EXISTING WATER LINE
PLAN NEW
TESTING DETAIL
EXISTING WATER UNE
FINAL CONNECTION OCTAL
Fir IN_
AFTER ALL TESTING. CLEANING BY POLYPIG, AND DISINFECTION,
REMOVE TEMP. BLOCK & SLOW-CM & CONNECT
WITH SLEEVE (W) & D.I. SPOOLS
FINAL CONNECTION BY Cltt FORCES
EXISTING WATER UNE
PUBWC WORKS CONNECTION TO WATER MAIN CUT 'PLAN - 900.2
DEPARTMENT IN -LINE TEE & ONE VALVE MARCH 2010
CONNECTION TO WATER MAIN CUT
IN -LINE TEE AND ONE VALVE
WATER UTILITY NOTES AND SPECIFICATIONS
1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING /BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA STANDARDS AND SPECIFICATIONS,
AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED
PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE
APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT AT (425) 430 -7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911
SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY
THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48 -HOUR LOCATORS
800 - 4245555.
4. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE - CONSTRUCTION MEETING.
5. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND FOR HORIZONTAL CONTROL SHALL
BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS
DEPARTMENT. REFERENCE BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AW WA C110 AND C111 OR LATEST REVISION,
THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AW WA C104 OR LATEST REVISION. PIPE
JOINTS TO BE PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE
POLYETHYLENE WRAPPED PER ANSI /AW WA C105/A21.5 -93 STANDARDS.
7. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH
ANSI /AW WA C110/A21.10-67. CEMENT LINING SHALL BE INACCORDANCE WITH ANSI /AW WA C104/421/4 -90. IF FITTINGS ARE 3 TO 12 INCHES
IN DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER ANSI /AW WA C110- A21.10 -87 OR
ANSI/AW WA C153/A21.53 -94. THREE (3) INCH TO 12 INCH DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND /OR FLANGED
JOINTS, SHALL BE IN ACCORDANCE WITH ANSI /AW WA C1 101A21.10.87 OR A COMBINATION OF ANSI /AW WA C1 10/A21.10.87 AND ANSIAWWA
C153/A21.53 -94 SUCH THAT THE PORTION OF THE FITTING WITH A MECHANICAL JOINTS MAY BE WITH ANSI /AW WA C153/A21.5 3-94 AND
THAT PORTION OF THE FITTING WITH FLANGED JOINTS) SHALL BE IN ACCORDANCE WITH AW WA C11 O/A21.10 -87. ACCEPTANCE TESTING
IN ACCORDANCE WITH SECTION 53.53 OF ANSI /AW WA SECTION 10-4.3 OF ANSI /AW WA C11 O/A21.10 -87 SHALL BE OBTAINED BY THE
CONTRACTOR AND TRANSMITTED TO THE OWNER.
B. GATE VALVES SHALL BE IRON BODY, BRONZED - MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O -RING STUFFING BOX
(AW WA C500) OR OF RESILIENT SEATED TYPE (AW WA C509 VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE
OF 2DO PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H.
9. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE)
CONFORMING TO AW WA C- 502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCH, TWO 2 -112
INCH HOSE NOZZLES WITH NATIONAL STANDARD THREADS 7 -1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLE WITH THE NEW
SEATTLE PATTERN 6 THREADS PER INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER
4.6263. HYDRANTS SHALL HAVE A 1-1/4 INCH PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
Know whars below.
Call before you dig.
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F -5110 OR
COMPRESSION TYPE SUCH AS CLOW MEOAWON: M & H 929, MUELLER
SUPER CENTURION 200, AND WATEROUS PACER WITH 6- MECHANICAL
JOINT INLET WITH LUGS. 5 -1/4' MAIN VALVE OPENING. TWO 2 -1/2'
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4' PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORE ADAPTOR.
