HomeMy WebLinkAbout15-000011 (CA-Careage Facility) Staff CommentsPREAPPLICATION MEETING FOR
Careage Nursing Facility
PRE 15-000011
CITY OF RENTON
Department of Community & Economic Development
Planning Division
January 29, 2015
Contact Information:
Planner: Rocale Timmons, 425.430.7219
Public Works Plan Reviewer: Jan Illian, 425.430.7216
Fire Prevention Reviewer: Corey Thomas, 425.430.7024
Building Department Reviewer: Craig Burnell, 425.430.7290
Please retain this packet throughout the course of your project as a reference. Consider
giving copies of it to any engineers, architects, and contractors who work on the
project. You will need to submit a copy of this packet when you apply for land use
and/or environmental permits.
Pre-screening: When you have the project application ready for submittal, call and
schedule an appointment with the project manager to have it pre-screened before
making all of the required copies.
The pre-application meeting is informal and non-binding. The comments provided on
the proposal are based on the codes and policies in effect at the time of review. The
applicant is cautioned that the development regulations are regularly amended and the
proposal will be formally reviewed under the regulations in effect at the time of project
submittal. The information contained in this summary is subject to modification and/or
concurrence by official decision-makers (e.g., Hearing Examiner, Planning Director,
Development Services Director, Department of Community & Economic Development
Administrator, Public Works Administrator and City Council).
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\15-000011 (ca-careage
facility) (2).doc
DEPARTMENT OF
COMMUNITY AND ECONOMIC
DEVELOPMENT
M E M O R A N D U M
DATE: January 29, 2015
TO: Pre-Application File No. 15-000011
FROM: Rocale Timmons, Senior Planner
SUBJECT: Careage Skilled Nursing
10635 SE 174th St
General: We have completed a preliminary review of the pre-application for the above-
referenced development proposal. The following comments on development and permitting
issues are based on the pre-application submittals made to the City of Renton by the applicant
and the codes in effect on the date of review. The applicant is cautioned that information
contained in this summary may be subject to modification and/or concurrence by official
decision-makers (e.g., Hearing Examiner, Community & Economic Development Administrator,
Public Works Administrator, Planning Director, Development Services Director, and City
Council). Review comments may also need to be revised based on site planning and other
design changes required by City staff or made by the applicant. The applicant is encouraged to
review all applicable sections of the Renton Municipal Code. The Development Regulations are
available for purchase for $50.00 plus tax, from the Finance Division on the first floor of City Hall
or online at www.rentonwa.gov
Project Proposal: The subject property consists of one parcel located at the intersection of SE
174th St and 106th Place SE. The project site totals 76,615 square feet in area and is zoned
Commercial Arterial (CA). The proposal is to develop the site with a three story, approximately
55,000 square foot, post-operative rehabilitation center containing 60 beds. Parking is provided
within surface parking areas containing a total of 63 parking spaces. Access is proposed via
106th Pl SE with an additional connection to the neighboring commercial property to the east.
There are no critical areas located on site.
Current Use: Currently the site is vacant.
Development Standards: The project would be subject to RMC 4-2-120A, “Development
Standards for Commercial Zoning Designations” effective at the time of complete application
(noted as “CA Standards” herein).
Zoning: The property is located within the Commercial Corridor (CC) land use designation and
the Commercial Arterial (CA) zoning classification. Per RMC 4-11, a Convalescent Center is
defined as a facility licensed by the State for patients who are recovering health and strength
after illness or injury, or receiving long-term care for chronic conditions, disabilities, or terminal
illnesses. Facilities provide twenty-four (24) hour supervised nursing care and feature extended
treatment that is administered by a skilled nursing staff. Typically, residents do not live in
Careage Skilled Nursing
Page 2 of 6
January 29, 2015
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\15-000011 (ca-careage
facility) (2).doc
individual units and the facilities provide personal care, room, board, laundry service, and
organized activities. This definition does not include adult family homes, assisted living, group
homes II, medical institutions, and/or secure community transition facilities.
Convalescent Centers are permitted through an Administrative Conditional Use Permit in to CA
zone. The Conditional use Permit would be heard by the City’s Hearing Examiner if any other
land use entitlement requires a public hearing. The following criteria would be considered when
making a decision on the Conditional Use Permit:
1. Consistency with Plans and Regulations: The proposed use shall be compatible with
the general goals, objectives, policies and standards of the Comprehensive Plan, the
zoning regulations and any other plans, programs, maps or ordinances of the City of
Renton.
2. Appropriate Location: The proposed location shall not result in the detrimental
overconcentration of a particular use within the City or within the immediate area of the
proposed use. The proposed location shall be suited for the proposed use.
