3. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON STANDARD SPECIFICATIONS. 4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 5. A PRECONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CITY INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. 6. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE. 7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION. 8. PLANS APPROVED BY THE CITY OF RENTON, DEVELOPMENT SERVICES DIVISION, SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. 9. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION' IS IN PROGRESS. 10. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS- BUILT DRAWING OF THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL ENGINEER OR A LICENSED PROFESSIONAL SURVEYOR. 11. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES; MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95% OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE BACKFILL OF THE PIPE SHALL BE THE SAME AS DESCRIBED. 12. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH A SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENTSTANDARDS. 13. DATUM SHALL BE CITY OF RENTON, U.S.C. AND G.S. 14. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. 15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH SECTION 7- 02.3(1) OF THE CURRENT STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO. UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6" ABOVE AND BELOW THE PIPE. 1 16. SANITARY, SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50. 17. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCH AND MAXIMUM 18 INCH ABOVE FINISHED GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. Wvvp -17 -2832 CONCIPA Cfl MON W/ BRASS PUNCH IN CASE e" J�Q ° .TOa a 0 2 f,1 +, V v I-Al ; 3 I I I rr'1 CONCRETC NON. W/ 13R/fSS PUNCH IN CASE CEXST� STA 2 +44.0 N -EXST SAN SWR MH p D RIM EL 445.7 6 / Q IE IN 439.8 C, o IE > OUT 439.6 ` -4" COMPACTED DEPTH / CL B ASPHALT CONCRETE 13 - I3 - 6' COMPACTED DEPTH 3/4j_11/2 CRUSHED ROCK I 27 z� COMPACT SUBGRADE 95 -EXST e' Pvc TYPICAL ROAD SECTION cn p NO SCALE I _ _ d D I 22 2 LF +06. �L SSPVG I E 439.8 > 4 SWR MN cb O1 EXST 20' - I PA VED ACCESS r zpslo / p \\ STA 1 +54.2 � R Q \� � 5'` M2N 5 o N ' F /- 153 LF N80 °2.3'12 _ 1 6 $g EoP ' PVC \ i N - _- \ < STA 1 +44.2 II.Sy, ��, f ``E 4480 EOp 4 X6 / j \ IF 433 F -M S ` 6 1 v I a STA 1 +16.5 � ,N 1+00T, 23 LF Z I G" PVC SS \ D 432 / 26.0 i\ •.84.73' 1 EXST 8 °PVC 432 439 F3617 SWR MN Nr" R 77 R6- A tP CD o STA. 0+00' -EXST SAN SWR 'AH 48" 0 \ i � a ; I E 47.0 \7 �l 1 I R 25' L \ N 152 LF I MI A t 6 PVC SS 60 90.0 200.75 9S� 26'ACCESS EASEMENT 20' PAVED !SEE ROAD SECTION DETAIL LEGAL DESCRIPTION THE WEST 130' OF THE W. 1/21OF THE E %2 , OF THE W Y? OF THE SE I/A OF SECT. 3 -23-5• r U r JAMES E HAYNES PE 37234 22ND AVENUE SOUTH (FEDERAL WAY, WA 96003 (253)661 -6794 uo J 1a�2O SCANNED MAR 3 0 LUUU - i� , 0 Im®m I� o- tpuri y °z° N D > F_ M m Cn r � M z yril o D � D D Z o m 10 , o 0 N �y J oNlo N u °3 460 450 440 430 4 +44.0, �. PROPOSED GRADE 4 +55.5 ROAD AND SEWER PROFILE LKG NORTH sT.4 z + 44 EXST 4e SAN SWR MN Film EL 445,72' 0 IE 439.82 IN (E) NEW PAVED ACCESS IE 439.G2 OUT(S) ` SEE DETAIL PROPOSED GRADE 450 440 430 420 r� rm _ aaTY wrrQ - 17 -22pj zz 4f 61 O 88 2. -7.