4.875' SEATTLE THREAD X 5' STORZ. ATTACHED WITH 1/8' STAINLESS
STEEL CABLE. 1 -1/4' PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY- MOORE/PRESERVATW
PAINT No. 5780 -563 ON ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT, FIRE HYDRANT EXTENSION TO
MIN. 18- TO 20- BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
3' SIDEWALK THAT IS ADJACENT TO
CURB
4.875' X 5' STORZ
\ ® 5'x5'x K THIC CONCRETE PAID AROUND ARND
\ \\ /
HYDRANT. T. C C TO MATCH SIDEWALK
EXPANSION JOINT AT
BACK OF SIDEWALK /
CONCRETE �
THRUST BLOCK
16' X 8" x 4" MININUM
CONCRETE BEARING
BLOCK UNDER HYDRANT
O6
CUT
TWO -PIECE CAST IRON VALVE BOX WITH LUG
TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO.
STANDARD B' TOP SECTION WITH REGULAR BASE
SECTION LENGTH TO FIT. VALVE NUT EXTENSION
AS REQUIRED.
RAISED PAVEMENT MARKER TYPE 88 -A
STMSONITE TWO -WAY BLUE REFLECTIVE
BLOCKING
-MAIN LINE TEE. WITH 6' FLANGE SIDE CURET.
6" GATE VALVE (FL X MJ) AWWA C -509, RESILIENT SEAT
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2 -3/4' COR -TEN STEEL TIE RODS,
1 -1/4' WASHED DRAIN ROCK
r FLANGE. PLACE 8 MIL
FILM AROUND TOP AND SIDES OF
FIRE HYDRANT ASSEMBLY
JEL ALL GROUND
MIN 3' RADIUS
PUBLIC WORKS
DEPARTMENT
ONE MAN ROCK
I
6" CONCRETE PAD
LEVEL ALL GROUND
MIN 3' RADIUS
6' CONCRETE PAO
FILL
HYDRANT LOCATION IN CUT OR FILL
FIRE HYDRANT ASSEMBLY I SID' PLAN - 510.1
MARCH 2010
NOTE: ONLY WORK REQUIRED TO INSTALL THE CONCRETE PAD SHOWN BY THE DETAIL IS REQUIRED.
1 FIRE HYDRANT ASSEMBLY
10. THE TWO 2 -1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN
AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER
TIGHTNESS UNDER TEST PRESSURES.
11. THE 41NCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 41NCH SEATTLE THREAD X 51NCH STORZ. STORZADAPTER
SHALL BE FORGED AND /OR EXTRUDED 6061 -T6 ALUMINUM ALLOY HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO
LUGS AND TWO SET SCREWS 180 DEGREES APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER. STORZ CAP TO HAVE
SYNTHETIC MOLDED RUBBER GASKET, AND SHALL BE ATTACHED TO HYDRANTADAPTER WITH 1/8 INCH, COATED, STAINLESS STEEL,
AIRCRAFT CABLE.
12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43-655 SAFETY YELLOW OR APPROVED
EQUAL.
13. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, LATEST REVISION.
15. ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATERMAIN 12
INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS
ARE TO BE LOWERED TO CLEAR.
16. ALL WATERMAINS 61NCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE
"POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB/CU. FT. DENSITY FOAM WITH 90A DUROMETER
URETHANE RUBBER COATING ON THE REAR OF °PIG" ONLY.
17. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING
OPERATION.
18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN
ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL
PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER
LOST FROM THE MAIN SHALL NOT EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS &
SPECIFICATIONS 7- 11.3(11). THE LOSS IN PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST PERIOD.
ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM MINIMUM CONCENTRATION
19 ( )
CHLORINEIWATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE
METERED /INJECTED IN ACCORDANCE WITH SECTION 7- 11.3(12)E OR 7- 11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED
ABOVE.
20. A PRE- CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM OF FIVE (5) WORKING DAYS NOTICE IS
REQUIRED FOR SCHEDULING.
21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
22. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION.
NO.
REVISION
ACB 11/28/141 WJF
BY I DATE I APPR
WATER PLAN GENERAL NOTES Standard Plan No. 300
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE COY OF RENTON PUBLIC WORKS
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWASFANDARD SPECIFICATIONS, LATEST EDITION AS
AMENDED BY THE CITY OF RENTON. A SET OF COY APPROVED PLANS SHALL BE KEPT ATTHEJ08SITE WHENEVERCONSFRUCO Ni
IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THESTART OF CONSTRucnoN.THEOONIRACFOR
AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL
CALL 1300.424 -5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION.