3. Effect on Adjacent Properties: The proposed use at the proposed location shall not
result in substantial or undue adverse effects on adjacent property.
4. Compatibility: The proposed use shall be compatible with the scale and character of
the neighborhood.
5. Parking: Adequate parking is, or will be made, available.
6. Traffic: The use shall ensure safe movement for vehicles and pedestrians and shall
mitigate potential effects on the surrounding area.
7. Noise, Light and Glare: Potential noise, light and glare impacts from the proposed use
shall be evaluated and mitigated.
8. Landscaping: Landscaping shall be provided in all areas not occupied by buildings,
paving, or critical areas. Additional landscaping may be required to buffer adjacent
properties from potentially adverse effects of the proposed use.
The property is also located within Urban Design District ‘D’, and therefore subject to
additional design elements. Proposals should have unique, identifiable design treatment in
terms of landscaping, building design, signage and street furniture.
Minimum Lot Size, Width and Depth – There are no minimum requirements for lot size, lot
width or depth within the CA zone at this location.
Lot Coverage – The CA zone allows a maximum building coverage of 65 percent, or 75 percent if
parking is provided within a building or within an on-site parking garage. The applicant did not
provide calculations for the footprint of the structure on site, therefore staff could not confirm
compliance with the lot coverage requirements of the zone. The applicant would be required,
at the time of formal land use application, to provide a lot coverage analysis.
Setbacks – Setbacks are the distance between the building and the property line or any private
access easement. Setback requirements in the CA zone are as follows: 10 feet minimum for the
front yard but may be reduced to zero feet through the Site Plan Review process provided blank
walls are not located within the reduced setback; a 15 foot maximum front yard setback; and no
rear or side yard setbacks unless the property abuts a residential zoned property.
Careage Skilled Nursing
Page 3 of 6
January 29, 2015
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\15-000011 (ca-careage
facility) (2).doc
While the front yard can be assessed from SE 174th St the Design District ‘D’ standards preclude
the placement of parking in between the street and the structure. The proposal would be
required to re-site the building remove parking between the building and all street frontages
which in turn would likely require the applicant to substantially reduce the setback from the
side yard along the street.
Gross Floor Area – There is no minimum requirements for gross floor area within the CA zone.
Building Height – The maximum building height that would be allowed in the CA zone is 50 feet
and 60 feet for mixed use structures. It appears the proposal would meet the height
requirements of the zone.
Screening – Screening must be provided for all surface-mounted and roof top utility and
mechanical equipment. The site plan application will need to include elevations and details for
the proposed methods of screening.
Refuse and Recycling Areas – Refuse and recycling areas need to meet the requirements of RMC
4-4-090, “Refuse and Recyclables Standards” (enclosed). For non-residential developments a
minimum of 3 square feet per dwelling unit is required for recyclable deposit areas and a
minimum of 6 square feet per dwelling unit is required for refuse deposit areas.
Properties: Outdoor refuse and recyclables deposit areas and collection points shall not be
located within fifty feet (50') of a property zoned RC, R-1, R-4, R-8, R-10, R-14, or RM.
Landscaping – All portions of the development area not covered by structures, required parking,
access, circulation or service areas, must be landscaped with native, drought-resistant
vegetative cover. The minimum on-site landscape width required along street frontages is 10
feet, except where reduced through the site plan development review process.
Surface parking lots with 51-99 parking stalls shall be landscaped with an additional 25 square
feet of landscaping per parking space.
Surface parking lots with more than 50 stalls shall provide a minimum of 25 square feet of
landscaping per parking space. Based on the total number of surface parking stalls the
applicant would be required to provide interior landscaping in the amount of 1,575 square feet
of landscaping in order to buffer the parking. Please refer to landscape regulations (RMC 4-4-
070 and RMC 4-4-080F.7) for further general and specific landscape requirements (enclosed).
Tree Preservation – A Tree Retention/ Land Clearing ( Tree Inventory) Plan along with a tree
retention worksheet shall be provided with the formal land use application. The tree retention
plan must show preservation of at least 10 percent (10 %) of significant trees, and indicate how
proposed building footprints would be sited to accommodate preservation of significant trees
that would be retained. The Administrator may authorize the planting of replacement trees on
the site if it can be demonstrated to the Administrator' s satisfaction that an insufficient number
of trees can be retained.
Significant trees shall be retained in the following priority order:
Priority One: Landmark trees; significant trees that form a continuous canopy; significant trees
on slopes greater than twenty percent (20%); Significant trees adjacent to critical areas and their
associated buffers; and Significant trees over sixty feet (60') in height or greater than eighteen
inches ( 18") caliper.