` _ 4 +44 -EXST GRADE D _NEW rol PVC S IE 435.8 NEW 6 °PVC 5S '-- Qo Frl �IE 430.5 :;F- 0 NEW G" �VC SS _ SR 900 _ IE 429 NEW-6 PVC SS_ e IE 426.9 � � EXST SWR Ti D 99•5 zz-- _ MH EXST 8" PVC e SAN. 5WR MN � ROAD AND SEWER PROFILE LKG EAST SCALE VERT:I ° =10' HORIZ : I'= 20 Agoft OEM 3 �5 � :•Mc A� lee 7 JAMES E HAYNES PE 37234 -22 "D AVENUEZOUFH balt FEDERAL WAY, WA J8b03 SCANNED MAR 3 0 200E (253) 661 -6794 O D Qo Frl :E :;F- 0 fTl � Ti D � :•Mc A� lee 7 JAMES E HAYNES PE 37234 -22 "D AVENUEZOUFH balt FEDERAL WAY, WA J8b03 SCANNED MAR 3 0 200E (253) 661 -6794 li -7 /2' x 13 -1 /2" CONCRETE TE METER �I'�IN UNIMPROVED RIGHT OF WAY, BIIX WITH 3/16' STEEL DIAMOND PLATE IN METER BOX AT COVER COUAL. TO FOG TITE METER vI PROPERTY' LINE. t SEAL CO ID METER BI1X. SIDEWALK WATER METER TO BE SUPPLIED BY THE CITY mr r TYPE 'K' SOFT � -- COPPER TUBING _ FORD COPPERSCTTEF, VH 132 -15W (FOR 5l8' x 3/4' METER) CAST IRON OR VH 174 -ISW tFOR 1• M':TER) , DUCTILE IRON / LOOP DOWN TO CENTERLINE BOTH INLET ADD OUTLET WITH PACK JOINT WITH GRIPPER. vATERMAIN pF WATER MAIN TO PROVIDE ON PADLSCV GUTL WINGS ON KEY VALVE SINGLE CHECK VALVE / SLACK IN COPPER SERVICE ON OUTLET. JJ /J LINE TO METER ALL PACK -JOINT FITTINGS SHALL BE WITH GRIPPER CORPORATUON STOP. FORD TAPERED IF SERVICE LINE TO HOUSE 1S TO BE THREAT' (CC). PACK JOINT (3/4' F3000) INSTALLED IN THE FUTURE INSTALL (1" Fi0001 FORD C14 -33 OR 44 1I0T u COMPRESSION COUPLING 3/4' OR I' GALVANIZED PLUG ,3/4"2 1" WATER SERl, ICE NO SCALE FLOE HYDRANT SHALL BE COREY -TYPE EQUAL TO IDwA F -5110 OR COUPRF-R9OM TYPE SUCH AS CLOW MEDALLION: M ✓r H 929 pun ue=CEM SUPER CENTU...,,.. GW Will 6- MECIiANICAL =NT INIET NTH LUGS 5-1/4' MAIN VALVE OPENING_ TWO 2 -1/2- HOSE.CONNECTIWNS NATIONAL STANDARD THREADS 4- PUMPER CONNECTION CITY OF SEATTLE THREADS MATH A STORTZ ADAPTOR, 4- SEATTLE THREAD X S. STORTZ, ATTACHED VAIN 1/8- STAINLESS STEEL CABLE, 1 -1/47 PENTAGON OPERATING NUT, FIRE HYDRANT TO BE — TO 20' PAINTED VAIN TWO COATS OF PAINT, PRESERVATIVE OR 12- BEHIND BACK OF SIDEWALK THAT IS ADJACENT TO CURB PAINT Nn 43-655 SAFETY YELLOW OR APPROVED EQUAL PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY FOR 4 -1/2- TRENCH, MAX 4'-1 • FIRE HYDRANT EXTENTION TO BE USED IF REQUIRED. MIN 2 -� RAISED PAVEMENT MARKER TYPE 88 AB STIMSONITE TWO -WAY BLUE" TWO -PIECE CAST IRON VALVE BOX. EQUAL TO OLYMIC FOUNDRY CO. STANDARD B' TOP SECTION WITH REGULAR CONCRETE BLOCKING BASE SECTION LENGTH TO FIT. Q =s CONCRETE BLOCKING LCAST IRON TEE. WITH 6' FLANGE SIDE OUTLET. 