3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND
"CATALOG CUTS' FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CRY OF RENTON PRIOR TO BRINGING ANY
MATERIALS ONI
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT UNED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AW WA C 151 AND
106. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL101NT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250
PER ANSI /AVIWA C310/A21.1032. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8- MRBIACK, TUBE -TYPE,
POLYETHYLENE PLASTIC PER AW WA C105 STANDARDS
5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMEIEROF 104NCH OR LESS
AND 48 INCHES FOR PIPE DIAMETER OF I24NCH AND LARGER. MAXIMUM COVER FOR ALLWATER MAINSSHALL BE 60 INCHES.
ANY DEVIATIONS MUST BE APPROVED BYTHE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTIMCONFUCT50CCUR,
THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS ANDTO PROVIDEMINM LRA COVER.
PIPE DEFLECTION SHALL NOT EXCEED ONE -HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALLTRFNOH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITYAS DETERMINED BYTHE MODIFIED PROCTORTEST
METHOD (Moo) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED
AREAS. ALL PIPE ZONE COMPACTION SHALL BE 951
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF
RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICALAND HOROONTALBENDS, FITTINGS
AND BASEOF HYDRANTS. MEGA-LUGS (OR SIMILAR PRODUCT) MAYBE REQUIRED ON ALL MECHANI CALJOINIS IN ADDDKINTO
CONCREM BLOCKING.
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PIRORTO BEING FLUSHED,
DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDERTHE
SUPERVISION OF A COY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALLSUPPLY, INSTALLAND REMOVE PLUGS,
CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT/ BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WEPTAP VALVETOAN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM - PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSUREAND PURTFYTESnNG.
8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP OARING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, RUSHW,
AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR
9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST IO WORKING
DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER
MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR
THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALLSURFACE MATERIALS, AND PROVIDESHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TOTHE EXISTING WATERSYSTEM. THE
CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION.
PUBLIC WORKS S- PLAN - 500.0
DEPARTMENT WATER PLAN GENERAL NOTES
MARCH 2010
23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS,
METER APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON.
24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE MADE BY
APPROVED WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION
AND MATERIALS ARE TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS.
25. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24) HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION.
THE CONTRACTOR, AS WELL AS THE ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS.
26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL
TIE -IN.
27. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING
COMPANY OF COLUMBUS OHIO, OR EQUAL, APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT.
28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY BE
SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUTTO
A MINIMUM DEPTH OF TWO (2) INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT.
29. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH
TO BE PLACED, TO CITY OF RENTON POLICY, WITHIN 10 DAYS. CALL
30. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE
SCHEDULE 80 PVC PIPE. SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS.
PERMIT SET
AS NOTED
A BRAUN
F. KATONA m_,,,,
W. FIERST F ,
�
FNR pEECM
I SOME WxwmXRr
W- 311504
Checked for b
Compliance to City Standards
P
x
F
0 F
I wARI
a
:mt
a
01 _
l
0
NAL
I
Nonce T A C O M A- SEATTLE - SPOKANE • TRI- CITIES
u1FMlXx 6TES W]Ipr9WL MWGE F
IRIS 4Y NO 9iX/S R9Gn 6
f8 FT
-z-7
O
�z
°n
=`a
a p
0 NEW WATER LINE
2215 North 30th Street, Suite 300
Taooma, WA 9840:
OLT M LIE PMFCI MXRR X ➢F ➢R 9FG
WN N Nor T
253.383.2422 TEL 253.3832572 FAX
www.ahN.00m WEB
Aoo1la Io RNT XMELTa -MW AYR IWMLL
A= z
VERTICAL CROSS(MJI FOR POLYPIGGING
3
O
W
ONE BLIND FLANGE ON TOP WON 21AP & 21PLUG
m
ONE BLIND FIANCE ON W70M
z
�
ONE (W) PLUG WITH Y TAP & 2" TEMPORARY BLOW -OFF
{
TEMPORARY BLOCK
(BY FORCES)
WE (F W/ CONC. BLOCK
WE (
1- COTE VALVES (Rata)
E VA vE
2- S (W) OR RO -MA COUPLINGS
I- MUG (MU) W/2-!M &TEMP.