Careage Skilled Nursing
Page 4 of 6
January 29, 2015
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\15-000011 (ca-careage
facility) (2).doc
Priority Two: Healthy tree groupings whose associated undergrowth can be preserved; Other
significant native evergreen or deciduous trees; and Other significant non- native trees.
Priority Three: Alders and cottonwoods shall be retained when all other trees have been
evaluated for retention and are not able to be retained, unless the alders and/ or cottonwoods
are used as part of an approved enhancement project within a critical area or its buffer.
The Administrator may require independent review of any land use application that involves
tree removal and land clearing at the City' s discretion.
Fences – If the applicant intends to install any fences as part of this project, the location must be
designated on the landscape plan. A fence detail should also be included on the plan as well.
Parking – The following ratios would be applicable to the site:
Use Square Footage of Use Ratio Required Spaces
Convalescent
Center
60 beds A minimum and maximum
of 1 for every 2 employees
plus 1 for every 3 beds.
20 + Unknown
The proposal includes a total of 63 surface parking stalls. It is unclear the number of
employees anticipated for the facility. The applicant would be required to provide this
information at the time of formal land use application in order to calculate the number of
stalls required for the project.
Where practical difficulties exist in meeting parking requirements, the applicant may request a
modification from these standards. The applicant will be required at the time of formal land use
application to provide detailed parking information (i.e. stall and drive aisle dimensions) and
calculations of the subject site and the overall campus use.
It should be noted that the parking regulations specify standard stall dimensions. Surface
parking stalls must be a minimum of 9 feet x 20 feet, compact dimensions of 8½ feet x 16 feet,
and parallel stall dimensions of 9 feet x 23 feet; compact surface parking spaces shall not
account for more than 30 percent of the spaces in the surface parking lots.
ADA accessible stalls must be a minimum of 8 feet in width by 20 feet in length, with an adjacent
access aisle of 8 feet in width for van accessible spaces. The appropriate amount of ADA
accessible stalls based on the total number of spaces must be provided.
Additionally, the proposal would need to be revised in order to provide bicycle parking based
on 10 % of the required number of parking stalls.
Where practical difficulties exist in meeting bicycle parking requirements, the applicant may
request a modification from these standards.
Access – Driveway widths are limited by the driveway standards, in RMC 4-4080I.
Pedestrian Access – A pedestrian connection shall be provided from all public entrances to the
street, in order to provide direct, clear and separate pedestrian walks from sidewalks to building
entries and internally from buildings to abutting properties.
Building Design Standards – Compliance with Urban Design Regulations, District ‘D’, is
required. See the attached checklist and Renton Municipal Code section 4-3-100. The following
bullets are a few of the standards outlined in the regulations.
Careage Skilled Nursing
Page 5 of 6
January 29, 2015
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\15-000011 (ca-careage
facility) (2).doc
A primary entrance of each building shall be located on the facade facing a street, shall
be prominent, visible from the street, connected by a walkway to the public sidewalk,
and include human-scale elements.
Parking shall be located so that no surface parking is located between a building and
the front property line, or the building and side property line, on the street side of a
corner lot.
The number of driveways and curb cuts shall be minimized, so that pedestrian
circulation along the sidewalk is minimally impeded.
Amenities such as outdoor group seating, benches, transit shelters, fountains, and
public art shall be provided.
All buildings and developments with over thirty thousand (30,000) square feet of
nonresidential uses shall provide pedestrian-oriented space. The pedestrian-oriented
space shall be provided according to the following formula: 1% of the site area + 1% of
the gross building area, at minimum.
All building facades shall include modulation or articulation at intervals of no more than
forty feet (40').
Modulations shall be a minimum of two feet (2') deep, sixteen feet (16') in height, and
eight feet (8') in width.
On any facade visible to the public, transparent windows and/or doors are required to
comprise at least fifty percent (50%) of the portion of the ground floor facade that is
between four feet (4') and eight feet (8') above ground (as measured on the true
elevation).
Buildings shall use at least one of the following elements to create varied and
interesting roof profiles (see illustration, subsection RMC 4-3-100.I5f):
(a) Extended parapets;
(b) Feature elements projecting above parapets;
(c) Projected cornices;
(d) Pitched or sloped roofs.
Buildings shall employ material variations such as colors, brick or metal banding,
patterns, or textural changes.
Critical Areas
There appears to be no critical areas on site. If there is any indication of critical areas on the
site, this must be disclosed to the City prior to development and appropriate studies must be
undertaken.
It appears Coal Mines are in the vicinity of the site. Whenever proposed development is
abutting or adjacent sites within fifty feet (50') of the subject site, special geotechnical studies
by qualified professionals shall be required, including a coal mine assessment. The applicant
would be required to demonstrate the proposal will not increase the threat of the geological
hazard to adjacent or abutting properties beyond pre-development conditions; the proposal will
not adversely impact other critical areas; and the development can be safely accommodated on
the site.