6- GATE VALVE (FL X MJ) EQUAL TO MUELLER CD. A- 2380 -16 —6' DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT TWO 3/4- 16' x 8" x 4" MINIMUM STEEL TIE RODS. SEE STD DETAIL FOR TIE RODS CONCRETE BLOCK 7 CU. FT. MINIMUM WASHED GRAVEL PASSING 1 -1/2- AND RETAINED ON 1/4" MESH FOR DRAIN. FIRE HYCIR�. IT I FTAIL NO SC.ALL r WATER MAIN / IF ADDITIONAL ADJUSTMENT IS REQUIRED, INSTALL 2 -2' CLOSE NIPPLE AND 2 -2' 90' BEND, SCREWED AT THIS POINT. FIELD LOCATE 2' CLOSE NIPPLE F - - y�CONCRETE METER BOX I I 2" CLOSE NIPPLE 2' 90°ELBOW '2' 90 ° ELBOW dal a 2' GALVANIZED PIPE AS REQUIRED CONCRETE BLOCKING PLAN TWO PIECE CAST IRON VALVE EOU:.L TO OLYMPIC FOUNDRY CO. STANDARDS* TOP SECTION, WITH /- GROUND LINE //- CONCRETE SIDEWALK REGULAR BASE SECTION LENGTH / TO FIT- i PROPERTY LINE T-F T -D•' niN. 6• -0'• -1 FUTURE 6" BUILDING SEVER PIPE I BUILDING SEWER ? 2"x 4" STUD SERVICE MARKER PAINT UPPER TEE WITH 6" SIDE OUTLET PORTION WHITE ANS STENCIL ON SIDE „ WO0RDING 'SEWER' WITH 3" HIGH BLACK LETTERS. 6" SIDE SEWER AND BUILDING SEWER AND 16 WIRE WRAPPED AROUND THE STUD AND o I EXTENDED TO THE TOP OF THE STUD. a UNLESS OTHERWISE APPROVED BY THE CITY, MAKE TAP THROUGH CAST IRON SADDLE SECURED TO SEWER MAIN WITH STAINLESS STEEL BANDS WHEN CONNECTING NEW SIDE SEWERS TO EXISTING MAIN. 60" ALLOWABLE MAX. VITRIFIED CLAY, PLAIN AND REINFORCED CONCRETE. DI PIPE AND Cl FOR CAST IRON PIPE PIPE SEWER MAINS ARE TO BE CORE DRILLED OR DUCTILE IRON PIPE. lo.s nix /p / Yt K�JG BLOCKING Ha zs �Y,p'1"•G0.ESf` co`4 zz nm garc HORIZONTAL 6" SIDE WTLET TEE B.. nIN -SEWER MAIN SEWER MAIN (Q CRE:FE BLOCKING ANGLE DF'TEL AT MAIN OVER 25 TYPICAL SIDE SEWER ELEVATION ELEVATION NOTES, UNLESS, OTHERWISE SHOWN ON PLAN, SIDE SEVER, SHALL HAVE A MINIMUM 5' COVER AT PROPERTY LINE OR -3 -5' LOWER THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER. TYPICAL SIDE SEWER INSTALLATION °�• - - -G I 2 -1/2" NST (HOSE) ?" GATE VALVE, SCREVED BLOW -UFF HYDRANT EQUAL TO 2" GALVANIZED 478 KUPFERLE FOJNDRY CO PIPE 12" LONG 2".2'x2' TEE 2" CLOSE NIPPLE BETTEEN 2" CLOSE NIPPLE TEE AND 90'ELBOW. BETWEEN CAP OR PLUG ` AND 2" 90 2" 9L ELBO90"L BOW INSTALL 4 MIL POLYETHYLENE 2' GALVANIZED PIPE PLASTIC COVER OVER WASHED - o - - °8 18" LONG GRAVEL. CUT HOLE FOR PIPE _ o o° - o9popo °oo 2' CAP WITH 1/8' 10 CU FT. WASHED GRAVEL PASSING °o x-`°o °-0�4 TAP FOR DRAIN I -1/2' AND RETAINED ON 114' MESH s o� FOP DRAIN ELEVATION PERMAP,W N T 2 Bf_r�, r (= [Vi BI_, NO SCALE q/1ol'660'! AS BUILT 7'6:0 -4YO -28dZ ® - - - NO SCALE � ST \ - LOT LOT Z All � \ LQT 4 j LOT 3 S VICINITY PLAN NO SCi;LE -- �1 yl� j t�I II-z i' I 31 f 3i PROJECT DATA APPLICANT/ DEVELOPER SURVEYOR ENGINEER TOTALAREA NUMBER OF LOTS J & J CONSTRUCTION 2509 Aberdeen Ave NE Renton, WA 98056 (425) 255 -2362 CONTACT- JIM JACQUES JAMES CRONES JAMES E. HAYNES, P -E- 37234 22ND AVE SO FEDERAL WAY, WA 98003 (206) 661 -6794 0,75 ACRES 4 AO%l *Am 240 A ww+ LOCATION DESCRIPTION A ?'m � "MW *1#45 4? Olvil THE WEST 130' OF THE WEST OF THE EAST % OF THE WEST % SOUTHEAST Y. OF SECT 3-23 -5 F JAMES E HAYNES PE 37234 22" AVENUE SOUT4 FEDERAL WAY, WA 98V03 (253) 661 -6794 O Z 6� z CJ ggN e PT F9 I t2i f4 Zy Z' +, n _z r n Z C V7 rTl_ O S ::E D X D m D F- (1) SCANNED MAR 3 0 2000 /-I 1 R - ac;ANNED SEP 13 2002 I A 0 y -c d 3d O ?'- N W N u V SANITARY SEWER UTILITY - GENERAL NOTES 1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON AND THE LATEST EDITION OF WSDOT /APWA STANDARDS AND SPECIFICATIONS. 2- THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30 AM. TO 3.30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE TRANSPORTATION DIVISION AT 277- 6222. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE TRANSPORTATION DIVISION 24 HOURS IN ADVANCE, THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE. 13, ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION' PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON STANDARD SPECIFICATIONS. 4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 5. A PRECONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION- IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE CONT RAGTIOWS RESPONSIBILITY TO NOTIFY THE CITY INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. 6. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE. 7- IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION - 8. PLANS APPROVED BY THE CITY OF RENTON, DEVELOPMENT SERVICES DIVISION, SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. 9. A COPY OF THESE APPROVED PLANS !'RUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 10. THE CONTRACT OR SHALL PROVIDE THE CITY OF RENTON WITH AN AS- BUILT DRAWING OF THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL ENGINEER OR A LICENSED PROFESSIONAL SURVEYOR. 11. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95% OF MAXIMUM DENSITY- THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE BACKFILL OF THE PIPE SHALL BE THE SAME AS DESCRIBED. 12. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH A SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT STANDARDS. 13. DATUM SHALL BE CITY OF RENTON, U.S -C. AND G.S. 14. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. 15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH SECTION 7- 02.3(1) OF THE CURRENT STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6" ABOVE AND BELOW THE PIPE. 16. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50. 17. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCH AND MAXIMUM 18 INCH ABOVE FINISHED GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. Wwp-27 -1832 fN CUN�1 I (E MON W1 GRAS S PUNCH 0 IN CASE CONCRETC NON. W/ BRASS PUNCH IN CASE (EXST) STA 2 +44.0 —EXST SAN SWR MH D RIM EL 445.7 6, Q IF IN 439.8 cp w IF OUT 4396 411 COMPACTED DEPTH CL B ASPHALT CONCRETE I 6 COMPACTED DEPTH 10' Y 3�-I %Z CRUSHED ROCK �� -- 4 I 27 n -- COMPACT j SUBGRADE 95 A ° w TYPICAL ROAD SECTION NAB °35IS�W y N _ —EXST S PVC NO SCALE � 3z.0' SWR MN -� i P 4 3 T !_ OI EXST 20 I PAVED ACCESS v �Ij �3 �0 i I I i 1 \ o I y 1 22 LF +06.2 r 11 N 1 ,o m� � \SJPVC -IE 439.8 '6 °� zG w zosl � a o N68° 55, IBN W I,X 2+ \ \ _'`,\ �1 26'ACCE5S EASEMENT O 20' PAVED STA 1 +54,2 \ t R25' v 4 \ I' 1 'SEE ROAD SECTION DETAIL 2 \ 1 MIN.,{ v` _� - ��- �� \ I 1 N_ T23'1 - S \ LEGAL. DESCRIPTION 6 " PVC SS 1 N THE ;LEST 130i iut THE STA 1 +44.2 7 eoP W [/?,OF THE E YZ , v� 1� OF THE W ! %Z OF THE SE %tl 6 rr.sy,/�,1'd,6 �6 GF SECT 3 -23 -5. Eop \ \ may\\ CIE 433 a �, X25' v I +oo+ STA 1 +16.3 cp 1 13� \ I I 6'PVC \ 