BLOW OFF
TEMP. BLOCK
EXISTING WATER LINE
EXISTING WATER UNE
FINAL CONNECTION OCTAL
Fir IN_
AFTER ALL TESTING. CLEANING BY POLYPIG, AND DISINFECTION,
REMOVE TEMP. BLOCK & SLOW-CM & CONNECT
WITH SLEEVE (W) & D.I. SPOOLS
FINAL CONNECTION BY Cltt FORCES
EXISTING WATER UNE
PUBWC WORKS CONNECTION TO WATER MAIN CUT 'PLAN - 900.2
DEPARTMENT IN -LINE TEE & ONE VALVE MARCH 2010
CONNECTION TO WATER MAIN CUT
IN -LINE TEE AND ONE VALVE
WATER UTILITY NOTES AND SPECIFICATIONS
1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING /BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA STANDARDS AND SPECIFICATIONS,
AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED
PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE
APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT AT (425) 430 -7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911
SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY
THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48 -HOUR LOCATORS
800 - 4245555.
4. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE - CONSTRUCTION MEETING.
5. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND FOR HORIZONTAL CONTROL SHALL
BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS
DEPARTMENT. REFERENCE BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AW WA C110 AND C111 OR LATEST REVISION,
THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AW WA C104 OR LATEST REVISION. PIPE
JOINTS TO BE PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE
POLYETHYLENE WRAPPED PER ANSI /AW WA C105/A21.5 -93 STANDARDS.
7. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH
ANSI /AW WA C110/A21.10-67. CEMENT LINING SHALL BE INACCORDANCE WITH ANSI /AW WA C104/421/4 -90. IF FITTINGS ARE 3 TO 12 INCHES
IN DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER ANSI /AW WA C110- A21.10 -87 OR
ANSI/AW WA C153/A21.53 -94. THREE (3) INCH TO 12 INCH DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND /OR FLANGED
JOINTS, SHALL BE IN ACCORDANCE WITH ANSI /AW WA C1 101A21.10.87 OR A COMBINATION OF ANSI /AW WA C1 10/A21.10.87 AND ANSIAWWA
C153/A21.53 -94 SUCH THAT THE PORTION OF THE FITTING WITH A MECHANICAL JOINTS MAY BE WITH ANSI /AW WA C153/A21.5 3-94 AND
THAT PORTION OF THE FITTING WITH FLANGED JOINTS) SHALL BE IN ACCORDANCE WITH AW WA C11 O/A21.10 -87. ACCEPTANCE TESTING
IN ACCORDANCE WITH SECTION 53.53 OF ANSI /AW WA SECTION 10-4.3 OF ANSI /AW WA C11 O/A21.10 -87 SHALL BE OBTAINED BY THE
CONTRACTOR AND TRANSMITTED TO THE OWNER.
B. GATE VALVES SHALL BE IRON BODY, BRONZED - MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O -RING STUFFING BOX
(AW WA C500) OR OF RESILIENT SEATED TYPE (AW WA C509 VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE
OF 2DO PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H.
9. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE)
CONFORMING TO AW WA C- 502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCH, TWO 2 -112
INCH HOSE NOZZLES WITH NATIONAL STANDARD THREADS 7 -1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLE WITH THE NEW
SEATTLE PATTERN 6 THREADS PER INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER
4.6263. HYDRANTS SHALL HAVE A 1-1/4 INCH PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
Know whars below.
Call before you dig.
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F -5110 OR
COMPRESSION TYPE SUCH AS CLOW MEOAWON: M & H 929, MUELLER
SUPER CENTURION 200, AND WATEROUS PACER WITH 6- MECHANICAL
JOINT INLET WITH LUGS. 5 -1/4' MAIN VALVE OPENING. TWO 2 -1/2'
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4' PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORE ADAPTOR.