Environmental Review
Environmental (SEPA) Review is required for projects nine residential units or greater, or on
sites that contain critical areas. Therefore SEPA would be required.
Permit Requirements
Careage Skilled Nursing
Page 6 of 6
January 29, 2015
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\15-000011 (ca-careage
facility) (2).doc
Given the proposal exceeds 25,000 square feet of gross floor area (nonresidential) in the CA
zone a Hearing Examiner Site Plan approval would be required. Additionally, the proposal would
require a Conditional Use Permit and Environmental (SEPA) Review. There all may be
modifications required (parking, bicycle parking, etc.).
All land use permits would be processed within an estimated time frame of 12 weeks. The
application fee for SEPA Review (Environmental Checklist) is $1,000 and the Hearing Examiner
Site Plan Review Fee is $2,500 and the Conditional Use Permit fee is $1,500. All modifications
are going to be $150 each.
A 3% technology fee would also be assessed at the time of land use application. Detailed
information regarding the land use application submittal is provided in the attached handouts.
In addition to the required land use permits, separate construction and building permits would
be required. The review of these permits may occur concurrently with the review of the land
use permits, but cannot be issued prior to the completion of any appeal periods.
Impact Mitigation Fees: In addition to the applicable building and construction fees, the
following impact fees would be required prior to the issuance of building permits:
A Fire Mitigation fee currently assessed at $3.88 per new square foot of medical care
facility. This rate would increase to $5.56 on January 1, 2016.
A Transportation Mitigation Fee currently assessed at $3.91.14 per bed and would
increase to $494.92 per bed on January 1, 2016. Alternatively, the fee would be
calculated per the ITE manual.
A handout listing all of the City’s Development related fees is attached for your review.
Note: When formal application materials are complete, the applicant must make an
appointment with the project manager, Rocale Timmons, to have one copy of the
application materials pre-screened at the 6th floor public counter prior to submitting
the complete application package. Rocale Timmons may be contacted at (425) 430-
7219 or rtimmons@rentonwa.gov.
FIRE & EMERGENCY SERVICES DEPARTMENT
M E M O R A N D U M
DATE: January 29, 2015
TO: Rocale Timmons, Senior Planner
FROM: Corey Thomas, Plans Review Inspector
SUBJECT: Careage Nursing Facility
1. The preliminary fire flow is 2,000 gpm. A minimum of two fire hydrants
are required. One within 150-feet and one within 300-feet of the building.
Maximum hydrant spacing of 300-feet on center shall also be met. One
hydrant is required within 50-feet of the fire department connection.
Existing hydrants may be counted towards the requirements as long as they
meet current codes and distance requirements, including 5-inch storz
fittings, which they don’t appear to have. A water availability certificate is
required from Soos Creek Water and Sewer District.
2. Fire impact fees are applicable at the rate of $3.88 per square foot of
space. This fee is paid at time of building permit issuance.
3. Approved fire sprinkler and fire alarm systems are required thro ughout
the building. Dry standpipes are required in all stairways. Kitchen hood fire
suppression systems required. Separate plans and permits required by the
fire department. Direct outside access is required to the fire sprinkler riser
room. Fully addressable and full detection is required for the fire alarm
system.
4. Fire department apparatus access roadways are required within 150 -
feet of all points on the building. Fire lane signage required for the on site
roadway. Required turning radius are 25-feet inside and 45-feet outside.
Roadways shall be a minimum of 20-feet wide. Roadways shall support a
minimum of a 30-ton vehicle and 75-psi point loading.
5. An electronic site plan is required prior to occupancy for pre-fire
planning purposes.
6. All buildings equipped with an elevator in the City of Renton are
required to have at least one elevator meet the size requirements for a
bariatric size stretcher. Car size shall accommodate a minimum of a 40 -inch
by 84-inch stretcher.
Careage Nursing Facility
Page 2 of 2
January 29, 2015
h:\ced\planning\current planning\preapps\2015 preapps\15-000011.rocale\fire comments.docx
7. The building shall comply with the City of Renton Emergency Radio
Coverage ordinance. Testing shall verify both incoming and outgoing
minimum emergency radio signal coverage. If inadequate, the building shall
be enhanced with amplification equipment in order to meet minimum
coverage. Separate plans and permits are required for any proposed
amplification systems.
8. Standy power is required as follows per city ordinance. Standy power
shall be provided to power all heating and refrigeration, communication
and alarm systems, ventilation systems, emergency lighting, patient care
related circuits and at least one elevator.