1 /£ 1 MIN J 1p \ \ Jzs le 0^0 SS _ _ �-) � 6`PVC SS \ p f Q a n ii om �a �3 °z° D � \A A STA. 0 +00' EXST SAN SWR MIA 48" D v \ \ P Lei' / -// d0 _ 9 f } Q \ p a�lotZa2 JAMES E HAYNES PE_ S BUILT 37234 22 "D AVENUE SOUTH A -- -- FEDERAL WAY, WA 98003 (253) 661 -6794 /1 r^ 1 . - 20'5-, CD SCANNED MAR 3 0 2000 SCANNED SEP 13 2002 176 F R' 1: `_ o • , a 8 9*Po o{ S2_ . '- N N M t Z� %-0283204 i 84.73' \ \\ 200.75' gS4 _u EXST B��PVC 43 4\p 17 'p Fg 2 3V 363 0'e ` I I m r- ::E M SWR MN Q A I g 176 D n O D � \A A STA. 0 +00' EXST SAN SWR MIA 48" D v \ \ P Lei' / -// d0 _ 9 f } Q \ p a�lotZa2 JAMES E HAYNES PE_ S BUILT 37234 22 "D AVENUE SOUTH A -- -- FEDERAL WAY, WA 98003 (253) 661 -6794 /1 r^ 1 . - 20'5-, CD SCANNED MAR 3 0 2000 SCANNED SEP 13 2002 176 F R' 1: `_ o • , a 8 9*Po o{ S2_ . '- N N M t WATER UTILITY - GENERAL NOTES 1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON UTILITY DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA STANDARDS AND SPECIFICATIONS, AS APPROVED BY THE CITY OF RENTON. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION_ 2. THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE TRANSPORTATION DIVISION AT 277- 6222. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE TRANSPORTATION DIVISION AT 277 -6222 24 HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE. 3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATE CALL 48 HOURS LOCATORS, 1- 800 -424 -5555. 4. ALL WATER MAIN PIPE TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AW WA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AW WA C104 OR LATEST REVISION. PIPE JOINTS TO BE PUSH-ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE INSTALLED SOUTH OF SUNSET BLVD. (EMPIRE WAY, SR 900) AND WEST OF SR 167 ( EAST VALLEY FREEWAY) OR IN SOILS OF HIGH RESISTIVITY SHALL BE POLYETHYLENE WRAPPED PER ANSI/AW WA C105 -77 STANDARDS, 5. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH ANSIIAW WA C110/A21.10-82. CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI /AWWA C104/A21.4 -85. IF FITTINGS ARE 3 INCHES TO 12 INCHES IN DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL BE IN ACCORDANCE WITH EITHER ANSI /AWWA I C1 i0iA21.10 -82 0R ANSI /AWWA C153/A21.53 -84. 3 INCHES TO 12 INCHES DIAMETER FITTINGS WHICH HAVE MECHANICAL JOINTS AND /OR FLANGED JOINTS, SHALL BE IN ACCORDANCE WITH ANSI /AW WA Cl 10/A21.10.82 OR A COMEMATION OF ANSI /AW WA Cl 10/A21.10.82 AND ANSVAW WA C1531A21.53 -84 SUCH THAT THE PORTION OF THE FITTING WITH A MECHANICAL JOINT(S), MAY BE IN ACCORDANCE WITH ANSUAIVWA C153/A21.53 -84 AND THE PORTION OF THE FITTING WITH FLANGED JOINT(S) SHALL BE IN ACCORDANCE WITH ANSI /AWWA Cl l0/A2i.10 -82_ ACCEPTANCE TESTING WITH SECTION 53.53 OF ANSI /AWWA C153IA21 -53-34 OR WITH SECTION 10-4.3 OF ANSI /AWWA C110/A21.10 -82 SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER_ 6. GATE VALVES SHALL CONFORM TO AW WA C500 AND SHALL BE IRON BODY, BRONZED - MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O -RING STUFFING BOX_ VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO A2380, OR M & H. ALL VALVES 12" IN DIAMETER AND LARGER, SHALL BE INSTALLED IN A VAULT. SEE WATER STANDARD DETAIL FOR 12" GATE VAJ VE ASSEMBLY VAULT AND 1" BYPASS INSTALLATION. T FIRE HYDRANTS SHALL BE COREY TYPE (OPERATING WITH THE PRESSURE) CONFORMING TO AWWA C- 504-80 WITH A 6 INCH INLET AND A M.V.O. OF 5 INCHES, TWO 2 -112" HOSE NOZZLES WITH NATIONAL STANDARD 7 INCH, 60 DEGREES V THREADS, O.D_ THREAD 4.875 AND ROOT DIAMETER 4,6263,1-3/4 INCH PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT). 8. ALL WATER MAIN 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATER MAIN 12 INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATER MAINS ARE TO BE LOWERED TO CLEAR. 9. ALL WATER MAINS SIX (6) INCHES IN DIAMETER AND LARGER SHALL BE CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE "POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB /CU FT. DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER COATING ON THE REAR OF "PIG" ONLY. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CITY WILL ASSIST THE CONTRACTOR WHO WILL PERFORM THE CLEANING OPERATION. 9A. ALL WATER MAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. 9B. ALL WATER MAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM (MINIMUM CONCENTRATION) CHLORINEANATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE METERED /INJECTED IN ACCORDANCE WITH SECTION 7 -11.3 (12)E OR 7- 11.3 (12) F OF THE STANDARDS SPECIFICATIONS REFERENCED IN 1 ABOVE. WTie - .27 - 2A;?Z 5TA 1+72,52 Qf i 2 _ T STA 2+27.5 HIRT 12"X 8" TAPPING TEE (MJ X FL) CONCRETE BLOCKING 8 °TAPPING VALVE (MJ XFL) SEE CONNECTION DETAIL � EXST SAN SWR MH \ % I RIM EL 445,7 OD kp STA 2 +58.74 10. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CTR C -D -S CONSTRUCTION. A MINIMUM OF 10 (TEN) WORKING DAYS NOTICE IS EXST WTR MN' 12' DI w REQUIRED FOR SCHEDULING_ PRIOR TO SCHEDULING THE PRECON A � N PERMIT SHEET MUST BE SUPPLIED TO THE UTILITY ENGINEER'S a O � z \ z STARTING NEW CONSTRUCTION_ 113" LT STA 21-41 6"F 8 °X 6 TEE (MJ X FL) CGATE VALVE (FL XMJ) CONCRETE BLOCKING I FIRE HYDRANT ASSY SEE DETAIL 6 LI= 6' /DI � 3? o CD � O � I 3 I TSR SVC LOT ' I I 16 LFB"DI I t I I STA 2+41,83( LT M 8" 45° BEND MJ r CONCRETE BLOCKING Lei D N - I � t 1 I 8 °CAP `^ ;?_ TAP 2 "BLOwO�F y CONC BLOCKING 3 8 "VERT CROSS(MJ)XFL '*l/Z -8 "BLIND FLANGES ( I W ITH 2" TAP z" PLUG) g32 EXST e PVC SAN SWR W m 12X8�TAPPIN�G TEE;I�4 EXST 12"MN � v 5-- 8 "TAPPING VALVE 10} '* ,1INSTALL �/ 8 "SOLID SLEEVE CAP W/TEMP 2 ?.- eNIPPLES NEW 8 MAIN -_ BLOWOFFF SIZE TO FIT OLYPIG7'- lrts£RSiora Poims WATER MAIN CONNECTION DETAIL NO SCALE Ln ON O' -A ti LOT I LOT 2 261 ACCESS EASEMENT 20' PAVED l /3 / 1, 24� I "WTR SVC \ '\ LOT 3 1" WTR SVC _ LOT 2 ! I 3 WTR SVC I 4 LOT 4 > j I LOT 4 I I LOT 3 i I Q3F363�'o � 2 Q 2 3. A cp gsc� 6 CT 10. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM OF 10 (TEN) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING_ PRIOR TO SCHEDULING THE PRECON A PERMIT SHEET MUST BE SUPPLIED TO THE UTILITY ENGINEER'S OFFICE. TWENTY FOUR HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION_ 11. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL �_. 4t 00 NECESSARY PERMITS PRIOR T O STARTING CONSTRUCTION. 12. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND -4 -A METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON. 13. ALL CONNECTION TO EXI TING MAINS TO BE ACCOMPLISHED BY THE CITY OF RENTON. EXCEPT WET TAPS WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM BUILT THE WATER UTILITY SECTION_ ALL NECESSARY EXCAVATION AND JAMES E HAYNES PE 3723422 ND AVENUE SOUTH MATERIALS TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS. FEDERAL WAY, WA 98003 14. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY (253) 661 -6794 TO NOTIFY THE CITY INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE CONTRACTOR AS WELL AS THE ENGINEERS SHALL KEEP AS -BUILT DRAWINGS, 15. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN - II& ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC_) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING S COMPANY OF COLUMBUS OHIO OR EQUAL APPROVED IN WRITING BY r' THE WATER UTILITY SECTION- 17 ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A F6� MINIMUM DEPTH OF TWO INCHES. OIL MAT STREETS MAY BE SPADE CUT_ ALL SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURBS, GUTTERS, AND DRIVEWAYS APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT_ 18. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE vs DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO 6 BE PLACED, TO CITY OF RENTON POLICY, WITHIN TEN DAYS_ CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH, TRENCHES WILL NOT BE LEFT OPEN OVER NIGHT WITHOUT PRIOR WRI i EN APPROVAL OF THE INSPECTOR_ 19. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE 4S j SHALL BE SCHEDULE 401N UNIMPROVED AREAS AND SCHEDULE 80 g I UNDER I;APROVED AREAS. ALL CHEMICAL LINES SHALL BE SCHEDULE 80 PVC PIPE. 3. A cp gsc� 6 CT 4mw 4r W-283202 �_. 4t 00 1 AS BUILT // k G a #'I+ 114 (i000 ;, JAMES E HAYNES PE 3723422 ND AVENUE SOUTH FEDERAL WAY, WA 98003 (253) 661 -6794 0 z t aff r„ SCA14NEU twa a G 206-0 /,A t-�, w c' 2 SCANNED SEP 13 2002 o f , + B L L 176 FR 1 91 1 Lle Z M P-1 F1 z° D � Isl m cf)� rn r z %_ O m m C y c� N V> N W N 4, 0 46 45 44 43 1 0 PROPOSED GRADE EXST GRADE - 4 +55.5 4 +44.0, i 0 - - -- 0 S7A 4 t 44 EXST 48" SAN SWR MH RIM EL 445.72' IE 439.82 IN (E) I E 439.62 OUT (S) 450 440 430 420 410 TEO -fio- ,78T2 wnQ -1 7 -�g32 Y ROAD AND SEWER PROFILE LKG NORTH 4i NEW PAVED ACCESS SEE DETAIL PROPOSED GRADE I6 _88, 4+44 -EXST GRADE NEW 6" PVC S QO m = IE 435.8 NEW GPVC SS ~ t 430.5 378 �IE NEW G'PVC 55 Fri IE 4Z9 NEW 6 PVC sr- 83.8 -i IE 42_6.9 99 -8 -:z- ROAD AND SEWER PROFILE 127.5 U) 0 Z Jill z z m i Eo�N1 S-2463 20.3 sue.„ C)"l r � k O � r o D m CL - _ SR 900 QO m = EXST SWR MR _ - - -_ Fri EX5T a- PVG 5AN. SWR MN r- _ o T -_ . -.--I r m ROAD AND SEWER PROFILE LKG EAST SCALE VERT:I ° =10 HORIZ. I' =20 ' I �� SCaNNED SEP 13 2002 AS �1 �''p- -- --„.; JAMES E HAYNES PE 3723422 N" AVENUE SOUTH-- l� C 3 FEDERAL WAY, WA 98003 (253) 661 -6794 i - N 4CONNCf1 MAR i o ?FOB Y Sii .1,I: ti { Yk