4.875' SEATTLE THREAD X 5' STORZ. ATTACHED WITH 1/8' STAINLESS
STEEL CABLE. 1 -1/4' PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY- MOORE/PRESERVATW
PAINT No. 5780 -563 ON ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT, FIRE HYDRANT EXTENSION TO
MIN. 18- TO 20- BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
3' SIDEWALK THAT IS ADJACENT TO
CURB
4.875' X 5' STORZ
\ ® 5'x5'x K THIC CONCRETE PAID AROUND ARND
\ \\ /
HYDRANT. T. C C TO MATCH SIDEWALK
EXPANSION JOINT AT
BACK OF SIDEWALK /
CONCRETE �
THRUST BLOCK
16' X 8" x 4" MININUM
CONCRETE BEARING
BLOCK UNDER HYDRANT
O6
CUT
TWO -PIECE CAST IRON VALVE BOX WITH LUG
TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO.
STANDARD B' TOP SECTION WITH REGULAR BASE
SECTION LENGTH TO FIT. VALVE NUT EXTENSION
AS REQUIRED.
RAISED PAVEMENT MARKER TYPE 88 -A
STMSONITE TWO -WAY BLUE REFLECTIVE
BLOCKING
-MAIN LINE TEE. WITH 6' FLANGE SIDE CURET.
6" GATE VALVE (FL X MJ) AWWA C -509, RESILIENT SEAT
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2 -3/4' COR -TEN STEEL TIE RODS,
1 -1/4' WASHED DRAIN ROCK
r FLANGE. PLACE 8 MIL
FILM AROUND TOP AND SIDES OF
FIRE HYDRANT ASSEMBLY
JEL ALL GROUND
MIN 3' RADIUS
PUBLIC WORKS
DEPARTMENT
ONE MAN ROCK
I
6" CONCRETE PAD
LEVEL ALL GROUND
MIN 3' RADIUS
6' CONCRETE PAO
FILL
HYDRANT LOCATION IN CUT OR FILL
FIRE HYDRANT ASSEMBLY I SID' PLAN - 510.1
MARCH 2010
NOTE: ONLY WORK REQUIRED TO INSTALL THE CONCRETE PAD SHOWN BY THE DETAIL IS REQUIRED.
1 FIRE HYDRANT ASSEMBLY
10. THE TWO 2 -1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN
AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER
TIGHTNESS UNDER TEST PRESSURES.
11. THE 41NCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 41NCH SEATTLE THREAD X 51NCH STORZ. STORZADAPTER
SHALL BE FORGED AND /OR EXTRUDED 6061 -T6 ALUMINUM ALLOY HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO
LUGS AND TWO SET SCREWS 180 DEGREES APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER. STORZ CAP TO HAVE
SYNTHETIC MOLDED RUBBER GASKET, AND SHALL BE ATTACHED TO HYDRANTADAPTER WITH 1/8 INCH, COATED, STAINLESS STEEL,
AIRCRAFT CABLE.
12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43-655 SAFETY YELLOW OR APPROVED
EQUAL.
13. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, LATEST REVISION.
15. ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATERMAIN 12
INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS
ARE TO BE LOWERED TO CLEAR.
16. ALL WATERMAINS 61NCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE
"POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB/CU. FT. DENSITY FOAM WITH 90A DUROMETER
URETHANE RUBBER COATING ON THE REAR OF °PIG" ONLY.
17. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING
OPERATION.
18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN
ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL
PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER
LOST FROM THE MAIN SHALL NOT EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS &
SPECIFICATIONS 7- 11.3(11). THE LOSS IN PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST PERIOD.
ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM MINIMUM CONCENTRATION
19 ( )
CHLORINEIWATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE
METERED /INJECTED IN ACCORDANCE WITH SECTION 7- 11.3(12)E OR 7- 11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED
ABOVE.
20. A PRE- CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM OF FIVE (5) WORKING DAYS NOTICE IS
REQUIRED FOR SCHEDULING.
21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
22. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION.
NO.
REVISION
ACB 11/28/141 WJF
BY I DATE I APPR
WATER PLAN GENERAL NOTES Standard Plan No. 300
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE COY OF RENTON PUBLIC WORKS
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWASFANDARD SPECIFICATIONS, LATEST EDITION AS
AMENDED BY THE CITY OF RENTON. A SET OF COY APPROVED PLANS SHALL BE KEPT ATTHEJ08SITE WHENEVERCONSFRUCO Ni
IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THESTART OF CONSTRucnoN.THEOONIRACFOR
AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL
CALL 1300.424 -5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION.
3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND
"CATALOG CUTS' FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CRY OF RENTON PRIOR TO BRINGING ANY
MATERIALS ONI
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT UNED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AW WA C 151 AND
106. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL101NT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250
PER ANSI /AVIWA C310/A21.1032. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8- MRBIACK, TUBE -TYPE,
POLYETHYLENE PLASTIC PER AW WA C105 STANDARDS
5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMEIEROF 104NCH OR LESS
AND 48 INCHES FOR PIPE DIAMETER OF I24NCH AND LARGER. MAXIMUM COVER FOR ALLWATER MAINSSHALL BE 60 INCHES.
ANY DEVIATIONS MUST BE APPROVED BYTHE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTIMCONFUCT50CCUR,
THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS ANDTO PROVIDEMINM LRA COVER.
PIPE DEFLECTION SHALL NOT EXCEED ONE -HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALLTRFNOH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITYAS DETERMINED BYTHE MODIFIED PROCTORTEST
METHOD (Moo) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED
AREAS. ALL PIPE ZONE COMPACTION SHALL BE 951
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF
RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICALAND HOROONTALBENDS, FITTINGS
AND BASEOF HYDRANTS. MEGA-LUGS (OR SIMILAR PRODUCT) MAYBE REQUIRED ON ALL MECHANI CALJOINIS IN ADDDKINTO
CONCREM BLOCKING.
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PIRORTO BEING FLUSHED,
DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDERTHE
SUPERVISION OF A COY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALLSUPPLY, INSTALLAND REMOVE PLUGS,
CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT/ BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WEPTAP VALVETOAN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM - PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSUREAND PURTFYTESnNG.
8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP OARING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, RUSHW,
AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR
9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST IO WORKING
DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER
MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR
THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALLSURFACE MATERIALS, AND PROVIDESHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TOTHE EXISTING WATERSYSTEM. THE
CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION.
PUBLIC WORKS S- PLAN - 500.0
DEPARTMENT WATER PLAN GENERAL NOTES
MARCH 2010
23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS,
METER APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON.
24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE MADE BY
APPROVED WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION
AND MATERIALS ARE TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS.
25. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24) HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION.
THE CONTRACTOR, AS WELL AS THE ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS.
26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL
TIE -IN.
27. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING
COMPANY OF COLUMBUS OHIO, OR EQUAL, APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT.
28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY BE
SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUTTO
A MINIMUM DEPTH OF TWO (2) INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT.
29. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH
TO BE PLACED, TO CITY OF RENTON POLICY, WITHIN 10 DAYS. CALL
30. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE
SCHEDULE 80 PVC PIPE. SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS.
PERMIT SET
AS NOTED
A BRAUN
F. KATONA m_,,,,
W. FIERST F ,
�
FNR pEECM
I SOME WxwmXRr
W- 311504
Checked for b
Compliance to City Standards
P
x
F
0 F
I wARI
a
:mt
a
01 _
l
0
NAL
I
Nonce T A C O M A- SEATTLE - SPOKANE • TRI- CITIES
u1FMlXx 6TES W]Ipr9WL MWGE F
IRIS 4Y NO 9iX/S R9Gn 6
-z-7
O
�z
°n
=`a
a p
INS NOMI
ON RM ME` °�' X°r °MINT'" fR01 `�
OIIR9V -HIS X N. MS WYXr Xq IH
2215 North 30th Street, Suite 300
Taooma, WA 9840:
OLT M LIE PMFCI MXRR X ➢F ➢R 9FG
WN N Nor T
253.383.2422 TEL 253.3832572 FAX
www.ahN.00m WEB
Aoo1la Io RNT XMELTa -MW AYR IWMLL
A= z
CITY OF RENTON ACADEMY AT SPRING GLEN ELEMENTARY 31 MARCH 2